Download Zipped Amended WordPerfect HB0045.ZIP
[Introduced][Status][Bill Documents][Fiscal Note][Bills Directory]
H.B. 45
This document includes House Committee Amendments incorporated into the bill on Thu,
Jan 28, 2010 at 11:24 AM by lerror. -->
1
STATE CONSTRUCTION CODE ADOPTION
2
2010 GENERAL SESSION
3
STATE OF UTAH
4
Chief Sponsor: Michael T. Morley
5
Senate Sponsor:
J. Stuart Adams
6
7
LONG TITLE
8
Committee Note:
9
The Business and Labor Interim Committee recommended this bill.
10
General Description:
11
This bill adopts the State Construction Code in accordance with the Utah Uniform
12
Building Standards Act.
13
Highlighted Provisions:
14
This bill:
15
. includes general provisions; and
16
. adopts the state construction code.
17
Monies Appropriated in this Bill:
18
None
19
Other Special Clauses:
20
This bill takes effect on July 1, 2010.
21
Utah Code Sections Affected:
22
ENACTS UNCODIFIED MATERIAL
23
24
Be it enacted by the Legislature of the state of Utah:
25
Section 1. Title -- Definitions -- General Provisions.
26
(1) This bill is known as the "State Construction Code Adoption Act."
27
(2) As used in this bill:
28
(a) "Division" means the Division of Occupational and Professional Licensing created
29
in Utah Code, Section
58-1-103
.
30
(b) "State Construction Code" means the code adopted under Section 2 of this bill.
31
(c) "Utah Code" means the Utah Code Annotated (1953), as amended.
32
(3) As part of the division's compliance with Utah Code, Section 58-56-6, the division
33
may modify the format of the state construction code to provide accessibility to users of the
34
State Construction Code.
35
Section 2. State Construction Code adopted.
36
In accordance with Utah Code, Title 58, Chapter 56, Utah Uniform Building Standards
37
Act, the Legislature, repeals the state construction code in effect on June 30, 2010, and adopts
38
the following as the State Construction Code effective July 1, 2010:
39
State Construction Code
40
Part 1. General Provisions
41
Section 101. Specific editions of construction codes of a nationally recognized code
42
authority adopted -- Scope of application.
43
(1) (a) Subject to the limitations contained in Subsections (4), (5), and (6), the
44
following construction codes are incorporated by reference, and together with the amendments
45
specified under this bill, are the construction standards to be applied to building construction,
46
alteration, remodeling, and repair, and in the regulation of building construction, alteration,
47
remodeling and repair in the state:
48
(i) the 2009 edition of the International Building Code (IBC), including Appendix J,
49
issued by the International Code Council;
50
(ii) the 2008 edition of the National Electrical Code (NEC), issued by the National Fire
51
Protection Association;
52
(iii) the 2009 edition of the International Plumbing Code (IPC), issued by the
53
International Code Council;
54
(iv) the 2009 edition of the International Mechanical Code (IMC), issued by the
55
International Code Council;
56
(v) the 2009 edition of the International Residential Code (IRC), issued by the
57
International Code Council;
58
(vi) the 2009 edition of the International Energy Conservation Code (IECC), issued by
59
the International Code Council;
60
(vii) the 2009 edition of the International Fuel Gas Code (IFGC), issued by the
61
International Code Council;
62
(viii) subject to Subsection (3), the Federal Manufactured Housing Construction and
63
Safety Standards Act (HUD Code), as issued by the Department of Housing and Urban
64
Development and published in 24 C.F.R. Parts 3280 and 3282 (as revised April 1, 1990);
65
(ix) subject to Subsection (2), Appendix E of the 2009 edition of the International
66
Residential Code, issued by the International Code Council; and
67
(x) subject to Subsection (2), the 2005 edition of the NFPA 225 Model Manufactured
68
Home Installation Standard, issued by the National Fire Protection Association.
69
(b) Consistent with Title 65A, Chapter 8, Management of Forest Lands and Fire
70
Control, the Legislature adopts the 2006 edition of the Utah Wildland Urban Interface Code
71
(UWUI) issued by the International Code Council, with the alternatives or amendments
72
approved by the Utah Division of Forestry, as a construction code that may be adopted by a
73
local compliance agency by local ordinance or other similar action as a local amendment to the
74
codes listed in this Subsection (1).
75
(2) The following are the installation standards for manufactured housing for new
76
installations or for existing manufactured or mobile homes that are subject to relocation,
77
building alteration, remodeling, or rehabilitation in the state:
78
(a) The manufacturer's installation instruction for the model being installed is the
79
primary standard.
80
(b) If the manufacturer's installation instruction for the model being installed is not
81
available or is incomplete, the following standards apply:
82
(i) Appendix E of the 2009 edition of the IRC, as issued by the International Code
83
Council for installations defined in Section AE101 of Appendix E; or
84
(ii) if an installation is beyond the scope of the 2009 edition of the IRC as defined in
85
Section AE101 of Appendix E, the 2005 edition of the NFPA 225 Model Manufactured Home
86
Installation Standard, issued by the National Fire Protection Association.
87
(c) A manufacturer, dealer, or homeowner is permitted to design for unusual
88
installation of a manufactured home not provided for in the manufacturer's standard installation
89
instruction Appendix E of the 2009 edition of the IRC, or the 2005 edition of the NFPA 225, if
90
the design is approved in writing by a professional engineer or architect licensed in Utah.
91
(d) For a mobile home built before June 15, 1976, the home shall also comply with the
92
additional installation and safety requirements specified in State Construction Code, Section
93
208.
94
(3) Pursuant to the HUD Code Section 604(d), a manufactured home may be installed
95
in the state that does not meet the local snow load requirements as specified in State
96
Construction Code, Section 202, except that the manufactured home shall have a protective
97
structure built over the home that meets the IRC and the snow load requirements under State
98
Construction Code, Section 202.
99
(4) To the extent that a construction code adopted under Subsection (1) establishes a
100
local administrative function or establishes a method of appeal which pursuant to Utah Code,
101
Section 58-56-8 is designated to be established by the compliance agency:
102
(a) that provision of the construction code is not included in the State Construction
103
Code; and
104
(b) a compliance agency may establish provisions to establish a local administrative
105
function or a method of appeal.
106
(5) (a) To the extent that a construction code adopted under Subsection (1) establishes
107
a provision, standard, or reference to another code that by state statute is designated to be
108
established or administered by another state agency, or a local city, town, or county
109
jurisdiction:
110
(i) that provision of the construction code is not included in the State Construction
111
Code; and
112
(ii) the agency or local government has authority over that provision of the construction
113
code.
114
(b) Provisions excluded under this Subsection (5) include:
115
(i) the International Property Maintenance Code;
116
(ii) the International Private Sewage Disposal Code, authority over which is reserved to
117
the Department of Health and the Department of Environmental Quality;
118
(iii) the International Fire Code, authority over which is reserved to the Utah Fire
119
Prevention Board, pursuant to Utah Code, Section
53-7-106
;
120
(iv) a day care provision that is in conflict with Utah Code, Title 26, Chapter 39, Utah
121
Child Care Licensing Act, authority over which is designated to the Utah Department of
122
Health; and
123
(v) a wildland urban interface provision that goes beyond the authority under Utah
124
Code, Section 58-56-4, for the State Construction Code, authority over which is designated to
125
the Utah Division of Forestry or to a local compliance agency.
126
(6) If a construction code adopted under Subsection (1) establishes a provision that
127
exceeds the scope described in Title 58, Chapter 56, Utah Uniform Building Standards Act, to
128
the extent the scope is exceeded, the provision is not included in the State Construction Code.
129
Part 2. Statewide Amendments
130
Section 201. Statewide amendments to the IBC.
131
The following are adopted as amendments to the IBC to be applicable statewide:
132
(1) IBC, Section 106, is deleted.
133
(2) (a) In IBC, Section 110, a new section is added as follows: "110.3.5,
134
Weather-resistant exterior wall envelope. An inspection shall be made of the weather-resistant
135
exterior wall envelope as required by Section 1403.2, and flashing as required by Section
136
1405.4 to prevent water from entering the weather-resistive barrier."
137
(b) The remaining sections of IBC, Section 110, are renumbered as follows: 110.3.6,
138
Lath or gypsum board inspection; 110.3.7, Fire-and smoke-resistant penetrations; 110.3.8
139
Energy efficiency inspections; 110.3.9 Other inspections; 110.3.10 Special inspections;
140
110.3.11 Final inspection.
141
(3) IBC, Section 115.1, is deleted and replaced with the following: "115.1 Authority.
142
Whenever the building official finds any work regulated by this code being performed in a
143
manner either contrary to the provisions of this code or other pertinent laws or ordinances or
144
dangerous or unsafe, the building official is authorized to stop work."
145
(4) In IBC, Section 202, the definition for "Assisted Living Facility" is deleted and
146
replaced with the following: "ASSISTED LIVING FACILITY. See Section 308.1.1."
147
(5) In IBC, Section 202, the definition for "Child Care Facilities" is deleted and
148
replaced with the following: "CHILD CARE FACILITIES. See Section 308.3.1."
149
(6) In the list in IBC, Section 304.1, "Ambulatory health care facilities" is deleted and
150
replaced with "Ambulatory health care facilities with four or fewer surgical operating rooms."
151
(7) IBC, Section 305.2, is deleted and replaced with the following: "305.2 Day care.
152
The use of a building or structure, or portion thereof, for educational, supervision, child day
153
care centers, or personal care services of more than four children shall be classified as a Group
154
E occupancy. See Section 424 for special requirements for Group E child day care centers.
155
Exception: Areas used for child day care purposes with a Residential Certificate or a Family
156
License, as defined in Utah Administrative Code, R430-90 Licensed Family Child Care, may
157
be located in a Group R-2 or R-3 occupancy as provided in Section 310.1 or shall comply with
158
the International Residential Code in accordance with Section 101.2. Areas used for Hourly
159
Child Care Centers, as defined in Utah Administrative Code, R430-60, or Out of School Time
160
Programs, as defined in Utah Administrative Code, R430-70, may be classified as accessory
161
occupancies."
162
(8) In IBC, Section 308, the following definitions are added: "308.1.1 Definitions. The
163
following words and terms shall, for the purposes of this section and as used elsewhere in this
164
code, have the meanings shown herein.
165
TYPE I ASSISTED LIVING FACILITY. A residential facility licensed by the Utah
166
Department of Health that provides a protected living arrangement for ambulatory,
167
non-restrained persons who are capable of achieving mobility sufficient to exit the facility
168
without the assistance of another person.
169
TYPE II ASSISTED LIVING FACILITY. A residential facility licensed by the Utah
170
Department of Health that provides an array of coordinated supportive personal and health care
171
services to residents who meet the definition of semi-independent.
172
SEMI-INDEPENDENT. A person who is:
173
A. Physically disabled but able to direct his or her own care; or
174
B. Cognitively impaired or physically disabled but able to evacuate from the facility with the
175
physical assistance of one person.
176
RESIDENTIAL TREATMENT/SUPPORT ASSISTED LIVING FACILITY. A residential
177
treatment/support assisted living facility which creates a group living environment for four or
178
more residents licensed by the Utah Department of Human Services, and provides a protected
179
living arrangement for ambulatory, non-restrained persons who are capable of achieving
180
mobility sufficient to exit the facility without the physical assistance of another person."
181
(9) In IBC, Section 308.2, the words "Assisted living facilities" are deleted and
182
replaced with "Type I Assisted living facilities."
183
(10) IBC, Section 308.3, is deleted and replaced with the following: "308.3 Group I-2.
184
This occupancy shall include buildings and structures used for medical, surgical, psychiatric,
185
nursing, or custodial care on a 24-hour basis of more than three persons who are not capable of
186
self-preservation. This group shall include, but not be limited to the following: hospitals,
187
nursing homes (both intermediate care facilities and skilled nursing facilities), mental hospitals,
188
detoxification facilities, ambulatory surgical centers with five or more operating rooms where
189
care is less than 24 hours, and type II assisted living facilities. Type II assisted living facilities
190
with five or fewer persons shall be classified as a Group R-4. Type II assisted living facilities
191
as defined in 308.1.1 with at least six and not more than sixteen residents shall be classified as
192
a Group I-1 facility."
193
(11) In IBC, Section 308.3.1, the definition for "CHILD CARE FACILITIES" is
194
deleted and replaced with the following: "CHILD CARE FACILITIES. A child care facility, as
195
licensed by the Department of Human Services in Utah Administrative Code, R501, that
196
provides care on a 24-hour basis to more than four children 2 1/2 years of age or less shall be
197
classified as Group I-2."
198
(12) IBC, Section 308.5, is deleted and replaced with the following: "308.5 Group I-4,
199
day care facilities. This group shall include buildings and structures occupied by persons of any
200
age who receive custodial care less than 24 hours by individuals other than parents or
201
guardians, relatives by blood, marriage, or adoption, and in a place other than the home of the
202
person cared for. A facility such as the above with four or fewer persons shall be classified as
203
an R-3 or shall comply with the International Residential Code in accordance with Section
204
101.2. Places of worship during religious functions and Group E child day care centers are not
205
included."
206
(13) IBC, Section 308.5.2, is deleted.
207
(14) In IBC, Section 310.1, in the subsection designated as R-1, at the end of the
208
sentence beginning with "Congregate living facilities" the following is added: "or shall comply
209
with the International Residential Code."
210
(15) In IBC, Section 310.1, in the subsection designated as R-2, at the end of the
211
sentence beginning with "Congregate living facilities" the following is added: "or shall comply
212
with the International Residential Code."
213
(16) In IBC, Section 310.1, the following is added at the end of the subsection
214
designated as R-3: "Areas used for day care purposes may be located in a residential dwelling
215
unit under all of the following conditions:
216
1. Compliance with the Utah Administrative Code, R710-8, Day Care Rules, as enacted under
217
the authority of the Utah Fire Prevention Board.
218
2. Use is approved by the State Department of Health, as enacted under the authority of the
219
Utah Code, Title 26, Chapter 39, Utah Child Care Licensing Act, and in any of the following
220
categories:
221
a. Utah Administrative Code, R430-50, Residential Certificate Child Care.
222
b. Utah Administrative Code, R430-90, Licensed Family Child Care.
223
3. Compliance with all zoning regulations of the local regulator."
224
(17) In IBC, Section 310.1, the subsection designated as R-4 is deleted and replaced
225
with the following: "R-4: Residential occupancies shall include buildings arranged for
226
occupancy as Type I Assisted Living Facilities or Residential Treatment/Support Assisted
227
Living Facilities including more than five but not more than 16 residents, excluding staff.
228
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3
229
except as otherwise provided for in this code."
230
(18) In IBC, Section 310.2, the definition for "Residential Care/Assisted Living
231
Facilities" is deleted and replaced with the following: "Assisted Living Facilities, see Section
232
308.1.1".
233
(19) Section IBC, 403.5.5, is deleted.
234
(20) In IBC, Section 422.1, the words "Sections 422.1 to 422.6" are replaced with
235
"Sections 422.1 to 422.7".
236
(21) In IBC, Section 422, a new section is added as follows: "422.7 Separation.
237
Occupancies classified as Group B Ambulatory Health Care Facilities shall be separated from
238
all surrounding tenants and occupancies in accordance with Table 508.4 but not less than
239
one-hour fire barrier when the suite is capable of providing care for four or more care recipients
240
who are incapable of self preservation."
241
(22) A new IBC, Section 424, is added as follows: "Section 424 Group E Child Day
242
Care Centers. Group E child day care centers shall comply with Section 424.
243
424.1 Location at grade. Group E child day care centers shall be located at the level of exit
244
discharge.
245
Exception: Child day care spaces for children over the age of 24 months may be located on the
246
second floor of buildings equipped with automatic fire protection throughout and an automatic
247
fire alarm system.
248
424.2 Egress. All Group E child day care spaces with an occupant load of more than 10 shall
249
have a second means of egress. If the second means of egress is not an exit door leading
250
directly to the exterior, the room shall have an emergency escape and rescue window
251
complying with Section 1029.
252
424.3 All Group E Child Day Care Centers shall comply with Utah Administrative Code,
253
R430-100 Child Care Centers."
254
(23) In IBC, Section 504.2, a new section is added as follows: "504.2.1
255
Notwithstanding the exceptions to Section 504.2, Group I-2 Assisted Living Facilities shall be
256
allowed to be two stories of Type V-A construction when all of the following apply:
257
1. All secured units are located at the level of exit discharge in compliance with Section
258
1008.1.9.3 as amended;
259
2. The total combined area of both stories shall not exceed the total allowable area for a
260
one-story building; and
261
3. All other provisions that apply in Section 407 have been provided."
262
(24) In IBC, Table 508.4, a new footnote g is added as follows: "g. See Section 422.7
263
for additional requirements of Group B Ambulatory Health Care Facilities."
264
(25) In IBC, Section 707.5.1, a new exception 4 is added as follows: "4. Group B
265
Ambulatory Health Care Facilities."
266
(26) In IBC, Section (F)902, the definition for record drawings is deleted and replaced
267
with the following: "(F)RECORD DRAWINGS. Drawings ("as builts") that document all
268
aspects of a fire protection system as installed."
269
(27) In IBC, Section (F)903.2.2, the words "all fire areas" are deleted and replaced with
270
"buildings".
271
(28) IBC, Section (F)903.2.4, condition 2, is deleted and replaced with the following:
272
"2. A Group F-1 fire area is located more than three stories above the lowest level of fire
273
department vehicle access."
274
(29) IBC, Section (F)903.2.7, condition 2, is deleted and replaced with the following:
275
"2. A Group M fire area is located more than three stories above the lowest level of fire
276
department vehicle access."
277
(30) IBC, Section (F)903.2.8, is deleted and replaced with the following: "(F)903.2.8
278
Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be
279
provided throughout all buildings with a Group R fire area.
280
Exceptions:
281
1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses)
282
constructed in accordance with the International Residential Code For One- and Two-Family
283
Dwellings.
284
2. Group R-4 fire areas not more than 4,500 gross square feet and not containing more than 16
285
residents, provided the building is equipped throughout with an approved fire alarm system that
286
is interconnected and receives its primary power from the building wiring and a commercial
287
power system."
288
(31) IBC, Section (F)903.2.9, condition 2, is deleted and replaced with the following:
289
"2. A Group S-1 fire area is located more than three stories above the lowest level of fire
290
department vehicle access."
291
(32) IBC, Section (F)903.2.10, is deleted and replaced with the following: "(F)903.2.10
292
Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as
293
parking garages in accordance with Section 406.2 or where located beneath other groups.
294
Exception 1: Parking garages of less than 5,000 square feet (464 m2) accessory to Group R-3
295
occupancies.
296
Exception 2: Open parking garages not located beneath other groups if one of the following
297
conditions is met:
298
a. Access is provided for fire fighting operations to within 150 feet (45,720 mm) of all
299
portions of the parking garage as measured from the approved fire department vehicle access;
300
or
301
b. Class I standpipes are installed throughout the parking garage."
302
(33) In IBC, Section (F)903.2.10.1, the last clause "where the fire area exceeds 5,000
303
square feet (464 m2)" is deleted.
304
(34) IBC, Section (F)904.11, is deleted and replaced with the following: "(F)904.11
305
Commercial cooking systems. The automatic fire-extinguishing system for commercial
306
cooking systems shall be of a type recognized for protection of commercial cooking equipment
307
and exhaust systems. Pre-engineered automatic extinguishing systems shall be tested in
308
accordance with UL 300 and listed and labeled for the intended application. The system shall
309
be installed in accordance with this code, its listing and the manufacturer's installation
310
instructions.
311
Exception: Factory-built commercial cooking recirculating systems that are tested in
312
accordance with UL 710B and listed, labeled, and installed in accordance with Section 304.1 of
313
the International Mechanical Code."
314
(35) IBC, Subsections (F)904.11.3, (F)904.11.3.1, (F)904.11.4, and (F)904.11.4.1, are
315
deleted.
316
(36) A new IBC, Section (F)907.9, is added as follows: "Section (F)907.9 Carbon
317
monoxide alarms. Carbon monoxide alarms shall be installed on each habitable level of a
318
dwelling unit or sleeping unit in Groups R-2, R-3, R-4, and I-1 equipped with fuel burning
319
appliances and in dwelling units that have attached garages. If more than one carbon monoxide
320
alarm is required, they shall be interconnected as required in the International Fire Code,
321
Chapter 9, Section 907.2.11.3. In new construction, carbon monoxide alarms shall receive their
322
primary power as required in the International Fire Code, Chapter 9, Section 907.2.11.4. Listed
323
single- and multiple-station carbon monoxide alarms shall comply with UL 2034 and shall be
324
installed in accordance with the provisions of this code and NFPA 720."
325
(37) In IBC, Section 1008.1.9.6:
326
(a) the words "Group I-1 and" are added in the title and in the first sentence before the
327
words "Group I-2";
328
(b) the word "delayed" is deleted throughout and replaced with "controlled"; and
329
(c) the last sentence before the numbered subsections 1 through 6 is deleted.
330
(38) In IBC, Section 1009.4.2, exception 5 is deleted and replaced with the following:
331
"5. In Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group
332
U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual
333
dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches (203
334
mm) and the minimum tread depth shall be 9 inches (229 mm). The minimum winder tread
335
depth at the walk line shall be 10 inches (254 mm), and the minimum winder tread depth shall
336
be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25
337
inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less
338
than 10 inches (254 mm)."
339
(39) In IBC, Section 1009.12, a new exception 6 is added as follows: "6. In
340
occupancies in Group R-3, as applicable in Section 101.2 and in occupancies in Group U,
341
which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails
342
shall be provided on at least one side of stairways consisting of four or more risers."
343
(40) In IBC, Section 1013.2, the words "adjacent fixed seating" are deleted.
344
(41) In IBC, Section 1013.2, a new exception 5 is added as follows: "5. For
345
occupancies in Group R-3 and within individual dwelling units in occupancies in Group R-2,
346
as applicable in Section 101.2, guards shall form a protective barrier not less than 36 inches
347
(914 mm) in height."
348
(42) In IBC, Section 1015.2.2, the following sentence is added at the end: "Additional
349
exits or exit access doorways shall be arranged a reasonable distance apart so that if one
350
becomes blocked, the others will be available."
351
(43) IBC, Section 1024, is deleted.
352
(44) A new IBC, Section 1109.7.1, is added as follows: "1109.7.1 Platform
353
(wheelchair) lifts. All platform (wheelchair) lifts shall be capable of independent operation
354
without a key."
355
(45) In IBC, Section 1208.4, subparagraph 1 is deleted and replaced with the
356
following: "1. The unit shall have a living room of not less than 165 square feet (15.3 m2) of
357
floor area. An additional 100 square feet (9.3 m2) of floor area shall be provided for each
358
occupant of such unit in excess of two."
359
(46) In IBC, Table 1604.5, Occupancy Category III, in the sentence that begins Group
360
I-2, a new footnote b is added as follows: "b. Type II Assisted Living Facilities that are I-2
361
occupancy classifications in accordance with Section 308 shall be Occupancy Category II in
362
this table."
363
(47) In IBC, Section 1605.2.1, the formula shown as "f2 = 0.2 for other roof
364
configurations" is deleted and replaced with the following: "f2 = 0.20 + .025(A-5) for other
365
configurations where roof snow load exceeds 30 psf;
366
f2 = 0 for roof snow loads of 30 psf (1.44kN/m2) or less.
367
Where A = Elevation above sea level at the location of the structure (ft/1000)."
368
(48) In IBC, Section 1605.3.1 and Section 1605.3.2, exception 2 in each section is
369
deleted and replaced with the following: "2. Flat roof snow loads of 30 pounds per square foot
370
(1.44 kNm2) or less need not be combined with seismic loads. Where flat roof snow loads
371
exceed 30 pounds per square foot (1.44 kNm2), the snow loads may be reduced in accordance
372
with the following in load combinations including both snow and seismic loads. Ws as
373
calculated below, shall be combined with seismic loads.
374
Ws = (0.20 + 0.025(A-5))Pf is greater than or equal to 0.20 Pf.
375
Where:
376
Ws = Weight of snow to be included in seismic calculations;
377
A = Elevation above sea level at the location of the structure (ft/1000)
378
Pf = Design roof snow load, psf;
379
For the purpose of this section, snow load shall be assumed uniform on the roof footprint
380
without including the effects of drift or sliding. The Importance Factor, I, used in calculating Pf
381
may be considered 1.0 for use in the formula for Ws.".
382
(49) IBC, Section 1608.1, is deleted and replaced with the following: "1608.1 General.
383
Except as modified in section 1608.1.1, 1608.1.2, and 1608.1.3 design snow loads shall be
384
determined in accordance with Chapter 7 of ASCE 7, but the design roof load shall not be less
385
than that determined by Section 1607."
386
(50) A new IBC, Section 1608.1.1, is added as follows: "1608.1.1 Section 7.4.5 of
387
Chapter 7 of ASCE 7 referenced in Section 1608.1 of the IBC is deleted and replaced with the
388
following: "Section 7.4.5 Ice Dams and Icicles Along Eaves. Where ground snow loads exceed
389
75 psf, eaves shall be capable of sustaining a uniformly distributed load of 2pf on all
390
overhanging portions. No other loads except dead loads shall be present on the roof when this
391
uniformly distributed load is applied. All building exits under down-slope eaves shall be
392
protected from sliding snow and ice."
393
(51) In IBC, Section 1608.1.2, a new section is added as follows: "1608.1.2 Utah Snow
394
Loads. The ground snow load, Pg, to be used in the determination of design snow loads for
395
buildings and other structures shall be determined by using the following formula: Pg = (Po2 +
396
S2(A-Ao)2)0.5 for A greater than Ao, and Pg = Po for A less than or equal to Ao.
397
WHERE:
398
Pg = Ground snow load at a given elevation (psf);
399
Po = Base ground snow load (psf) from Table No. 1608.1.2(a);
400
S = Change in ground snow load with elevation (psf/100 ft.) From Table No. 1608.1.2(a);
401
A = Elevation above sea level at the site (ft./1000);
402
Ao = Base ground snow elevation from Table 1608.1.2(a) (ft./1000).
403
The building official may round the roof snow load to the nearest 5 psf. The ground snow load,
404
Pg, may be adjusted by the building official when a licensed engineer or architect submits data
405
substantiating the adjustments. A record of such action together with the substantiating data
406
shall be provided to the division for a permanent record.
407
The building official may also directly adopt roof snow loads in accordance with Table
408
1608.1.2(b), provided the site is no more than 100 ft. higher than the listed elevation.
409
Where the minimum roof live load in accordance with section 1607.11 is greater than the
410
design roof snow load, such roof live load shall be used for design, however, it shall not be
411
reduced to a load lower than the design roof snow load. Drifting need not be considered for
412
roof snow loads less than 20 psf."
413
(52) IBC, Table 1608.1.2(a) and Table 1608.1.2(b), are added as follows:
414
"TABLE NO. 1608.1.2(a)
415
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS
416
COUNTY Po S Ao
417
Beaver 43 63 6.2
418
Box Elder 43 63 5.2
419
Cache 50 63 4.5
420
Carbon 43 63 5.2
421
Daggett 43 63 6.5
422
Davis 43 63 4.5
423
Duchesne 43 63 6.5
424
Emery 43 63 6.0
425
Garfield 43 63 6.0
426
Grand 36 63 6.5
427
Iron 43 63 5.8
428
Juab 43 63 5.2
429
Kane 36 63 5.7
430
Millard 43 63 5.3
431
Morgan 57 63 4.5
432
Piute 43 63 6.2
433
Rich 57 63 4.1
434
Salt Lake 43 63 4.5
435
San Juan 43 63 6.5
436
Sanpete 43 63 5.2
437
Sevier 43 63 6.0
438
Summit 86 63 5.0
439
Tooele 43 63 4.5
440
Uintah 43 63 7.0
441
Utah 43 63 4.5
442
Wasatch 86 63 5.0
443
Washington 29 63 6.0
444
Wayne 36 63 6.5
445
Weber 43 63 4.5
446
TABLE NO. 1608.1.2(b)
447
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)
448
Roof Snow Ground Snow
449
Load (PSF) Load (PSF)
450
Beaver County
451
Beaver 5920 ft. 43 62
452
Box Elder County
453
Brigham City 4300 ft. 30 43
454
Tremonton 4290 ft. 30 43
455
Cache County
456
Logan 4530 ft. 35 50
457
Smithfield 4595 ft. 35 50
458
Carbon County
459
Price 5550 ft. 30 43
460
Daggett County
461
Manila 5377 ft. 30 43
462
Davis County
463
Bountiful 4300 ft. 30 43
464
Farmington 4270 ft. 30 43
465
Layton 4400 ft. 30 43
466
Fruit Heights 4500 ft. 40 57
467
Duchesne County
468
Duchesne 5510 ft. 30 43
469
Roosevelt 5104 ft. 30 43
470
Emery County
471
Castledale 5660 ft. 30 43
472
Green River 4070 ft. 25 36
473
Garfield County
474
Panguitch 6600 ft. 30 43
475
Grand County
476
Moab 3965 ft. H. [
5
] 25 .H 36
477
Iron County
478
Cedar City 5831 ft. 30 43
479
Juab County
480
Nephi 5130 ft. 30 43
481
Kane County
482
Kanab 5000 ft. 25 36
483
Millard County
484
Millard 5000 ft. 30 43
485
Delta 4623 ft. 30 43
486
Morgan County
487
Morgan 5064 ft. 40 57
488
Piute County
489
Piute 5996 ft. 30 43
490
Rich County
491
Woodruff 6315 ft. 40 57
492
Salt Lake County
493
Murray 4325 ft. 30 43
494
Salt Lake City 4300 ft. 30 43
495
Sandy 4500 ft. 30 43
496
West Jordan 4375 ft. 30 43
497
West Valley 4250 ft. 30 43
498
San Juan County
499
Blanding 6200 ft. 30 43
500
Monticello 6820 ft. 35 50
501
Sanpete County
502
Fairview 6750 ft. 35 50
503
Mt. Pleasant 5900 ft. 30 43
504
Manti 5740 ft. 30 43
505
Ephraim 5540 ft. 30 43
506
Gunnison 5145 ft. 30 43
507
Sevier County
508
Salina 5130 ft. 30 43
509
Richfield 5270 ft. 30 43
510
Summit County
511
Coalville 5600 ft. 60 86
512
Kamas 6500 ft. 70 100
513
Park City 6800 ft. 100 142
514
Park City 8400 ft. 162 231
515
Summit Park 7200 ft. 90 128
516
Tooele County
517
Tooele 5100 ft. 30 43
518
Uintah County
519
Vernal 5280 ft. 30 43
520
Utah County
521
American Fork 4500 ft. 30 43
522
Orem 4650 ft. 30 43
523
Pleasant Grove 5000 ft. 30 43
524
Provo 5000 ft. 30 43
525
Spanish Fork 4720 ft. 30 43
526
Wasatch County
527
Heber 5630 ft. 60 86
528
Washington County
529
Central 5209 ft. 25 36
530
Dameron 4550 ft. 25 36
531
Leeds 3460 ft. 20 29
532
Rockville 3700 ft. 25 36
533
Santa Clara 2850 ft. 15 (1) 21
534
St. George 2750 ft. 15 (1) 21
535
Wayne County
536
Loa 7080 ft. 30 43
537
Hanksville 4308 ft. 25 36
538
Weber County
539
North Ogden 4500 ft. 40 57
540
Ogden 4350 ft. 30 43
541
NOTES
542
(1) The IBC requires a minimum live load - See 1607.11.2.
543
(2) This table is informational only in that actual site elevations may vary. Table is only valid
544
if site elevation is within 100 feet of the listed elevation."
545
(53) A new IBC, Section 1608.1.3, is added as follows: "1608.1.3 Thermal Factor. The
546
value for the thermal factor, Ct, used in calculation of pf shall be determined from Table 7.3 in
547
ASCE 7.
548
Exception: Except for unheated structures, the value of Ct need not exceed 1.0 when ground
549
snow load, Pg is calculated using Section 1608.1.2 as amended."
550
(54) IBC, Section 1608.2, is deleted and replaced with the following: "1608.2 Ground
551
Snow Loads. The ground snow loads to be used in determining the design snow loads for roofs
552
in states other than Utah are given in Figure 1608.2 for the contiguous United States and Table
553
1608.2 for Alaska. Site-specific case studies shall be made in areas designated CS in figure
554
1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2
555
and for all sites within the CS areas shall be approved. Ground snow load determination for
556
such sites shall be based on an extreme value statistical analysis of data available in the vicinity
557
of the site using a value with a 2-percent annual probability of being exceeded (50-year mean
558
recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as
559
approved by the building official."
560
(55) In IBC, Section 1609.1.1, a new exception 7 is added as follows: "7. The wind
561
design procedure as found in Section 1616 through 1624 of the 1997 Uniform Building Code
562
may be used as an alternative wind design procedure for signs and free standing walls as listed
563
in item 7 listed in Table 16-H of the 1997 Uniform Building Code. The Importance Factor, I,
564
shall be determined in accordance with Table 6-1 of ASCE 7. Stress increases are only allowed
565
as provided in Section 1605.3 of the 2009 IBC."
566
(56) A new IBC, Section 1613.1.1, is added as follows: "1613.1.1 ASCE 12.7.2 and
567
12.14.8.1 of Chapter 12 of ASCE 7 referenced in Section 1613.1, Definition of W, Item 4 is
568
deleted and replaced with the following:
569
4. Where the flat roof snow load, Pf, exceeds 30 psf, the snow load included in seismic design
570
shall be calculated, in accordance with the following formula: Ws = (0.20 + 0.025(A-5))Pf is
571
greater than or equal to 0.20 Pf.
572
WHERE:
573
Ws = Weight of snow to be included in seismic calculations;
574
A = Elevation above sea level at the location of the structure (ft/1000);
575
Pf = Design roof snow load, psf.
576
For the purposes of this section, snow load shall be assumed uniform on the roof footprint
577
without including the effects of drift or sliding. The Importance Factor, I, used in calculating Pf
578
may be considered 1.0 for use in the formula for Ws."
579
(57) A new IBC, Section 1613.8, is added as follows: "1613.8 ASCE 7, Section
580
13.5.6.2.2 paragraph (e) is modified to read as follows: (e) Penetrations shall have a sleeve or
581
adapter through the ceiling tile to allow for free movement of at least 1 inch (25 mm) in all
582
horizontal directions.
583
Exceptions:
584
1. Where rigid braces are used to limit lateral deflections.
585
2. At fire sprinkler heads in frangible surfaces per NFPA 13."
586
(58) A new IBC, Section 1807.1.6.4, is added as follows: "1807.1.6.4 Empirical
587
concrete foundation design. Group R, Division 3 Occupancies three stories or less in height,
588
and Group U Occupancies, which are constructed in accordance with Section 2308, or with
589
other methods employing repetitive wood-frame construction or repetitive cold-formed steel
590
structural member construction, shall be permitted to have concrete foundations constructed in
591
accordance with Table 1807.1.6.4."
592
(59) A new IBC, Table 1807.1.6.4 is added as follows:
593
"
TABLE 1807.1.6.4
594
EMPIRICAL FOUNDATION WALLS (1,7,8)
595
Max. Height Top Edge Min. Vertical Horizontal Steel at Max. Lintel Min. Lintel
596
Support Thickness Steel (2) Steel (3) Openings (4) Length Length
597
2'(610 mm) None 6" (5) 2#4 Bars 2- #4 Bars above 2'(610 mm) 2"for each
598
1- #4 Bar each side foot of
599
1- #4 Bar below opening
600
width;
601
min. 6"
602
3'(914 mm) None 6" #4@32" 3-#4 Bars 2- #4 Bars above 2'(610 mm) 2"for each
603
1- #4 Bar each side foot of
604
1- #4 Bar below opening
605
width;
606
min. 6"
607
4'(1219 mm) None 6" #4@32" 4-#4 Bars 2- #4 Bars above 3'(914 mm) 2"for each
608
1- #4 Bar each side foot of
609
1- #4 Bar below opening
610
width;
611
min. 6"
612
6'(1829 mm) Floor or roof 8" #4@24" 5-#4 Bars 2- #4 Bars above 2"for each
613
Diaphragm 1- #4 Bar each side foot of
614
(6) 1- #4 Bar below opening
615
width;
616
min. 6"
617
8'(2438 mm) Floor or roof 8" #4@24" 6-#4 Bars 2- #4 Bars above 6'(1829 mm) 2"for each
618
Diaphragm 1- #4 Bar each side foot of
619
(6) 1- #4 Bar below opening
620
width;
621
min. 6"
622
9'(2743 mm) Floor or roof 8" #4@16" 7-#4 Bars 2- #4 Bars above 6'(1829 mm) 2"for each
623
Diaphragm 1- #4 Bar each side foot of
624
(6) 1- #4 Bar below opening
625
width;
626
min. 6"
627
Over 9' Engineering required for each column
628
(2743 mm)
629
Footnotes:
630
(1) Based on 3,000 psi (20.6 Mpa) concrete and 60,000 psi (414 Mpa) reinforcing steel.
631
(2) To be placed in the center of the wall, and extended from the footing to within three inches
632
(76 mm) of the top of the wall; dowels of #4 bars to match vertical steel placement shall be
633
provided in the footing, extending 24 inches (610 mm) into the foundation wall.
634
(3) One bar shall be located in the top four inches (102 mm), one bar in the bottom four inches
635
(102 mm) and the other bars equally spaced between. Such bar placement satisfies the
636
requirements of Section 1805.9. Corner reinforcing shall be provided so as to lap 24 inches
637
(610 mm).
638
(4) Bars shall be placed within two inches (51 mm) of the openings and extend 24 inches (610
639
mm) beyond the edge of the opening; vertical bars may terminate three inches (76 mm) from
640
the top of the concrete.
641
(5) Dowels of #4 bar at 32 inches on center shall be provided in the footing, extending 18
642
inches (457 mm) into the foundation wall.
643
(6) Diaphragm shall conform to the requirements of Section 2308.
644
(7) Footing shall be a minimum of nine inches thick by 20 inches wide.
645
(8) Soil backfill shall be soil classification types GW, GP, SW, or SP, per Table 1610.1. Soil
646
shall not be submerged or saturated in groundwater."
647
(60) A new IBC, Section 2306.1.5, is added as follows: "2306.1.5 Load duration
648
factors. The allowable stress increase of 1.15 for snow load, shown in Table 2.3.2, Frequently
649
Used Load Duration Factors, Cd, of the National Design Specifications, shall not be utilized at
650
elevations above 5,000 feet (1524 M)."
651
(61) In IBC, Section 2308.6, a new exception is added as follows: "Exception: Where
652
foundation plates or sills are bolted or anchored to the foundation with not less than 1/2 inch
653
(12.7 mm) diameter steel bolts or approved anchors, embedded at least 7 inches (178 mm) into
654
concrete or masonry and spaced not more than 32 inches (816 mm) apart, there shall be a
655
minimum of two bolts or anchor straps per piece located not less than 4 inches (102 mm) from
656
each end of each piece. A properly sized nut and washer shall be tightened on each bolt to the
657
plate."
658
(62) IBC, Section 2506.2.1, is deleted and replaced with the following: "2506.2.1
659
Other materials. Metal suspension systems for acoustical and lay-in panel ceilings shall
660
conform with ASTM C635 listed in Chapter 35 and Section 13.5.6 of ASCE 7-05, as amended
661
in Section 1613.8, for installation in high seismic areas."
662
(63) In IBC, Section 2902.1, the title for Table 2902.1 is deleted and replaced and a
663
new footnote g is added as follows:
664
(a) "Table 2902.1, Minimum Number of Required Plumbing Facilitiesa, g"; and
665
(b) "FOOTNOTE: g. When provided, in public toilet facilities there shall be an equal
666
number of diaper changing facilities in male toilet rooms and female toilet rooms."
667
(64) In IBC, Section 3006.5, a new exception is added as follows: "Exception:
668
Hydraulic elevators and roped hydraulic elevators with a rise of 50 feet or less."
669
(65) A new section IBC, Section 3401.6, is added as follows: "3401.6 Parapet bracing,
670
wall anchors, and other appendages. Buildings constructed prior to 1975 shall have parapet
671
bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary,
672
etc. evaluated by a licensed engineer when said building is undergoing reroofing, or alteration
673
of or repair to said feature. Such parapet bracing, wall anchors, and appendages shall be
674
evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When
675
allowed by the local building official, alternate methods of equivalent strength as referenced in
676
an approved code under Utah Code, Subsection 58-56-4(6)(a), will be considered when
677
accompanied by engineer-sealed drawings, details, and calculations. When found to be
678
deficient because of design or deteriorated condition, the engineer's recommendations to
679
anchor, brace, reinforce, or remove the deficient feature shall be implemented.
680
EXCEPTIONS:
681
1. Group R-3 and U occupancies.
682
2. Unreinforced masonry parapets need not be braced according to the above stated provisions
683
provided that the maximum height of an unreinforced masonry parapet above the level of the
684
diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times
685
the thickness of the parapet wall. The parapet height may be a maximum of two and one-half
686
times its thickness in other than Seismic Design Categories D, E, or F."
687
(66) IBC, Section 3408.4, is deleted and replaced with the following: "3408.4 Change
688
in Occupancy. When a change in occupancy results in a structure being reclassified to a higher
689
Occupancy Category (as defined in Table 1604.5), or when such change of occupancy results in
690
a design occupant load increase of 100% or more, the structure shall conform to the seismic
691
requirements for a new structure.
692
Exceptions:
693
1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not
694
be required to be met where it can be shown that the level of performance and seismic safety is
695
equivalent to that of a new structure. Such analysis shall consider the regularity, overstrength,
696
redundancy, and ductility of the structure within the context of the existing and retrofit (if any)
697
detailing providing. Alternatively, the building official may allow the structure to be upgraded
698
in accordance with referenced sections as found in an approved code under Utah Code,
699
Subsection 58-56-4(6)(a).
700
2. When a change of use results in a structure being reclassified from Occupancy Category I or
701
II to Occupancy Category III and the structure is located in a seismic map area where SDS is less
702
than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not required.
703
3. Where design occupant load increase is less than 25 occupants and the Occupancy Category
704
does not change."
705
(67) In IBC, Section 3411.1, the exception is deleted and replaced with the following:
706
"Exception: Type B dwelling or sleeping units required by section 1107 of this code are not
707
required to be provided in existing buildings and facilities unless being altered or undergoing a
708
change of occupancy classification."
709
(68) The following referenced standard is added under NFPA in IBC, Chapter 35:
710
"Referenced in code
711
Number Title Section number
712
720-09 Standard for the Installation of 907.9
713
Carbon Monoxide (CO) Detection and
714
Warning Equipment"
715
(69) The following referenced standard is added under UL in IBC, Chapter 35:
716
"Referenced in code
717
Number Title Section number
718
2034-2008 Standard of Single- and 907.9
719
Multiple-station Carbon Monoxide Alarms"
720
Section 202. Statewide Amendments to the IRC.
721
The following are adopted as amendments to the IRC to be applicable statewide:
722
(1) The statewide amendments to the following which may be applied to detached one
723
and two family dwellings and multiple single family dwellings shall be applicable to the
724
corresponding provisions of the IRC:
725
(a) IBC under State Construction Code, Section 201;
726
(b) IPC under State Construction Code, Section 203;
727
(c) IMC under State Construction Code, Section 204;
728
(d) IFGC under State Construction Code, Section 205;
729
(e) NEC under State Construction Code, Section 206; and
730
(f) IECC under State Construction Code, Section 207.
731
(2) In IRC, Section 109:
732
(a) A new IRC, Section 109.1.5, is added as follows: "R109.1.5 Weather-resistant
733
exterior wall envelope inspections. An inspection shall be made of the weather-resistant
734
exterior wall envelope as required by Section R703.1 and flashings as required by Section
735
R703.8 to prevent water from entering the weather-resistive barrier."
736
(b) The remaining sections are renumbered as follows: R109.1.6 Other inspections;
737
R109.1.6.1 Fire-and smoke-resistance-rated construction inspection; R109.1.6.2 Reinforced
738
masonry, insulating concrete form (ICF) and conventionally formed concrete wall inspection;
739
and R109.1.7 Final inspection.
740
(3) IRC, Section R114.1, is deleted and replaced with the following: "R114.1 Notice to
741
owner. Upon notice from the building official that work on any building or structured is being
742
prosecuted contrary to the provisions of this code or other pertinent laws or ordinances or in an
743
unsafe and dangerous manner, such work shall be immediately stopped. The stop work order
744
shall be in writing and shall be given to the owner of the property involved, or to the owner's
745
agent or to the person doing the work; and shall state the conditions under which work will be
746
permitted to resume."
747
(4) In IRC, Section R202, the following definition is added: "CERTIFIED
748
BACKFLOW PREVENTER ASSEMBLY TESTER: A person who has shown competence to
749
test Backflow prevention assemblies to the satisfaction of the authority having jurisdiction
750
under Utah Code, Subsection 19-4-104(4)."
751
(5) In IRC, Section R202, the definition of "Cross Connection" is deleted and replaced
752
with the following: "CROSS CONNECTION. Any physical connection or potential connection
753
or arrangement between two otherwise separate piping systems, one of which contains potable
754
water and the other either water of unknown or questionable safety or steam, gas, or chemical,
755
whereby there exists the possibility for flow from one system to the other, with the direction of
756
flow depending on the pressure differential between the two systems (see "Backflow, Water
757
Distribution")."
758
(6) In IRC, Section R202, the definition of "Potable Water" is deleted and replaced
759
with the following: "POTABLE WATER. Water free from impurities present in amounts
760
sufficient to cause disease or harmful physiological effects and conforming to the Utah Code,
761
Title 19, Chapters 4 and 5, and the regulations of the public health authority having
762
jurisdiction."
763
(7) IRC, Figure R301.2(5), is deleted and replaced with Table R301.2(5a) and Table
764
R301.2(5b) as follows:
765
"TABLE NO. R301.2(5a)
766
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS
767
COUNTY Po S Ao
768
Beaver 43 63 6.2
769
Box Elder 43 63 5.2
770
Cache 50 63 4.5
771
Carbon 43 63 5.2
772
Daggett 43 63 6.5
773
Davis 43 63 4.5
774
Duchesne 43 63 6.5
775
Emery 43 63 6.0
776
Garfield 43 63 6.0
777
Grand 36 63 6.5
778
Iron 43 63 5.8
779
Juab 43 63 5.2
780
Kane 36 63 5.7
781
Millard 43 63 5.3
782
Morgan 57 63 4.5
783
Piute 43 63 6.2
784
Rich 57 63 4.1
785
Salt Lake 43 63 4.5
786
San Juan 43 63 6.5
787
Sanpete 43 63 5.2
788
Sevier 43 63 6.0
789
Summit 86 63 5.0
790
Tooele 43 63 4.5
791
Uintah 43 63 7.0
792
Utah 43 63 4.5
793
Wasatch 86 63 5.0
794
Washington 29 63 6.0
795
Wayne 36 63 6.5
796
Weber 43 63 4.5
797
TABLE NO. R301.2(5b)
798
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)
799
Roof Snow Ground Snow
800
Load (PSF) Load (PSF)
801
Beaver County
802
Beaver 5920 ft 43 62
803
Box Elder County
804
Brigham City 4300 ft. 30 43
805
Tremonton 4290 ft. 30 43
806
Cache County
807
Logan 4530 ft. 35 50
808
Smithfield 4595 ft. 35 50
809
Carbon County
810
Price 5550 ft. 30 43
811
Daggett County
812
Manila 5377 ft. 30 43
813
Davis County
814
Bountiful 4300 ft. 30 43
815
Farmington 4270 ft. 30 43
816
Layton 4400 ft. 30 43
817
Fruit Heights 4500 ft. 40 57
818
Duchesne County
819
Duchesne 5510 ft. 30 43
820
Roosevelt 5104 ft. 30 43
821
Emery County
822
Castledale 5660 ft. 30 43
823
Green River 4070 ft. 25 36
824
Garfield County
825
Panguitch 6600 ft. 30 43
826
Grand County
827
Moab 3965 ft. 25 36
828
Iron County
829
Cedar City 5831 ft. 30 43
830
Juab County
831
Nephi 5130 ft. 30 43
832
Kane County
833
Kanab 5000 ft. 25 36
834
Millard County
835
H. [
Millard
] Fillmore .H 5000 ft. 30 43
836
Delta 4623 ft. 30 43
837
Morgan County
838
Morgan 5064 ft. 40 57
839
Piute County
840
Piute 5996 ft. 30 43
841
Rich County
842
Woodruff 6315 ft. 40 57
843
Salt Lake County
844
Murray 4325 ft. 30 43
845
Salt Lake City 4300 ft. 30 43
846
Sandy 4500 ft. 30 43
847
West Jordan 4375 ft. 30 43
848
West Valley 4250 ft. 30 43
849
San Juan County
850
Blanding 6200 ft. 30 43
851
Monticello 6820 ft. 35 50
852
Sanpete County
853
Fairview 6750 ft. 35 50
854
Mt. Pleasant 5900 ft. 30 43
855
Manti 5740 ft. 30 43
856
Ephraim 5540 ft. 30 43
857
Gunnison 5145 ft. 30 43
858
Sevier County
859
Salina 5130 ft. 30 43
860
Richfield 5270 ft. 30 43
861
Summit County
862
Coalville 5600 ft. 60 86
863
Kamas 6500 ft. 70 100
864
Park City 6800 ft. 100 142
865
Park City 8400 ft. 162 231
866
Summit Park 7200 ft. 90 128
867
Tooele County
868
Tooele 5100 ft. 30 43
869
Uintah County
870
Vernal 5280 ft. 30 43
871
Utah County
872
American Fork 4500 ft. 30 43
873
Orem 4650 ft. 30 43
874
Pleasant Grove 5000 ft. 30 43
875
Provo 5000 ft. 30 43
876
Spanish Fork 4720 ft. 30 43
877
Wasatch County
878
Heber 5630 ft. 60 86
879
Washington County
880
Central 5209 ft. 25 36
881
Dameron 4550 ft. 25 36
882
Leeds 3460 ft. 20 29
883
Rockville 3700 ft. 25 36
884
Santa Clara 2850 ft. 15 (1) 21
885
St. George 2750 ft. 15 (1) 21
886
Wayne County
887
Loa 7080 ft. 30 43
888
Hanksville 4308 ft. 25 36
889
Weber County
890
North Ogden 4500 ft. 40 57
891
Ogden 4350 ft. 30 43
892
NOTES
893
(1) The IRC requires a minimum live load - See R301.6.
894
(2) This table is informational only in that actual site elevations may vary. Table is only valid
895
if site elevation is within 100 feet of the listed elevation."
896
(8) IRC, Section R301.6, is deleted and replaced with the following: "R301.6 Utah
897
Snow Loads. The ground snow load, Pg, to be used in the determination of design snow loads
898
for buildings and other structures shall be determined by using the following formula: Pg = (Po2
899
+ S2(A-Ao)2)0.5 for A greater than Ao, and Pg = Po for A less than or equal to Ao.
900
WHERE:
901
Pg = Ground snow load at a given elevation (psf);
902
Po = Base ground snow load (psf) from Table No. R301.2(5a);
903
S = Change in ground snow load with elevation (psf/100 ft.) From Table No. R301.2(5a);
904
A = Elevation above sea level at the site (ft./1000);
905
Ao = Base ground snow elevation from Table R301.2(5a) (ft./1000).
906
The building official may round the roof snow load to the nearest 5 psf. The ground snow load,
907
Pg, may be adjusted by the building official when a licensed engineer or architect submits data
908
substantiating the adjustments. A record of such action together with the substantiating data
909
shall be provided to the division for a permanent record.
910
The building official may also directly adopt roof snow loads in accordance with Table
911
R301.2(5b), provided the site is no more than 100 ft. higher than the listed elevation.
912
Where the minimum roof live load in accordance with Table R301.6 is greater than the design
913
roof snow load, such roof live load shall be used for design, however, it shall not be reduced to
914
a load lower than the design roof snow load. Drifting need not be considered for roof snow
915
loads less than 20 psf."
916
(9) In IRC, Section R302.2, the words "Exception: A" are deleted and replaced with the
917
following: "Exceptions: 1. A common 2-hour fire-resistance-rated wall is permitted for
918
townhouses if such walls do not contain plumbing or mechanical equipment, ducts or vents in
919
the cavity of the common wall. Electrical installation shall be installed in accordance with
920
Chapters 34 through 43. Penetrations of electrical outlet boxes shall be in accordance with
921
Section R302.4.
922
2. In buildings equipped with an automatic residential fire sprinkler system, a".
923
(10) In IRC, Section R302.2.4, a new exception 6 is added as follows: "6. Townhouses
924
separated by a common 2-hour fire-resistance-rated wall as provided in Section R302.2."
925
(11) IRC, Sections R311.7.4 through R311.7.4.3, are deleted and replaced with the
926
following: "R311.7.4 Stair treads and risers. R311.7.4.1 Riser height. The maximum riser
927
height shall be 8 inches (203 mm). The riser shall be measured vertically between leading
928
edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed
929
the smallest by more than 3/8 inch (9.5 mm).
930
R311.7.4.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The tread
931
depth shall be measured horizontally between the vertical planes of the foremost projection of
932
adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within
933
any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads
934
shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12
935
inches (305 mm) from the side where the treads are narrower. Winder treads shall have a
936
minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the
937
greatest winder tread depth at the 12 inch (305 mm) walk line shall not exceed the smallest by
938
more than 3/8 inch (9.5 mm).
939
R311.7.4.3 Profile. The radius of curvature at the leading edge of the tread shall be no greater
940
than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 1 1/4
941
inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing projection
942
shall not exceed the smallest nosing projection by more than 3/8 inches (9.5 mm) between two
943
stories, including the nosing at the level of floors and landings. Beveling of nosing shall not
944
exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading
945
edge of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open
946
risers are permitted, provided that the opening between treads does not permit the passage of a
947
4-inch diameter (102 mm) sphere.
948
Exceptions.
949
1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).
950
2. The opening between adjacent treads is not limited on stairs with a total rise of 30 inches
951
(762 mm) or less."
952
(12) In Section R312.2, the words "adjacent fixed seating" are deleted.
953
(13) IRC, Section R313, is deleted.
954
(14) IRC, Section R315.1, is deleted and replaced with the following: "R315.1 Carbon
955
monoxide alarms. For new construction, a listed carbon monoxide alarm shall be installed on
956
each habitable level of dwelling units within which fuel-fired appliances are installed and in
957
dwelling units that have attached garages."
958
(15) IRC, Section R315.3, is deleted and replaced with the following: "R315.3 Alarm
959
requirements. Listed single- and multiple-station carbon monoxide alarms shall comply with
960
U.L. 2034 and shall be installed in accordance with the provision of this code and NFPA 720."
961
(16) In IRC, Section R403.1.6, a new Exception 4 is added as follows: "4. When
962
anchor bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be placed
963
with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from
964
each end of each plate section at interior bearing walls, interior braced wall lines and at all
965
exterior walls."
966
(17) In IRC, Section R403.1.6.1, a new exception is added at the end of Item 2 and
967
Item 3 as follows: "Exception: When anchor bolt spacing does not exceed 32 inches (816 mm)
968
apart, anchor bolts may be placed with a minimum of two bolts per plate section located not
969
less than 4 inches (102 mm) from each end of each plate section at interior bearing walls,
970
interior braced wall lines and at all exterior walls."
971
(18) In IRC, Section R404.1, a new exception is added as follows: "Exception: As an
972
alternative to complying with Sections R404.1 through R404.1.5.3, concrete and masonry
973
foundation walls may be designed in accordance with IBC Sections 1807.1.5 and 1807.1.6 as
974
amended in Section 1807.1.6.4 and Table 1807.1.6.4 under these rules."
975
(19) IRC, Sections R612.2 through R612.4.2, are deleted.
976
(20) IRC, Chapter 11, is deleted and replaced with Chapter 11 of the 2006 International
977
Residential Code and Chapter 4 of the 2006 International Energy Conservation Code.
978
(21) IRC, Section M1411.6, is deleted.
979
(22) In IRC, Section M1502.4.4.1, the words "25 feet (7620 mm)" are deleted and
980
replaced with "35 feet (10668 mm)".
981
(23) A new IRC, Section G2401.2, is added as follows: "G2401.2 Meter Protection.
982
Fuel gas services shall be in an approved location and/or provided with structures designed to
983
protect the fuel gas meter and surrounding piping from physical damage, including falling,
984
moving, or migrating ice and snow. If an added structure is used, it must provide access for
985
service and comply with the IBC or the IRC."
986
(24) A new IRC, Section P2602.3, is added as follows: "P2602.3 Individual water
987
supply. Where a potable public water supply is not available, individual sources of potable
988
water supply shall be utilized provided that the source has been developed in accordance with
989
Utah Code, Sections 73-3-1 and 73-3-25, as administered by the Department of Natural
990
Resources, Division of Water Rights. In addition, the quality of the water shall be approved by
991
the local health department having jurisdiction."
992
(25) A new IRC, Section P2602.4, is added as follows: "P2602.4 Sewer required.
993
Every building in which plumbing fixtures are installed and all premises having drainage
994
piping shall be connected to a public sewer where the sewer is within 300 feet of the property
995
line in accordance with Utah Code, Section 10-8-38; or an approved private sewage disposal
996
system in accordance with Utah Administrative Code, Chapter 4, Rule R317, as administered
997
by the Department of Environmental Quality, Division of Water Quality."
998
(26) In IRC, Section P2801.7, the word "townhouses" is deleted.
999
(27) A new IRC, Section P2902.1.1, is added as follows: "P2902.1.1 Backflow
1000
assembly testing. The premise owner or his designee shall have backflow prevention
1001
assemblies operation tested at the time of installation, repair, and relocation and at least on an
1002
annual basis thereafter, or more frequently as required by the authority having jurisdiction.
1003
Testing shall be performed by a Certified Backflow Preventer Assembly Tester. The assemblies
1004
that are subject to this paragraph are the Spill Resistant Vacuum Breaker, the Pressure Vacuum
1005
Breaker Assembly, the Double Check Backflow Prevention Assembly, the Double Check
1006
Detector Assembly Backflow Preventer, the Reduced Pressure Principle Backflow Preventer,
1007
and Reduced Pressure Detector Assembly."
1008
(28) IRC, Table P2902.3 is deleted and replaced with the following:
1009
"TABLE P2902.3
1010
General Methods of Protection
1011
Assembly Degree Application Installation Criteria
1012
(applicable of
1013
standard) Hazard
1014
Reduced High or Backpressure or a. The bottom of each
1015
Pressure Low Backsiphonage RP assembly shall
1016
Principle Backflow 1/2" - 16" be a minimum of 12
1017
Preventer (AWWA inches above the
1018
C511, USC-FCCCHR, ground or floor.
1019
ASSE 1013 b. RP assemblies shall
1020
CSA CNA/CSA-B64.4) NOT be installed in
1021
and Reduced Pressure a pit.
1022
Detector Assembly c. The relief valve on
1023
(ASSE 1047, USC- each RP assembly
1024
FCCCHR) shall not be
1025
directly connected
1026
to any waste
1027
disposal line,
1028
including sanitary
1029
sewer, storm drains,
1030
or vents.
1031
d. The assembly shall
1032
be installed in a
1033
horizontal position
1034
only unless listed
1035
or approved for
1036
vertical installation.
1037
Double Check Low Backpressure or a. If installed in a
1038
Backflow Backsiphonage pit, the DC assembly
1039
Prevention 1/2" - 16" shall be installed
1040
Assembly with a minimum of
1041
(AWWA C510, 12 inches of
1042
USC-FCCCHR, clearance between
1043
ASSE 1015) all sides of the
1044
Double Check vault including
1045
Detector Assembly the floor and roof
1046
Backflow Preventer or ceiling with
1047
(ASSE 1048, adequate room for
1048
USC-FCCCHR) testing and
1049
maintenance.
1050
b. Shall be installed
1051
in a horizontal
1052
position unless
1053
listed or approved
1054
for vertical
1055
installation.
1056
Pressure High or Backsiphonage a. Shall not be
1057
Vacuum Low 1/2" - 2" installed in an
1058
Breaker area that could be
1059
Assembly subjected to
1060
(ASSE 1020, backpressure or
1061
USC-FCCCHR) back drainage
1062
conditions.
1063
b. Shall be installed
1064
a minimum of 12
1065
inches above all
1066
downstream piping
1067
and the highest
1068
point of use.
1069
c. Shall not be
1070
installed below
1071
ground or in a
1072
vault or pit.
1073
d. Shall be installed
1074
in a vertical position
1075
only.
1076
Spill High or Backsiphonage a. Shall not be
1077
Resistant Low 1/4" - 2" installed in an
1078
Vacuum area that could
1079
Breaker be subjected to
1080
(ASSE 1056, backpressure or
1081
USC-FCCCHR) back drainage
1082
conditions.
1083
b. Shall be installed
1084
a minimum of 12
1085
inches above all
1086
downstream piping
1087
and the highest
1088
point of use.
1089
c. Shall not be
1090
installed below
1091
ground or in a
1092
vault or pit.
1093
d. Shall be installed
1094
in a vertical position
1095
only.
1096
General The assembly owner,
1097
Installation when necessary,
1098
Criteria shall provide devices
1099
or structures to
1100
facilitate testing,
1101
repair, and/or
1102
maintenance and
1103
to ensure the safety of
1104
the backflow
1105
technician.
1106
Assemblies shall not
1107
be installed more than
1108
five feet off the floor
1109
unless a permanent
1110
platform is installed.
1111
The body of the
1112
assembly shall not be
1113
closer than 12 inches
1114
to any wall, ceiling or
1115
encumbrance, and
1116
shall be accessible for
1117
testing, repair and/or
1118
maintenance.
1119
In cold climates,
1120
assemblies shall be
1121
protected from
1122
freezing by a means
1123
acceptable to the code
1124
official.
1125
Assemblies shall be
1126
maintained as an intact
1127
assembly."
1128
(29) IRC, Table 2902.3a, is added as follows:
1129
"TABLE 2902.3a
1130
Specialty Backflow Devices for low hazard use only
1131
Device Degree of Application Applicable
1132
Hazard Standard
1133
Air Gap High or Backsiphonage See Table P2902.3.1
1134
Low ASME A112.1.2
1135
Antisiphon-type Low Backsiphonage ASSE 1002
1136
Water Closet Flush CSA CAN/
1137
Tank Ball Cock CSA-B125
1138
Atmospheric High or Backsiphonage ASSE 1001
1139
Vacuum Low a. Shall not be USC-FCCCHR,
1140
Breaker installed in an CSA
1141
area that could be CAN/CSA-B64.1.1
1142
subjected to
1143
backpressure or back
1144
drainage conditions.
1145
b. Shall not be installed
1146
where it may be subjected
1147
to continuous pressure
1148
for more than 12 consecutive
1149
hours at any time.
1150
c. Shall be installed a
1151
minimum of six inches above
1152
all downstream piping and
1153
the highest point of use.
1154
d. Shall be installed on the
1155
discharge (downstream) side
1156
of any valves.
1157
e. The AVB shall be installed
1158
in a vertical position only.
1159
Dual check valve Low Backsiphonage ASSE 1024
1160
Backflow Preventer or Backpressure
1161
1/4" - 1"
1162
Backflow Preventer Low Backsiphonage ASSE 1012
1163
with Intermediate Residential or Backpressure CSA CAN/
1164
Atmospheric Vent Boiler 1/4" - 3/4" CSA-B64.3
1165
Dual check valve Low Backsiphonage ASSE 1022
1166
type Backflow or Backpressure
1167
Preventer for 1/4" - 3/8"
1168
Carbonated Beverage
1169
Dispensers/Post
1170
Mix Type
1171
Hose-connection Low Backsiphonage ASSE 1011
1172
Vacuum Breaker 1/2", 3/4", 1" CSA CAN/
1173
CSA-B64.2
1174
Vacuum Breaker Low Backsiphonage ASSE 1019
1175
Wall Hydrants, 3/4", 1" CSA CAN/
1176
Frost-resistant, CSA-B64.2.2
1177
Automatic Draining
1178
Type
1179
Laboratory Faucet Low Backsiphonage ASSE 1035
1180
Backflow Preventer CSA CAN/
1181
CSA-B64.7
1182
Hose Connection Low Backsiphonage ASSE 1052
1183
Backflow Preventer 1/2" - 1"
1184
Installation Guidelines: The above specialty devices shall be installed in accordance with their
1185
listing and the manufacturer's instructions and the specific provisions of this chapter."
1186
(30) In IRC, Section P3103.6, the following sentence is added at the end of the
1187
paragraph: "Vents extending through the wall shall terminate not less than 12 inches from the
1188
wall with an elbow pointing downward."
1189
(31) In IRC, Section P3104.4, the following sentence is added at the end of the
1190
paragraph: "Horizontal dry vents below the flood level rim shall be permitted for floor drain
1191
and floor sink installations when installed below grade in accordance with Chapter 30, and
1192
Sections P3104.2 and P3104.3. A wall cleanout shall be provided in the vertical vent."
1193
(32) In IRC, Section E3902.11, the following words are deleted: "family rooms, dining
1194
rooms, living rooms, parlors, libraries, dens, sunrooms, recreations rooms, closets, hallways,
1195
and similar rooms or areas".
1196
(33) IRC, Chapter 44, is amended by adding the following reference standard:
1197
"Standard
1198
reference Referenced in code
1199
number Title Section number
1200
USC- Foundation for Cross-Connection Table P2902.3
1201
FCCCHR Control and Hydraulic Research
1202
9th University of Southern California
1203
Edition Kaprielian Hall 300
1204
Manual Los Angeles CA 90089-2531
1205
of Cross
1206
Connection
1207
Control"
1208
(34) In IRC, Chapter 44, the following standard is added under NFPA as follows:
1209
Standard
1210
reference Referenced in code
1211
number Title section number
1212
720-09 Standard for the Installation R315.3
1213
of Carbon Monoxide (CO) Detection
1214
and Warning Equipment"
1215
(35) IRC, Appendix O, Gray Water Recycling Systems, is deleted and replaced with
1216
Appendix C of the International Plumbing Code as amended by the state construction code.
1217
Section 203. Statewide Amendments to the IPC.
1218
The following are adopted as amendments to the IPC to be applicable statewide:
1219
(1) A new IPC, Section 101.2, is added as follows: "For clarification, the International
1220
Private Sewage Disposal Code is not part of the plumbing code even though it is in the same
1221
printed volume."
1222
(2) In IPC, Section 202, the definition for "Backflow Backpressure, Low Head" is
1223
deleted.
1224
(3) In IPC, Section 202, the following definition is added: "Certified Backflow
1225
Preventer Assembly Tester. A person who has shown competence to test Backflow prevention
1226
assemblies to the satisfaction of the authority having jurisdiction under Utah Code, Subsection
1227
19-4-104(4)."
1228
(4) In IPC, Section 202, the definition for "Cross Connection" is deleted and replaced
1229
with the following: "Cross Connection. Any physical connection or potential connection or
1230
arrangement between two otherwise separate piping systems, one of which contains potable
1231
water and the other either water of unknown or questionable safety or steam, gas, or chemical,
1232
whereby there exists the possibility for flow from one system to the other, with the direction of
1233
flow depending on the pressure differential between the two systems (see "Backflow")."
1234
(5) In IPC, Section 202, the definition for "Potable Water" is deleted and replaced with
1235
the following: "Potable Water. Water free from impurities present in amounts sufficient to
1236
cause disease or harmful physiological effects and conforming to the Utah Code, Title 19,
1237
Chapters 4 and 5, and the regulations of the public health authority having jurisdiction."
1238
(6) In IPC, Table 303.4, the item listed as "Backflow prevention devises" is modified
1239
as follows:
1240
(a) in the Third-Party Certified field, after the word "Required" add "See footnote 1";
1241
(b) in the Third-Party Tested field the following is added: "Required see footnote 1";
1242
and
1243
(c) a new footnote 1 is added as follows: "1. Third party certification will consist of
1244
any combination of two certifications, laboratory or field. Acceptable third party laboratory
1245
certifying agencies are ASSE, IAPMO, and USC-FCCCHR. USC-FCCCHR currently provides
1246
the only field testing of backflow protection assemblies. Also see www.drinkingwater.utah.gov
1247
and Division of Drinking Water Rule R309-305-6."
1248
(7) IPC, Section 304.3, Meter Boxes, is deleted.
1249
(8) IPC, Section 311.1, is deleted.
1250
(9) IPC, Sections 312.10 through 312.10.2, are deleted and replaced with the
1251
following: "312.10 Backflow assembly testing. The premise owner or his designee shall have
1252
backflow prevention assemblies operation tested at the time of installation, repair, and
1253
relocation and at least on an annual basis thereafter, or more frequently as required by the
1254
authority having jurisdiction. Testing shall be performed by a Certified Backflow Preventer
1255
Assembly Tester. The assemblies that are subject to this paragraph are the Spill Resistant
1256
Vacuum Breaker, the Pressure Vacuum Breaker Assembly, the Double Check Backflow
1257
Prevention Assembly, the Double Check Detector Assembly Backflow Preventer, the Reduced
1258
Pressure Principle Backflow Preventer, and Reduced Pressure Detector Assembly."
1259
(10) In IPC, Section 403.1, a new footnote g is added as follows: "FOOTNOTE: g.
1260
When provided, in public toilet facilities there shall be an equal number of diaper changing
1261
facilities in male toilet rooms and female toilet rooms."
1262
(11) A new IPC, Section 406.4, is added as follows: "406.4 Automatic clothes washer
1263
safe pans. Safe pans, when installed under automatic clothes washers, shall be installed in
1264
accordance with Section 504.7."
1265
(12) A new IPC, Section 412.5, is added as follows: "412.5 Public toilet rooms. All
1266
public toilet rooms shall be equipped with at least one floor drain."
1267
(13) In IPC, Section 504.7.2, the following is added at the end of the section: "When
1268
permitted by the code official, the pan drain may be directly connected to a soil stack, waste
1269
stack, or branch drain. The pan drain shall be individually trapped and vented as required in
1270
Section 907.1. The pan drain shall not be directly or indirectly connected to any vent. The trap
1271
shall be provided with a trap primer conforming to ASSE 1018 or ASSE 1044."
1272
(14) A new IPC, Section 504.7.3, is added as follows: "504.7.3 Pan Designation. A
1273
water heater pan shall be considered an emergency receptor designated to receive the discharge
1274
of water from the water heater only and shall not receive the discharge from any other fixtures,
1275
devises or equipment."
1276
(15) IPC, Section 602.3, is deleted and replaced with the following: "602.3 Individual
1277
water supply. Where a potable public water supply is not available, individual sources of
1278
potable water supply shall be utilized provided that the source has been developed in
1279
accordance with Utah Code, Sections 73-3-1, 73-3-3, and 73-3-25, as administered by the
1280
Department of Natural Resources, Division of Water Rights. In addition, the quality of the
1281
water shall be approved by the local health department having jurisdiction. The source shall
1282
supply sufficient quantity of water to comply with the requirements of this chapter."
1283
(16) IPC, Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4, 602.3.5, and 602.3.5.1, are
1284
deleted.
1285
(17) A new IPC, Section 604.4.1, is added as follows: "604.4.1 Manually operated
1286
metering faucets. Self closing or manually operated metering faucets shall provide a flow of
1287
water for at least 15 seconds without the need to reactivate the faucet."
1288
(18) IPC, Section 606.5, is deleted and replaced with the following: "606.5 Water
1289
pressure booster systems. Water pressure booster systems shall be provided as required by
1290
Section 606.5.1 through 606.5.11."
1291
(19) A new IPC, Section 606.5.11, is added as follows: "606.5.11 Prohibited
1292
installation. In no case shall a booster pump be allowed that will lower the pressure in the
1293
public main to less than 20 psi."
1294
(20) IPC, Table 608.1, is deleted and replaced with the following:
1295
"TABLE 608.1
1296
General Methods of Protection
1297
Assembly Degree Application Installation Criteria
1298
(applicable of
1299
standard) Hazard
1300
Reduced High or Backpressure or a. The bottom of each
1301
Pressure Low Backsiphonage RP assembly shall
1302
Principle Backflow 1/2" - 16" be a minimum of 12
1303
Preventer (AWWA inches above the
1304
C511, USC-FCCCHR, ground or floor.
1305
ASSE 1013 b. RP assemblies shall
1306
CSA CNA/CSA-B64.4) NOT be installed in
1307
and Reduced Pressure a pit.
1308
Detector Assembly c. The relief valve on
1309
(ASSE 1047, USC- each RP assembly
1310
FCCCHR) shall not be directly
1311
connected to any waste
1312
disposal line, including
1313
sanitary sewer, storm rains,
1314
or vents.
1315
d. The assembly shall be
1316
installed in a horizontal
1317
position only unless listed
1318
or approved for vertical
1319
installation.
1320
Double Check Low Backpressure or a. If installed in a pit,
1321
Backflow Backsiphonage the DC assembly
1322
Prevention 1/2" - 16" shall be installed
1323
Assembly with a minimum of
1324
(AWWA C510, 12 inches of
1325
USC-FCCCHR, clearance between
1326
ASSE 1015) all sides of the
1327
Double Check vault including the
1328
Detector Assembly floor and roof or
1329
Backflow Preventer ceiling with adequate
1330
(ASSE 1048, room for testing and
1331
USC-FCCCHR) maintenance.
1332
b. Shall be installed in a
1333
horizontal position unless
1334
listed or approved for
1335
vertical installation.
1336
Pressure High or Backsiphonage a. Shall not be installed
1337
Vacuum Low 1/2" - 2" in an area that could be
1338
Breaker subjected to
1339
Assembly backpressure or
1340
(ASSE 1020, back drainage
1341
USC-FCCCHR) conditions.
1342
b. Shall be installed a
1343
minimum of 12 inches
1344
above all downstream
1345
piping and the highest point
1346
of use.
1347
c. Shall not be installed
1348
below ground or in a vault
1349
or pit.
1350
d. Shall be installed in a
1351
vertical position only.
1352
Spill High or Backsiphonage a. Shall not be
1353
Resistant Low 1/4" - 2" installed in an
1354
Vacuum area that could
1355
Breaker be subjected to
1356
(ASSE 1056, backpressure or
1357
USC-FCCCHR) back drainage
1358
conditions.
1359
&n