Download Zipped Amended WordPerfect HB0045.ZIP
[Introduced][Status][Bill Documents][Fiscal Note][Bills Directory]

H.B. 45

This document includes House Committee Amendments incorporated into the bill on Thu, Jan 28, 2010 at 11:24 AM by lerror. -->              1     

STATE CONSTRUCTION CODE ADOPTION

             2     
2010 GENERAL SESSION

             3     
STATE OF UTAH

             4     
Chief Sponsor: Michael T. Morley

             5     
Senate Sponsor: J. Stuart Adams

             6     
             7      LONG TITLE
             8      Committee Note:
             9          The Business and Labor Interim Committee recommended this bill.
             10      General Description:
             11          This bill adopts the State Construction Code in accordance with the Utah Uniform
             12      Building Standards Act.
             13      Highlighted Provisions:
             14          This bill:
             15          .    includes general provisions; and
             16          .    adopts the state construction code.
             17      Monies Appropriated in this Bill:
             18          None
             19      Other Special Clauses:
             20          This bill takes effect on July 1, 2010.
             21      Utah Code Sections Affected:
             22      ENACTS UNCODIFIED MATERIAL
             23          
             24      Be it enacted by the Legislature of the state of Utah:
             25          Section 1. Title -- Definitions -- General Provisions.
             26          (1) This bill is known as the "State Construction Code Adoption Act."
             27          (2) As used in this bill:


             28          (a) "Division" means the Division of Occupational and Professional Licensing created
             29      in Utah Code, Section 58-1-103 .
             30          (b) "State Construction Code" means the code adopted under Section 2 of this bill.
             31          (c) "Utah Code" means the Utah Code Annotated (1953), as amended.
             32          (3) As part of the division's compliance with Utah Code, Section 58-56-6, the division
             33      may modify the format of the state construction code to provide accessibility to users of the
             34      State Construction Code.
             35      Section 2. State Construction Code adopted.
             36          In accordance with Utah Code, Title 58, Chapter 56, Utah Uniform Building Standards
             37      Act, the Legislature, repeals the state construction code in effect on June 30, 2010, and adopts
             38      the following as the State Construction Code effective July 1, 2010:
             39     
State Construction Code

             40     
Part 1. General Provisions

             41      Section 101. Specific editions of construction codes of a nationally recognized code
             42      authority adopted -- Scope of application.
             43          (1) (a) Subject to the limitations contained in Subsections (4), (5), and (6), the
             44      following construction codes are incorporated by reference, and together with the amendments
             45      specified under this bill, are the construction standards to be applied to building construction,
             46      alteration, remodeling, and repair, and in the regulation of building construction, alteration,
             47      remodeling and repair in the state:
             48          (i) the 2009 edition of the International Building Code (IBC), including Appendix J,
             49      issued by the International Code Council;
             50          (ii) the 2008 edition of the National Electrical Code (NEC), issued by the National Fire
             51      Protection Association;
             52          (iii) the 2009 edition of the International Plumbing Code (IPC), issued by the
             53      International Code Council;
             54          (iv) the 2009 edition of the International Mechanical Code (IMC), issued by the
             55      International Code Council;
             56          (v) the 2009 edition of the International Residential Code (IRC), issued by the
             57      International Code Council;
             58          (vi) the 2009 edition of the International Energy Conservation Code (IECC), issued by


             59      the International Code Council;
             60          (vii) the 2009 edition of the International Fuel Gas Code (IFGC), issued by the
             61      International Code Council;
             62          (viii) subject to Subsection (3), the Federal Manufactured Housing Construction and
             63      Safety Standards Act (HUD Code), as issued by the Department of Housing and Urban
             64      Development and published in 24 C.F.R. Parts 3280 and 3282 (as revised April 1, 1990);
             65          (ix) subject to Subsection (2), Appendix E of the 2009 edition of the International
             66      Residential Code, issued by the International Code Council; and
             67          (x) subject to Subsection (2), the 2005 edition of the NFPA 225 Model Manufactured
             68      Home Installation Standard, issued by the National Fire Protection Association.
             69          (b) Consistent with Title 65A, Chapter 8, Management of Forest Lands and Fire
             70      Control, the Legislature adopts the 2006 edition of the Utah Wildland Urban Interface Code
             71      (UWUI) issued by the International Code Council, with the alternatives or amendments
             72      approved by the Utah Division of Forestry, as a construction code that may be adopted by a
             73      local compliance agency by local ordinance or other similar action as a local amendment to the
             74      codes listed in this Subsection (1).
             75          (2) The following are the installation standards for manufactured housing for new
             76      installations or for existing manufactured or mobile homes that are subject to relocation,
             77      building alteration, remodeling, or rehabilitation in the state:
             78          (a) The manufacturer's installation instruction for the model being installed is the
             79      primary standard.
             80          (b) If the manufacturer's installation instruction for the model being installed is not
             81      available or is incomplete, the following standards apply:
             82          (i) Appendix E of the 2009 edition of the IRC, as issued by the International Code
             83      Council for installations defined in Section AE101 of Appendix E; or
             84          (ii) if an installation is beyond the scope of the 2009 edition of the IRC as defined in
             85      Section AE101 of Appendix E, the 2005 edition of the NFPA 225 Model Manufactured Home
             86      Installation Standard, issued by the National Fire Protection Association.
             87          (c) A manufacturer, dealer, or homeowner is permitted to design for unusual
             88      installation of a manufactured home not provided for in the manufacturer's standard installation
             89      instruction Appendix E of the 2009 edition of the IRC, or the 2005 edition of the NFPA 225, if


             90      the design is approved in writing by a professional engineer or architect licensed in Utah.
             91          (d) For a mobile home built before June 15, 1976, the home shall also comply with the
             92      additional installation and safety requirements specified in State Construction Code, Section
             93      208.
             94          (3) Pursuant to the HUD Code Section 604(d), a manufactured home may be installed
             95      in the state that does not meet the local snow load requirements as specified in State
             96      Construction Code, Section 202, except that the manufactured home shall have a protective
             97      structure built over the home that meets the IRC and the snow load requirements under State
             98      Construction Code, Section 202.
             99          (4) To the extent that a construction code adopted under Subsection (1) establishes a
             100      local administrative function or establishes a method of appeal which pursuant to Utah Code,
             101      Section 58-56-8 is designated to be established by the compliance agency:
             102          (a) that provision of the construction code is not included in the State Construction
             103      Code; and
             104          (b) a compliance agency may establish provisions to establish a local administrative
             105      function or a method of appeal.
             106          (5) (a) To the extent that a construction code adopted under Subsection (1) establishes
             107      a provision, standard, or reference to another code that by state statute is designated to be
             108      established or administered by another state agency, or a local city, town, or county
             109      jurisdiction:
             110          (i) that provision of the construction code is not included in the State Construction
             111      Code; and
             112          (ii) the agency or local government has authority over that provision of the construction
             113      code.
             114          (b) Provisions excluded under this Subsection (5) include:
             115          (i) the International Property Maintenance Code;
             116          (ii) the International Private Sewage Disposal Code, authority over which is reserved to
             117      the Department of Health and the Department of Environmental Quality;
             118          (iii) the International Fire Code, authority over which is reserved to the Utah Fire
             119      Prevention Board, pursuant to Utah Code, Section 53-7-106 ;
             120          (iv) a day care provision that is in conflict with Utah Code, Title 26, Chapter 39, Utah


             121      Child Care Licensing Act, authority over which is designated to the Utah Department of
             122      Health; and
             123          (v) a wildland urban interface provision that goes beyond the authority under Utah
             124      Code, Section 58-56-4, for the State Construction Code, authority over which is designated to
             125      the Utah Division of Forestry or to a local compliance agency.
             126          (6) If a construction code adopted under Subsection (1) establishes a provision that
             127      exceeds the scope described in Title 58, Chapter 56, Utah Uniform Building Standards Act, to
             128      the extent the scope is exceeded, the provision is not included in the State Construction Code.
             129     
Part 2. Statewide Amendments

             130      Section 201. Statewide amendments to the IBC.
             131          The following are adopted as amendments to the IBC to be applicable statewide:
             132          (1) IBC, Section 106, is deleted.
             133          (2) (a) In IBC, Section 110, a new section is added as follows: "110.3.5,
             134      Weather-resistant exterior wall envelope. An inspection shall be made of the weather-resistant
             135      exterior wall envelope as required by Section 1403.2, and flashing as required by Section
             136      1405.4 to prevent water from entering the weather-resistive barrier."
             137          (b) The remaining sections of IBC, Section 110, are renumbered as follows: 110.3.6,
             138      Lath or gypsum board inspection; 110.3.7, Fire-and smoke-resistant penetrations; 110.3.8
             139      Energy efficiency inspections; 110.3.9 Other inspections; 110.3.10 Special inspections;
             140      110.3.11 Final inspection.
             141          (3) IBC, Section 115.1, is deleted and replaced with the following: "115.1 Authority.
             142      Whenever the building official finds any work regulated by this code being performed in a
             143      manner either contrary to the provisions of this code or other pertinent laws or ordinances or
             144      dangerous or unsafe, the building official is authorized to stop work."
             145          (4) In IBC, Section 202, the definition for "Assisted Living Facility" is deleted and
             146      replaced with the following: "ASSISTED LIVING FACILITY. See Section 308.1.1."
             147          (5) In IBC, Section 202, the definition for "Child Care Facilities" is deleted and
             148      replaced with the following: "CHILD CARE FACILITIES. See Section 308.3.1."
             149          (6) In the list in IBC, Section 304.1, "Ambulatory health care facilities" is deleted and
             150      replaced with "Ambulatory health care facilities with four or fewer surgical operating rooms."
             151          (7) IBC, Section 305.2, is deleted and replaced with the following: "305.2 Day care.


             152      The use of a building or structure, or portion thereof, for educational, supervision, child day
             153      care centers, or personal care services of more than four children shall be classified as a Group
             154      E occupancy. See Section 424 for special requirements for Group E child day care centers.
             155      Exception: Areas used for child day care purposes with a Residential Certificate or a Family
             156      License, as defined in Utah Administrative Code, R430-90 Licensed Family Child Care, may
             157      be located in a Group R-2 or R-3 occupancy as provided in Section 310.1 or shall comply with
             158      the International Residential Code in accordance with Section 101.2. Areas used for Hourly
             159      Child Care Centers, as defined in Utah Administrative Code, R430-60, or Out of School Time
             160      Programs, as defined in Utah Administrative Code, R430-70, may be classified as accessory
             161      occupancies."
             162          (8) In IBC, Section 308, the following definitions are added: "308.1.1 Definitions. The
             163      following words and terms shall, for the purposes of this section and as used elsewhere in this
             164      code, have the meanings shown herein.
             165      TYPE I ASSISTED LIVING FACILITY. A residential facility licensed by the Utah
             166      Department of Health that provides a protected living arrangement for ambulatory,
             167      non-restrained persons who are capable of achieving mobility sufficient to exit the facility
             168      without the assistance of another person.
             169      TYPE II ASSISTED LIVING FACILITY. A residential facility licensed by the Utah
             170      Department of Health that provides an array of coordinated supportive personal and health care
             171      services to residents who meet the definition of semi-independent.
             172      SEMI-INDEPENDENT. A person who is:
             173      A. Physically disabled but able to direct his or her own care; or
             174      B. Cognitively impaired or physically disabled but able to evacuate from the facility with the
             175      physical assistance of one person.
             176      RESIDENTIAL TREATMENT/SUPPORT ASSISTED LIVING FACILITY. A residential
             177      treatment/support assisted living facility which creates a group living environment for four or
             178      more residents licensed by the Utah Department of Human Services, and provides a protected
             179      living arrangement for ambulatory, non-restrained persons who are capable of achieving
             180      mobility sufficient to exit the facility without the physical assistance of another person."
             181          (9) In IBC, Section 308.2, the words "Assisted living facilities" are deleted and
             182      replaced with "Type I Assisted living facilities."


             183          (10) IBC, Section 308.3, is deleted and replaced with the following: "308.3 Group I-2.
             184      This occupancy shall include buildings and structures used for medical, surgical, psychiatric,
             185      nursing, or custodial care on a 24-hour basis of more than three persons who are not capable of
             186      self-preservation. This group shall include, but not be limited to the following: hospitals,
             187      nursing homes (both intermediate care facilities and skilled nursing facilities), mental hospitals,
             188      detoxification facilities, ambulatory surgical centers with five or more operating rooms where
             189      care is less than 24 hours, and type II assisted living facilities. Type II assisted living facilities
             190      with five or fewer persons shall be classified as a Group R-4. Type II assisted living facilities
             191      as defined in 308.1.1 with at least six and not more than sixteen residents shall be classified as
             192      a Group I-1 facility."
             193          (11) In IBC, Section 308.3.1, the definition for "CHILD CARE FACILITIES" is
             194      deleted and replaced with the following: "CHILD CARE FACILITIES. A child care facility, as
             195      licensed by the Department of Human Services in Utah Administrative Code, R501, that
             196      provides care on a 24-hour basis to more than four children 2 1/2 years of age or less shall be
             197      classified as Group I-2."
             198          (12) IBC, Section 308.5, is deleted and replaced with the following: "308.5 Group I-4,
             199      day care facilities. This group shall include buildings and structures occupied by persons of any
             200      age who receive custodial care less than 24 hours by individuals other than parents or
             201      guardians, relatives by blood, marriage, or adoption, and in a place other than the home of the
             202      person cared for. A facility such as the above with four or fewer persons shall be classified as
             203      an R-3 or shall comply with the International Residential Code in accordance with Section
             204      101.2. Places of worship during religious functions and Group E child day care centers are not
             205      included."
             206          (13) IBC, Section 308.5.2, is deleted.
             207          (14) In IBC, Section 310.1, in the subsection designated as R-1, at the end of the
             208      sentence beginning with "Congregate living facilities" the following is added: "or shall comply
             209      with the International Residential Code."
             210          (15) In IBC, Section 310.1, in the subsection designated as R-2, at the end of the
             211      sentence beginning with "Congregate living facilities" the following is added: "or shall comply
             212      with the International Residential Code."
             213          (16) In IBC, Section 310.1, the following is added at the end of the subsection


             214      designated as R-3: "Areas used for day care purposes may be located in a residential dwelling
             215      unit under all of the following conditions:
             216      1. Compliance with the Utah Administrative Code, R710-8, Day Care Rules, as enacted under
             217      the authority of the Utah Fire Prevention Board.
             218      2. Use is approved by the State Department of Health, as enacted under the authority of the
             219      Utah Code, Title 26, Chapter 39, Utah Child Care Licensing Act, and in any of the following
             220      categories:
             221      a. Utah Administrative Code, R430-50, Residential Certificate Child Care.
             222      b. Utah Administrative Code, R430-90, Licensed Family Child Care.
             223      3. Compliance with all zoning regulations of the local regulator."
             224          (17) In IBC, Section 310.1, the subsection designated as R-4 is deleted and replaced
             225      with the following: "R-4: Residential occupancies shall include buildings arranged for
             226      occupancy as Type I Assisted Living Facilities or Residential Treatment/Support Assisted
             227      Living Facilities including more than five but not more than 16 residents, excluding staff.
             228      Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3
             229      except as otherwise provided for in this code."
             230          (18) In IBC, Section 310.2, the definition for "Residential Care/Assisted Living
             231      Facilities" is deleted and replaced with the following: "Assisted Living Facilities, see Section
             232      308.1.1".
             233          (19) Section IBC, 403.5.5, is deleted.
             234          (20) In IBC, Section 422.1, the words "Sections 422.1 to 422.6" are replaced with
             235      "Sections 422.1 to 422.7".
             236          (21) In IBC, Section 422, a new section is added as follows: "422.7 Separation.
             237      Occupancies classified as Group B Ambulatory Health Care Facilities shall be separated from
             238      all surrounding tenants and occupancies in accordance with Table 508.4 but not less than
             239      one-hour fire barrier when the suite is capable of providing care for four or more care recipients
             240      who are incapable of self preservation."
             241          (22) A new IBC, Section 424, is added as follows: "Section 424 Group E Child Day
             242      Care Centers. Group E child day care centers shall comply with Section 424.
             243      424.1 Location at grade. Group E child day care centers shall be located at the level of exit
             244      discharge.


             245      Exception: Child day care spaces for children over the age of 24 months may be located on the
             246      second floor of buildings equipped with automatic fire protection throughout and an automatic
             247      fire alarm system.
             248      424.2 Egress. All Group E child day care spaces with an occupant load of more than 10 shall
             249      have a second means of egress. If the second means of egress is not an exit door leading
             250      directly to the exterior, the room shall have an emergency escape and rescue window
             251      complying with Section 1029.
             252      424.3 All Group E Child Day Care Centers shall comply with Utah Administrative Code,
             253      R430-100 Child Care Centers."
             254          (23) In IBC, Section 504.2, a new section is added as follows: "504.2.1
             255      Notwithstanding the exceptions to Section 504.2, Group I-2 Assisted Living Facilities shall be
             256      allowed to be two stories of Type V-A construction when all of the following apply:
             257      1. All secured units are located at the level of exit discharge in compliance with Section
             258      1008.1.9.3 as amended;
             259      2. The total combined area of both stories shall not exceed the total allowable area for a
             260      one-story building; and
             261      3. All other provisions that apply in Section 407 have been provided."
             262          (24) In IBC, Table 508.4, a new footnote g is added as follows: "g. See Section 422.7
             263      for additional requirements of Group B Ambulatory Health Care Facilities."
             264          (25) In IBC, Section 707.5.1, a new exception 4 is added as follows: "4. Group B
             265      Ambulatory Health Care Facilities."
             266          (26) In IBC, Section (F)902, the definition for record drawings is deleted and replaced
             267      with the following: "(F)RECORD DRAWINGS. Drawings ("as builts") that document all
             268      aspects of a fire protection system as installed."
             269          (27) In IBC, Section (F)903.2.2, the words "all fire areas" are deleted and replaced with
             270      "buildings".
             271          (28) IBC, Section (F)903.2.4, condition 2, is deleted and replaced with the following:
             272      "2. A Group F-1 fire area is located more than three stories above the lowest level of fire
             273      department vehicle access."
             274          (29) IBC, Section (F)903.2.7, condition 2, is deleted and replaced with the following:
             275      "2. A Group M fire area is located more than three stories above the lowest level of fire


             276      department vehicle access."
             277          (30) IBC, Section (F)903.2.8, is deleted and replaced with the following: "(F)903.2.8
             278      Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be
             279      provided throughout all buildings with a Group R fire area.
             280      Exceptions:
             281      1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses)
             282      constructed in accordance with the International Residential Code For One- and Two-Family
             283      Dwellings.
             284      2. Group R-4 fire areas not more than 4,500 gross square feet and not containing more than 16
             285      residents, provided the building is equipped throughout with an approved fire alarm system that
             286      is interconnected and receives its primary power from the building wiring and a commercial
             287      power system."
             288          (31) IBC, Section (F)903.2.9, condition 2, is deleted and replaced with the following:
             289      "2. A Group S-1 fire area is located more than three stories above the lowest level of fire
             290      department vehicle access."
             291          (32) IBC, Section (F)903.2.10, is deleted and replaced with the following: "(F)903.2.10
             292      Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as
             293      parking garages in accordance with Section 406.2 or where located beneath other groups.
             294      Exception 1: Parking garages of less than 5,000 square feet (464 m2) accessory to Group R-3
             295      occupancies.
             296      Exception 2: Open parking garages not located beneath other groups if one of the following
             297      conditions is met:
             298      a. Access is provided for fire fighting operations to within 150 feet (45,720 mm) of all
             299      portions of the parking garage as measured from the approved fire department vehicle access;
             300      or
             301      b. Class I standpipes are installed throughout the parking garage."
             302          (33) In IBC, Section (F)903.2.10.1, the last clause "where the fire area exceeds 5,000
             303      square feet (464 m2)" is deleted.
             304          (34) IBC, Section (F)904.11, is deleted and replaced with the following: "(F)904.11
             305      Commercial cooking systems. The automatic fire-extinguishing system for commercial
             306      cooking systems shall be of a type recognized for protection of commercial cooking equipment


             307      and exhaust systems. Pre-engineered automatic extinguishing systems shall be tested in
             308      accordance with UL 300 and listed and labeled for the intended application. The system shall
             309      be installed in accordance with this code, its listing and the manufacturer's installation
             310      instructions.
             311      Exception: Factory-built commercial cooking recirculating systems that are tested in
             312      accordance with UL 710B and listed, labeled, and installed in accordance with Section 304.1 of
             313      the International Mechanical Code."
             314          (35) IBC, Subsections (F)904.11.3, (F)904.11.3.1, (F)904.11.4, and (F)904.11.4.1, are
             315      deleted.
             316          (36) A new IBC, Section (F)907.9, is added as follows: "Section (F)907.9 Carbon
             317      monoxide alarms. Carbon monoxide alarms shall be installed on each habitable level of a
             318      dwelling unit or sleeping unit in Groups R-2, R-3, R-4, and I-1 equipped with fuel burning
             319      appliances and in dwelling units that have attached garages. If more than one carbon monoxide
             320      alarm is required, they shall be interconnected as required in the International Fire Code,
             321      Chapter 9, Section 907.2.11.3. In new construction, carbon monoxide alarms shall receive their
             322      primary power as required in the International Fire Code, Chapter 9, Section 907.2.11.4. Listed
             323      single- and multiple-station carbon monoxide alarms shall comply with UL 2034 and shall be
             324      installed in accordance with the provisions of this code and NFPA 720."
             325          (37) In IBC, Section 1008.1.9.6:
             326          (a) the words "Group I-1 and" are added in the title and in the first sentence before the
             327      words "Group I-2";
             328          (b) the word "delayed" is deleted throughout and replaced with "controlled"; and
             329          (c) the last sentence before the numbered subsections 1 through 6 is deleted.
             330          (38) In IBC, Section 1009.4.2, exception 5 is deleted and replaced with the following:
             331      "5. In Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group
             332      U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual
             333      dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches (203
             334      mm) and the minimum tread depth shall be 9 inches (229 mm). The minimum winder tread
             335      depth at the walk line shall be 10 inches (254 mm), and the minimum winder tread depth shall
             336      be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25
             337      inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less


             338      than 10 inches (254 mm)."
             339          (39) In IBC, Section 1009.12, a new exception 6 is added as follows: "6. In
             340      occupancies in Group R-3, as applicable in Section 101.2 and in occupancies in Group U,
             341      which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails
             342      shall be provided on at least one side of stairways consisting of four or more risers."
             343          (40) In IBC, Section 1013.2, the words "adjacent fixed seating" are deleted.
             344          (41) In IBC, Section 1013.2, a new exception 5 is added as follows: "5. For
             345      occupancies in Group R-3 and within individual dwelling units in occupancies in Group R-2,
             346      as applicable in Section 101.2, guards shall form a protective barrier not less than 36 inches
             347      (914 mm) in height."
             348          (42) In IBC, Section 1015.2.2, the following sentence is added at the end: "Additional
             349      exits or exit access doorways shall be arranged a reasonable distance apart so that if one
             350      becomes blocked, the others will be available."
             351          (43) IBC, Section 1024, is deleted.
             352          (44) A new IBC, Section 1109.7.1, is added as follows: "1109.7.1 Platform
             353      (wheelchair) lifts. All platform (wheelchair) lifts shall be capable of independent operation
             354      without a key."
             355          (45) In IBC, Section 1208.4, subparagraph 1 is deleted and replaced with the
             356      following: "1. The unit shall have a living room of not less than 165 square feet (15.3 m2) of
             357      floor area. An additional 100 square feet (9.3 m2) of floor area shall be provided for each
             358      occupant of such unit in excess of two."
             359          (46) In IBC, Table 1604.5, Occupancy Category III, in the sentence that begins Group
             360      I-2, a new footnote b is added as follows: "b. Type II Assisted Living Facilities that are I-2
             361      occupancy classifications in accordance with Section 308 shall be Occupancy Category II in
             362      this table."
             363          (47) In IBC, Section 1605.2.1, the formula shown as "f2 = 0.2 for other roof
             364      configurations" is deleted and replaced with the following: "f2 = 0.20 + .025(A-5) for other
             365      configurations where roof snow load exceeds 30 psf;
             366      f2 = 0 for roof snow loads of 30 psf (1.44kN/m2) or less.
             367      Where A = Elevation above sea level at the location of the structure (ft/1000)."
             368          (48) In IBC, Section 1605.3.1 and Section 1605.3.2, exception 2 in each section is


             369      deleted and replaced with the following: "2. Flat roof snow loads of 30 pounds per square foot
             370      (1.44 kNm2) or less need not be combined with seismic loads. Where flat roof snow loads
             371      exceed 30 pounds per square foot (1.44 kNm2), the snow loads may be reduced in accordance
             372      with the following in load combinations including both snow and seismic loads. Ws as
             373      calculated below, shall be combined with seismic loads.
             374      Ws = (0.20 + 0.025(A-5))Pf is greater than or equal to 0.20 Pf.
             375      Where:
             376      Ws = Weight of snow to be included in seismic calculations;
             377      A = Elevation above sea level at the location of the structure (ft/1000)
             378      Pf = Design roof snow load, psf;
             379      For the purpose of this section, snow load shall be assumed uniform on the roof footprint
             380      without including the effects of drift or sliding. The Importance Factor, I, used in calculating Pf
             381      may be considered 1.0 for use in the formula for Ws.".
             382          (49) IBC, Section 1608.1, is deleted and replaced with the following: "1608.1 General.
             383      Except as modified in section 1608.1.1, 1608.1.2, and 1608.1.3 design snow loads shall be
             384      determined in accordance with Chapter 7 of ASCE 7, but the design roof load shall not be less
             385      than that determined by Section 1607."
             386          (50) A new IBC, Section 1608.1.1, is added as follows: "1608.1.1 Section 7.4.5 of
             387      Chapter 7 of ASCE 7 referenced in Section 1608.1 of the IBC is deleted and replaced with the
             388      following: "Section 7.4.5 Ice Dams and Icicles Along Eaves. Where ground snow loads exceed
             389      75 psf, eaves shall be capable of sustaining a uniformly distributed load of 2pf on all
             390      overhanging portions. No other loads except dead loads shall be present on the roof when this
             391      uniformly distributed load is applied. All building exits under down-slope eaves shall be
             392      protected from sliding snow and ice."
             393          (51) In IBC, Section 1608.1.2, a new section is added as follows: "1608.1.2 Utah Snow
             394      Loads. The ground snow load, Pg, to be used in the determination of design snow loads for
             395      buildings and other structures shall be determined by using the following formula: Pg = (Po2 +
             396      S2(A-Ao)2)0.5 for A greater than Ao, and Pg = Po for A less than or equal to Ao.
             397      WHERE:
             398      Pg = Ground snow load at a given elevation (psf);
             399      Po = Base ground snow load (psf) from Table No. 1608.1.2(a);


             400      S = Change in ground snow load with elevation (psf/100 ft.) From Table No. 1608.1.2(a);
             401      A = Elevation above sea level at the site (ft./1000);
             402      Ao = Base ground snow elevation from Table 1608.1.2(a) (ft./1000).
             403      The building official may round the roof snow load to the nearest 5 psf. The ground snow load,
             404      Pg, may be adjusted by the building official when a licensed engineer or architect submits data
             405      substantiating the adjustments. A record of such action together with the substantiating data
             406      shall be provided to the division for a permanent record.
             407      The building official may also directly adopt roof snow loads in accordance with Table
             408      1608.1.2(b), provided the site is no more than 100 ft. higher than the listed elevation.
             409      Where the minimum roof live load in accordance with section 1607.11 is greater than the
             410      design roof snow load, such roof live load shall be used for design, however, it shall not be
             411      reduced to a load lower than the design roof snow load. Drifting need not be considered for
             412      roof snow loads less than 20 psf."
             413          (52) IBC, Table 1608.1.2(a) and Table 1608.1.2(b), are added as follows:
             414     
"TABLE NO. 1608.1.2(a)

             415     
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS

             416              COUNTY    Po    S    Ao
             417              Beaver    43    63    6.2
             418              Box Elder    43    63    5.2
             419              Cache        50    63    4.5
             420              Carbon    43    63    5.2
             421              Daggett    43    63    6.5
             422              Davis        43    63    4.5
             423              Duchesne    43    63    6.5
             424              Emery        43    63    6.0
             425              Garfield    43    63    6.0
             426              Grand        36    63    6.5
             427              Iron        43    63    5.8
             428              Juab        43    63    5.2
             429              Kane        36    63    5.7
             430              Millard    43    63    5.3


             431              Morgan    57    63    4.5
             432              Piute        43    63    6.2
             433              Rich        57    63    4.1
             434              Salt Lake    43    63    4.5
             435              San Juan    43    63    6.5
             436              Sanpete    43    63    5.2
             437              Sevier        43    63    6.0
             438              Summit    86    63    5.0
             439              Tooele     43    63    4.5
             440              Uintah        43    63    7.0
             441              Utah        43    63    4.5
             442              Wasatch    86    63    5.0
             443              Washington     29    63    6.0
             444              Wayne    36    63    6.5
             445              Weber        43    63    4.5
             446     
TABLE NO. 1608.1.2(b)

             447     
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)

             448                                  Roof Snow    Ground Snow
             449                                  Load (PSF)    Load (PSF)
             450              Beaver County
             451                  Beaver        5920 ft.    43        62
             452              Box Elder County
             453                  Brigham City        4300 ft.    30        43
             454                  Tremonton        4290 ft.    30        43
             455              Cache County
             456                  Logan            4530 ft.    35        50
             457                  Smithfield        4595 ft.    35        50
             458              Carbon County
             459                  Price            5550 ft.    30        43
             460              Daggett County
             461                  Manila        5377 ft.    30        43


             462              Davis County
             463                  Bountiful        4300 ft.    30        43
             464                  Farmington        4270 ft.    30        43
             465                  Layton        4400 ft.    30         43
             466                  Fruit Heights        4500 ft.    40        57
             467              Duchesne County
             468                  Duchesne        5510 ft.    30        43
             469                  Roosevelt        5104 ft.    30        43
             470              Emery County
             471                  Castledale        5660 ft.    30        43
             472                  Green River        4070 ft.    25        36
             473              Garfield County
             474                  Panguitch        6600 ft.    30        43
             475              Grand County
             476                  Moab            3965 ft. H. [ 5 ] 25 .H     36
             477              Iron County
             478                  Cedar City        5831 ft.    30        43
             479              Juab County
             480                  Nephi            5130 ft.    30        43
             481              Kane County
             482                  Kanab            5000 ft.    25        36
             483              Millard County
             484                  Millard        5000 ft.    30        43
             485                  Delta            4623 ft.    30        43
             486              Morgan County
             487                  Morgan        5064 ft.    40        57
             488              Piute County
             489                  Piute            5996 ft.    30        43
             490              Rich County
             491                  Woodruff        6315 ft.    40        57
             492              Salt Lake County


             493                  Murray        4325 ft.    30        43
             494                  Salt Lake City     4300 ft.    30        43
             495                  Sandy            4500 ft.    30        43
             496                  West Jordan        4375 ft.    30        43
             497                  West Valley        4250 ft.    30        43
             498              San Juan County
             499                  Blanding        6200 ft.    30        43
             500                  Monticello        6820 ft.    35        50
             501              Sanpete County
             502                  Fairview        6750 ft.    35        50
             503                  Mt. Pleasant        5900 ft.    30        43
             504                  Manti            5740 ft.    30        43
             505                  Ephraim        5540 ft.    30        43
             506                  Gunnison        5145 ft.    30        43
             507              Sevier County
             508                  Salina            5130 ft.    30        43
             509                  Richfield        5270 ft.    30        43
             510              Summit County
             511                  Coalville        5600 ft.    60        86
             512                  Kamas        6500 ft.    70        100
             513                  Park City        6800 ft.    100        142
             514                  Park City        8400 ft.    162        231
             515                  Summit Park        7200 ft.    90        128
             516              Tooele County
             517                  Tooele        5100 ft.    30        43
             518              Uintah County
             519                  Vernal            5280 ft.    30        43
             520              Utah County
             521                  American Fork    4500 ft.    30        43
             522                  Orem            4650 ft.    30        43
             523                  Pleasant Grove    5000 ft.    30        43


             524                  Provo            5000 ft.    30        43
             525                  Spanish Fork        4720 ft.    30        43
             526              Wasatch County
             527                  Heber            5630 ft.    60        86
             528              Washington County
             529                  Central        5209 ft.    25        36
             530                  Dameron        4550 ft.    25        36
             531                  Leeds            3460 ft.    20        29
             532                  Rockville        3700 ft.    25        36
             533                  Santa Clara        2850 ft.    15 (1)        21
             534                  St. George        2750 ft.    15 (1)        21
             535              Wayne County
             536                  Loa            7080 ft.    30        43
             537                  Hanksville        4308 ft.    25        36
             538              Weber County
             539                  North Ogden        4500 ft.    40        57
             540                  Ogden            4350 ft.    30        43
             541      NOTES
             542      (1) The IBC requires a minimum live load - See 1607.11.2.
             543      (2) This table is informational only in that actual site elevations may vary. Table is only valid
             544      if site elevation is within 100 feet of the listed elevation."
             545          (53) A new IBC, Section 1608.1.3, is added as follows: "1608.1.3 Thermal Factor. The
             546      value for the thermal factor, Ct, used in calculation of pf shall be determined from Table 7.3 in
             547      ASCE 7.
             548      Exception: Except for unheated structures, the value of Ct need not exceed 1.0 when ground
             549      snow load, Pg is calculated using Section 1608.1.2 as amended."
             550          (54) IBC, Section 1608.2, is deleted and replaced with the following: "1608.2 Ground
             551      Snow Loads. The ground snow loads to be used in determining the design snow loads for roofs
             552      in states other than Utah are given in Figure 1608.2 for the contiguous United States and Table
             553      1608.2 for Alaska. Site-specific case studies shall be made in areas designated CS in figure
             554      1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2


             555      and for all sites within the CS areas shall be approved. Ground snow load determination for
             556      such sites shall be based on an extreme value statistical analysis of data available in the vicinity
             557      of the site using a value with a 2-percent annual probability of being exceeded (50-year mean
             558      recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as
             559      approved by the building official."
             560          (55) In IBC, Section 1609.1.1, a new exception 7 is added as follows: "7. The wind
             561      design procedure as found in Section 1616 through 1624 of the 1997 Uniform Building Code
             562      may be used as an alternative wind design procedure for signs and free standing walls as listed
             563      in item 7 listed in Table 16-H of the 1997 Uniform Building Code. The Importance Factor, I,
             564      shall be determined in accordance with Table 6-1 of ASCE 7. Stress increases are only allowed
             565      as provided in Section 1605.3 of the 2009 IBC."
             566          (56) A new IBC, Section 1613.1.1, is added as follows: "1613.1.1 ASCE 12.7.2 and
             567      12.14.8.1 of Chapter 12 of ASCE 7 referenced in Section 1613.1, Definition of W, Item 4 is
             568      deleted and replaced with the following:
             569      4. Where the flat roof snow load, Pf, exceeds 30 psf, the snow load included in seismic design
             570      shall be calculated, in accordance with the following formula: Ws = (0.20 + 0.025(A-5))Pf is
             571      greater than or equal to 0.20 Pf.
             572      WHERE:
             573      Ws = Weight of snow to be included in seismic calculations;
             574      A = Elevation above sea level at the location of the structure (ft/1000);
             575      Pf = Design roof snow load, psf.
             576      For the purposes of this section, snow load shall be assumed uniform on the roof footprint
             577      without including the effects of drift or sliding. The Importance Factor, I, used in calculating Pf
             578      may be considered 1.0 for use in the formula for Ws."
             579          (57) A new IBC, Section 1613.8, is added as follows: "1613.8 ASCE 7, Section
             580      13.5.6.2.2 paragraph (e) is modified to read as follows: (e) Penetrations shall have a sleeve or
             581      adapter through the ceiling tile to allow for free movement of at least 1 inch (25 mm) in all
             582      horizontal directions.
             583      Exceptions:
             584      1. Where rigid braces are used to limit lateral deflections.
             585      2. At fire sprinkler heads in frangible surfaces per NFPA 13."


             586          (58) A new IBC, Section 1807.1.6.4, is added as follows: "1807.1.6.4 Empirical
             587      concrete foundation design. Group R, Division 3 Occupancies three stories or less in height,
             588      and Group U Occupancies, which are constructed in accordance with Section 2308, or with
             589      other methods employing repetitive wood-frame construction or repetitive cold-formed steel
             590      structural member construction, shall be permitted to have concrete foundations constructed in
             591      accordance with Table 1807.1.6.4."
             592          (59) A new IBC, Table 1807.1.6.4 is added as follows:
             593     
" TABLE 1807.1.6.4

             594     
EMPIRICAL FOUNDATION WALLS (1,7,8)

             595      Max. Height    Top Edge    Min.    Vertical    Horizontal    Steel at    Max. Lintel    Min. Lintel
             596              Support    Thickness    Steel (2)    Steel (3)    Openings (4)    Length    Length
             597      2'(610 mm)    None    6"    (5)    2#4 Bars    2- #4 Bars above    2'(610 mm)    2"for each
             598                              1- #4 Bar each side        foot of
             599                              1- #4 Bar below        opening
             600                                      width;
             601                                      min. 6"
             602      3'(914 mm)    None    6"    #4@32"    3-#4 Bars    2- #4 Bars above    2'(610 mm)    2"for each
             603                              1- #4 Bar each side        foot of
             604                              1- #4 Bar below        opening
             605                                      width;
             606                                      min. 6"
             607      4'(1219 mm)    None    6"    #4@32"    4-#4 Bars    2- #4 Bars above    3'(914 mm)    2"for each
             608                              1- #4 Bar each side        foot of
             609                              1- #4 Bar below        opening
             610                                      width;
             611                                      min. 6"
             612      6'(1829 mm)    Floor or roof    8"    #4@24"    5-#4 Bars    2- #4 Bars above        2"for each
             613              Diaphragm                1- #4 Bar each side        foot of
             614              (6)                1- #4 Bar below        opening
             615                                      width;
             616                                       min. 6"
             617      8'(2438 mm)    Floor or roof    8"    #4@24"    6-#4 Bars    2- #4 Bars above    6'(1829 mm)    2"for each
             618              Diaphragm                1- #4 Bar each side        foot of
             619              (6)                1- #4 Bar below        opening
             620                                      width;
             621                                      min. 6"
             622      9'(2743 mm)    Floor or roof    8"    #4@16"    7-#4 Bars    2- #4 Bars above    6'(1829 mm)    2"for each
             623              Diaphragm                1- #4 Bar each side        foot of
             624              (6)                1- #4 Bar below        opening


             625                                      width;
             626                                      min. 6"
             627      Over 9'        Engineering required for each column    
             628      (2743 mm)     
             629      Footnotes:
             630      (1) Based on 3,000 psi (20.6 Mpa) concrete and 60,000 psi (414 Mpa) reinforcing steel.
             631      (2) To be placed in the center of the wall, and extended from the footing to within three inches
             632      (76 mm) of the top of the wall; dowels of #4 bars to match vertical steel placement shall be
             633      provided in the footing, extending 24 inches (610 mm) into the foundation wall.
             634      (3) One bar shall be located in the top four inches (102 mm), one bar in the bottom four inches
             635      (102 mm) and the other bars equally spaced between. Such bar placement satisfies the
             636      requirements of Section 1805.9. Corner reinforcing shall be provided so as to lap 24 inches
             637      (610 mm).
             638      (4) Bars shall be placed within two inches (51 mm) of the openings and extend 24 inches (610
             639      mm) beyond the edge of the opening; vertical bars may terminate three inches (76 mm) from
             640      the top of the concrete.
             641      (5) Dowels of #4 bar at 32 inches on center shall be provided in the footing, extending 18
             642      inches (457 mm) into the foundation wall.
             643      (6) Diaphragm shall conform to the requirements of Section 2308.
             644      (7) Footing shall be a minimum of nine inches thick by 20 inches wide.
             645      (8) Soil backfill shall be soil classification types GW, GP, SW, or SP, per Table 1610.1. Soil
             646      shall not be submerged or saturated in groundwater."
             647          (60) A new IBC, Section 2306.1.5, is added as follows: "2306.1.5 Load duration
             648      factors. The allowable stress increase of 1.15 for snow load, shown in Table 2.3.2, Frequently
             649      Used Load Duration Factors, Cd, of the National Design Specifications, shall not be utilized at
             650      elevations above 5,000 feet (1524 M)."
             651          (61) In IBC, Section 2308.6, a new exception is added as follows: "Exception: Where
             652      foundation plates or sills are bolted or anchored to the foundation with not less than 1/2 inch
             653      (12.7 mm) diameter steel bolts or approved anchors, embedded at least 7 inches (178 mm) into
             654      concrete or masonry and spaced not more than 32 inches (816 mm) apart, there shall be a
             655      minimum of two bolts or anchor straps per piece located not less than 4 inches (102 mm) from
             656      each end of each piece. A properly sized nut and washer shall be tightened on each bolt to the


             657      plate."
             658          (62) IBC, Section 2506.2.1, is deleted and replaced with the following: "2506.2.1
             659      Other materials. Metal suspension systems for acoustical and lay-in panel ceilings shall
             660      conform with ASTM C635 listed in Chapter 35 and Section 13.5.6 of ASCE 7-05, as amended
             661      in Section 1613.8, for installation in high seismic areas."
             662          (63) In IBC, Section 2902.1, the title for Table 2902.1 is deleted and replaced and a
             663      new footnote g is added as follows:
             664          (a) "Table 2902.1, Minimum Number of Required Plumbing Facilitiesa, g"; and
             665          (b) "FOOTNOTE: g. When provided, in public toilet facilities there shall be an equal
             666      number of diaper changing facilities in male toilet rooms and female toilet rooms."
             667          (64) In IBC, Section 3006.5, a new exception is added as follows: "Exception:
             668      Hydraulic elevators and roped hydraulic elevators with a rise of 50 feet or less."
             669          (65) A new section IBC, Section 3401.6, is added as follows: "3401.6 Parapet bracing,
             670      wall anchors, and other appendages. Buildings constructed prior to 1975 shall have parapet
             671      bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary,
             672      etc. evaluated by a licensed engineer when said building is undergoing reroofing, or alteration
             673      of or repair to said feature. Such parapet bracing, wall anchors, and appendages shall be
             674      evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When
             675      allowed by the local building official, alternate methods of equivalent strength as referenced in
             676      an approved code under Utah Code, Subsection 58-56-4(6)(a), will be considered when
             677      accompanied by engineer-sealed drawings, details, and calculations. When found to be
             678      deficient because of design or deteriorated condition, the engineer's recommendations to
             679      anchor, brace, reinforce, or remove the deficient feature shall be implemented.
             680      EXCEPTIONS:
             681      1. Group R-3 and U occupancies.
             682      2. Unreinforced masonry parapets need not be braced according to the above stated provisions
             683      provided that the maximum height of an unreinforced masonry parapet above the level of the
             684      diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times
             685      the thickness of the parapet wall. The parapet height may be a maximum of two and one-half
             686      times its thickness in other than Seismic Design Categories D, E, or F."
             687          (66) IBC, Section 3408.4, is deleted and replaced with the following: "3408.4 Change


             688      in Occupancy. When a change in occupancy results in a structure being reclassified to a higher
             689      Occupancy Category (as defined in Table 1604.5), or when such change of occupancy results in
             690      a design occupant load increase of 100% or more, the structure shall conform to the seismic
             691      requirements for a new structure.
             692      Exceptions:
             693      1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not
             694      be required to be met where it can be shown that the level of performance and seismic safety is
             695      equivalent to that of a new structure. Such analysis shall consider the regularity, overstrength,
             696      redundancy, and ductility of the structure within the context of the existing and retrofit (if any)
             697      detailing providing. Alternatively, the building official may allow the structure to be upgraded
             698      in accordance with referenced sections as found in an approved code under Utah Code,
             699      Subsection 58-56-4(6)(a).
             700      2. When a change of use results in a structure being reclassified from Occupancy Category I or
             701      II to Occupancy Category III and the structure is located in a seismic map area where SDS is less
             702      than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not required.
             703      3. Where design occupant load increase is less than 25 occupants and the Occupancy Category
             704      does not change."
             705          (67) In IBC, Section 3411.1, the exception is deleted and replaced with the following:
             706      "Exception: Type B dwelling or sleeping units required by section 1107 of this code are not
             707      required to be provided in existing buildings and facilities unless being altered or undergoing a
             708      change of occupancy classification."
             709          (68) The following referenced standard is added under NFPA in IBC, Chapter 35:
             710                              "Referenced in code
             711      Number    Title                Section number
             712      720-09    Standard for the Installation of     907.9
             713              Carbon Monoxide (CO) Detection and
             714              Warning Equipment"
             715          (69) The following referenced standard is added under UL in IBC, Chapter 35:
             716                              "Referenced in code
             717      Number     Title                Section number
             718      2034-2008    Standard of Single- and        907.9


             719              Multiple-station Carbon Monoxide Alarms"
             720      Section 202. Statewide Amendments to the IRC.
             721          The following are adopted as amendments to the IRC to be applicable statewide:
             722          (1) The statewide amendments to the following which may be applied to detached one
             723      and two family dwellings and multiple single family dwellings shall be applicable to the
             724      corresponding provisions of the IRC:
             725          (a) IBC under State Construction Code, Section 201;
             726          (b) IPC under State Construction Code, Section 203;
             727          (c) IMC under State Construction Code, Section 204;
             728          (d) IFGC under State Construction Code, Section 205;
             729          (e) NEC under State Construction Code, Section 206; and
             730          (f) IECC under State Construction Code, Section 207.
             731          (2) In IRC, Section 109:
             732          (a) A new IRC, Section 109.1.5, is added as follows: "R109.1.5 Weather-resistant
             733      exterior wall envelope inspections. An inspection shall be made of the weather-resistant
             734      exterior wall envelope as required by Section R703.1 and flashings as required by Section
             735      R703.8 to prevent water from entering the weather-resistive barrier."
             736          (b) The remaining sections are renumbered as follows: R109.1.6 Other inspections;
             737      R109.1.6.1 Fire-and smoke-resistance-rated construction inspection; R109.1.6.2 Reinforced
             738      masonry, insulating concrete form (ICF) and conventionally formed concrete wall inspection;
             739      and R109.1.7 Final inspection.
             740          (3) IRC, Section R114.1, is deleted and replaced with the following: "R114.1 Notice to
             741      owner. Upon notice from the building official that work on any building or structured is being
             742      prosecuted contrary to the provisions of this code or other pertinent laws or ordinances or in an
             743      unsafe and dangerous manner, such work shall be immediately stopped. The stop work order
             744      shall be in writing and shall be given to the owner of the property involved, or to the owner's
             745      agent or to the person doing the work; and shall state the conditions under which work will be
             746      permitted to resume."
             747          (4) In IRC, Section R202, the following definition is added: "CERTIFIED
             748      BACKFLOW PREVENTER ASSEMBLY TESTER: A person who has shown competence to
             749      test Backflow prevention assemblies to the satisfaction of the authority having jurisdiction


             750      under Utah Code, Subsection 19-4-104(4)."
             751          (5) In IRC, Section R202, the definition of "Cross Connection" is deleted and replaced
             752      with the following: "CROSS CONNECTION. Any physical connection or potential connection
             753      or arrangement between two otherwise separate piping systems, one of which contains potable
             754      water and the other either water of unknown or questionable safety or steam, gas, or chemical,
             755      whereby there exists the possibility for flow from one system to the other, with the direction of
             756      flow depending on the pressure differential between the two systems (see "Backflow, Water
             757      Distribution")."
             758          (6) In IRC, Section R202, the definition of "Potable Water" is deleted and replaced
             759      with the following: "POTABLE WATER. Water free from impurities present in amounts
             760      sufficient to cause disease or harmful physiological effects and conforming to the Utah Code,
             761      Title 19, Chapters 4 and 5, and the regulations of the public health authority having
             762      jurisdiction."
             763          (7) IRC, Figure R301.2(5), is deleted and replaced with Table R301.2(5a) and Table
             764      R301.2(5b) as follows:
             765     
"TABLE NO. R301.2(5a)

             766     
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS

             767              COUNTY    Po        S    Ao
             768              Beaver        43        63    6.2
             769              Box Elder    43        63    5.2
             770              Cache        50        63    4.5
             771              Carbon        43        63    5.2
             772              Daggett        43        63    6.5
             773              Davis        43        63    4.5
             774              Duchesne    43        63    6.5
             775              Emery        43        63    6.0
             776              Garfield        43        63    6.0
             777              Grand        36        63    6.5
             778              Iron        43        63    5.8    
             779              Juab        43        63    5.2
             780              Kane        36        63    5.7


             781              Millard        43        63    5.3
             782              Morgan        57        63    4.5
             783              Piute        43        63    6.2
             784              Rich        57        63    4.1
             785              Salt Lake        43        63    4.5
             786              San Juan        43        63    6.5
             787              Sanpete        43        63    5.2
             788              Sevier        43        63    6.0
             789              Summit        86        63    5.0
             790              Tooele        43        63    4.5
             791              Uintah        43        63    7.0
             792              Utah        43        63    4.5
             793              Wasatch        86        63    5.0
             794              Washington    29        63    6.0
             795              Wayne        36        63    6.5
             796              Weber        43        63    4.5
             797     
TABLE NO. R301.2(5b)

             798     
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)

             799                                  Roof Snow        Ground Snow
             800                                  Load (PSF)        Load (PSF)
             801          Beaver County
             802              Beaver        5920 ft    43            62
             803          Box Elder County
             804              Brigham City        4300 ft.    30             43
             805              Tremonton        4290 ft.    30            43
             806          Cache County
             807              Logan            4530 ft.    35            50
             808              Smithfield        4595 ft.    35            50
             809          Carbon County
             810              Price            5550 ft.    30            43
             811          Daggett County


             812              Manila        5377 ft.    30            43
             813          Davis County
             814              Bountiful        4300 ft.    30            43
             815              Farmington        4270 ft.    30            43
             816              Layton        4400 ft.    30            43
             817              Fruit Heights        4500 ft.    40            57
             818          Duchesne County
             819              Duchesne        5510 ft.    30            43
             820              Roosevelt        5104 ft.    30            43
             821          Emery County
             822              Castledale        5660 ft.    30            43
             823              Green River        4070 ft.    25            36
             824          Garfield County
             825              Panguitch        6600 ft.    30            43
             826          Grand County
             827              Moab            3965 ft.    25            36
             828          Iron County
             829              Cedar City        5831 ft.    30            43
             830          Juab County
             831              Nephi            5130 ft.    30            43
             832          Kane County
             833              Kanab            5000 ft.    25            36
             834          Millard County
             835      H. [ Millard ] Fillmore .H     5000 ft.    30            43
             836              Delta            4623 ft.    30            43
             837          Morgan County
             838              Morgan        5064 ft.    40            57
             839          Piute County
             840              Piute            5996 ft.    30            43
             841          Rich County
             842              Woodruff        6315 ft.    40            57


             843          Salt Lake County
             844              Murray        4325 ft.    30            43
             845              Salt Lake City     4300 ft.    30            43
             846              Sandy            4500 ft.    30            43
             847              West Jordan        4375 ft.    30            43
             848              West Valley        4250 ft.    30            43
             849          San Juan County
             850              Blanding        6200 ft.    30            43
             851              Monticello        6820 ft.    35            50
             852          Sanpete County
             853              Fairview        6750 ft.    35            50
             854              Mt. Pleasant        5900 ft.    30            43
             855              Manti            5740 ft.    30            43
             856              Ephraim        5540 ft.    30            43
             857              Gunnison        5145 ft.    30            43
             858          Sevier County
             859              Salina            5130 ft.    30            43
             860              Richfield        5270 ft.    30            43
             861          Summit County
             862              Coalville        5600 ft.    60            86
             863              Kamas        6500 ft.    70            100
             864              Park City        6800 ft.    100            142
             865              Park City        8400 ft.    162            231
             866              Summit Park        7200 ft.    90            128
             867          Tooele County
             868              Tooele        5100 ft.    30            43
             869          Uintah County
             870              Vernal            5280 ft.    30            43
             871          Utah County
             872              American Fork    4500 ft.    30            43
             873              Orem            4650 ft.    30            43


             874              Pleasant Grove    5000 ft.    30            43
             875              Provo            5000 ft.    30            43
             876              Spanish Fork        4720 ft.    30            43
             877          Wasatch County
             878              Heber            5630 ft.    60            86
             879          Washington County
             880              Central        5209 ft.    25            36
             881              Dameron        4550 ft.    25            36
             882              Leeds            3460 ft.    20            29
             883              Rockville        3700 ft.    25            36
             884              Santa Clara        2850 ft.    15 (1)            21
             885              St. George        2750 ft.    15 (1)            21
             886          Wayne County
             887              Loa            7080 ft.    30            43
             888              Hanksville        4308 ft.    25            36
             889          Weber County
             890              North Ogden        4500 ft.    40            57
             891              Ogden            4350 ft.    30            43
             892      NOTES
             893      (1) The IRC requires a minimum live load - See R301.6.
             894      (2) This table is informational only in that actual site elevations may vary. Table is only valid
             895      if site elevation is within 100 feet of the listed elevation."
             896          (8) IRC, Section R301.6, is deleted and replaced with the following: "R301.6 Utah
             897      Snow Loads. The ground snow load, Pg, to be used in the determination of design snow loads
             898      for buildings and other structures shall be determined by using the following formula: Pg = (Po2
             899      + S2(A-Ao)2)0.5 for A greater than Ao, and Pg = Po for A less than or equal to Ao.
             900      WHERE:
             901      Pg = Ground snow load at a given elevation (psf);
             902      Po = Base ground snow load (psf) from Table No. R301.2(5a);
             903      S = Change in ground snow load with elevation (psf/100 ft.) From Table No. R301.2(5a);
             904      A = Elevation above sea level at the site (ft./1000);


             905      Ao = Base ground snow elevation from Table R301.2(5a) (ft./1000).
             906      The building official may round the roof snow load to the nearest 5 psf. The ground snow load,
             907      Pg, may be adjusted by the building official when a licensed engineer or architect submits data
             908      substantiating the adjustments. A record of such action together with the substantiating data
             909      shall be provided to the division for a permanent record.
             910      The building official may also directly adopt roof snow loads in accordance with Table
             911      R301.2(5b), provided the site is no more than 100 ft. higher than the listed elevation.
             912      Where the minimum roof live load in accordance with Table R301.6 is greater than the design
             913      roof snow load, such roof live load shall be used for design, however, it shall not be reduced to
             914      a load lower than the design roof snow load. Drifting need not be considered for roof snow
             915      loads less than 20 psf."
             916          (9) In IRC, Section R302.2, the words "Exception: A" are deleted and replaced with the
             917      following: "Exceptions: 1. A common 2-hour fire-resistance-rated wall is permitted for
             918      townhouses if such walls do not contain plumbing or mechanical equipment, ducts or vents in
             919      the cavity of the common wall. Electrical installation shall be installed in accordance with
             920      Chapters 34 through 43. Penetrations of electrical outlet boxes shall be in accordance with
             921      Section R302.4.
             922      2. In buildings equipped with an automatic residential fire sprinkler system, a".
             923          (10) In IRC, Section R302.2.4, a new exception 6 is added as follows: "6. Townhouses
             924      separated by a common 2-hour fire-resistance-rated wall as provided in Section R302.2."
             925          (11) IRC, Sections R311.7.4 through R311.7.4.3, are deleted and replaced with the
             926      following: "R311.7.4 Stair treads and risers. R311.7.4.1 Riser height. The maximum riser
             927      height shall be 8 inches (203 mm). The riser shall be measured vertically between leading
             928      edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed
             929      the smallest by more than 3/8 inch (9.5 mm).
             930      R311.7.4.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The tread
             931      depth shall be measured horizontally between the vertical planes of the foremost projection of
             932      adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within
             933      any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads
             934      shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12
             935      inches (305 mm) from the side where the treads are narrower. Winder treads shall have a


             936      minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the
             937      greatest winder tread depth at the 12 inch (305 mm) walk line shall not exceed the smallest by
             938      more than 3/8 inch (9.5 mm).
             939      R311.7.4.3 Profile. The radius of curvature at the leading edge of the tread shall be no greater
             940      than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 1 1/4
             941      inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing projection
             942      shall not exceed the smallest nosing projection by more than 3/8 inches (9.5 mm) between two
             943      stories, including the nosing at the level of floors and landings. Beveling of nosing shall not
             944      exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading
             945      edge of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open
             946      risers are permitted, provided that the opening between treads does not permit the passage of a
             947      4-inch diameter (102 mm) sphere.
             948      Exceptions.
             949      1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).
             950      2. The opening between adjacent treads is not limited on stairs with a total rise of 30 inches
             951      (762 mm) or less."
             952          (12) In Section R312.2, the words "adjacent fixed seating" are deleted.
             953          (13) IRC, Section R313, is deleted.
             954          (14) IRC, Section R315.1, is deleted and replaced with the following: "R315.1 Carbon
             955      monoxide alarms. For new construction, a listed carbon monoxide alarm shall be installed on
             956      each habitable level of dwelling units within which fuel-fired appliances are installed and in
             957      dwelling units that have attached garages."
             958          (15) IRC, Section R315.3, is deleted and replaced with the following: "R315.3 Alarm
             959      requirements. Listed single- and multiple-station carbon monoxide alarms shall comply with
             960      U.L. 2034 and shall be installed in accordance with the provision of this code and NFPA 720."
             961          (16) In IRC, Section R403.1.6, a new Exception 4 is added as follows: "4. When
             962      anchor bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be placed
             963      with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from
             964      each end of each plate section at interior bearing walls, interior braced wall lines and at all
             965      exterior walls."
             966          (17) In IRC, Section R403.1.6.1, a new exception is added at the end of Item 2 and


             967      Item 3 as follows: "Exception: When anchor bolt spacing does not exceed 32 inches (816 mm)
             968      apart, anchor bolts may be placed with a minimum of two bolts per plate section located not
             969      less than 4 inches (102 mm) from each end of each plate section at interior bearing walls,
             970      interior braced wall lines and at all exterior walls."
             971          (18) In IRC, Section R404.1, a new exception is added as follows: "Exception: As an
             972      alternative to complying with Sections R404.1 through R404.1.5.3, concrete and masonry
             973      foundation walls may be designed in accordance with IBC Sections 1807.1.5 and 1807.1.6 as
             974      amended in Section 1807.1.6.4 and Table 1807.1.6.4 under these rules."
             975          (19) IRC, Sections R612.2 through R612.4.2, are deleted.
             976          (20) IRC, Chapter 11, is deleted and replaced with Chapter 11 of the 2006 International
             977      Residential Code and Chapter 4 of the 2006 International Energy Conservation Code.
             978          (21) IRC, Section M1411.6, is deleted.
             979          (22) In IRC, Section M1502.4.4.1, the words "25 feet (7620 mm)" are deleted and
             980      replaced with "35 feet (10668 mm)".
             981          (23) A new IRC, Section G2401.2, is added as follows: "G2401.2 Meter Protection.
             982      Fuel gas services shall be in an approved location and/or provided with structures designed to
             983      protect the fuel gas meter and surrounding piping from physical damage, including falling,
             984      moving, or migrating ice and snow. If an added structure is used, it must provide access for
             985      service and comply with the IBC or the IRC."
             986          (24) A new IRC, Section P2602.3, is added as follows: "P2602.3 Individual water
             987      supply. Where a potable public water supply is not available, individual sources of potable
             988      water supply shall be utilized provided that the source has been developed in accordance with
             989      Utah Code, Sections 73-3-1 and 73-3-25, as administered by the Department of Natural
             990      Resources, Division of Water Rights. In addition, the quality of the water shall be approved by
             991      the local health department having jurisdiction."
             992          (25) A new IRC, Section P2602.4, is added as follows: "P2602.4 Sewer required.
             993      Every building in which plumbing fixtures are installed and all premises having drainage
             994      piping shall be connected to a public sewer where the sewer is within 300 feet of the property
             995      line in accordance with Utah Code, Section 10-8-38; or an approved private sewage disposal
             996      system in accordance with Utah Administrative Code, Chapter 4, Rule R317, as administered
             997      by the Department of Environmental Quality, Division of Water Quality."


             998          (26) In IRC, Section P2801.7, the word "townhouses" is deleted.
             999          (27) A new IRC, Section P2902.1.1, is added as follows: "P2902.1.1 Backflow
             1000      assembly testing. The premise owner or his designee shall have backflow prevention
             1001      assemblies operation tested at the time of installation, repair, and relocation and at least on an
             1002      annual basis thereafter, or more frequently as required by the authority having jurisdiction.
             1003      Testing shall be performed by a Certified Backflow Preventer Assembly Tester. The assemblies
             1004      that are subject to this paragraph are the Spill Resistant Vacuum Breaker, the Pressure Vacuum
             1005      Breaker Assembly, the Double Check Backflow Prevention Assembly, the Double Check
             1006      Detector Assembly Backflow Preventer, the Reduced Pressure Principle Backflow Preventer,
             1007      and Reduced Pressure Detector Assembly."
             1008          (28) IRC, Table P2902.3 is deleted and replaced with the following:
             1009     
"TABLE P2902.3

             1010     
General Methods of Protection

             1011      Assembly            Degree        Application        Installation Criteria
             1012      (applicable            of
             1013      standard)            Hazard
             1014      Reduced            High or        Backpressure or    a. The bottom of each
             1015      Pressure            Low            Backsiphonage     RP assembly shall
             1016      Principle Backflow                     1/2" - 16"        be a minimum of 12
             1017      Preventer (AWWA                                inches above the
             1018      C511, USC-FCCCHR,                            ground or floor.
             1019      ASSE 1013                                    b. RP assemblies shall
             1020      CSA CNA/CSA-B64.4)                            NOT be installed in
             1021      and Reduced Pressure                            a pit.
             1022      Detector Assembly                                c. The relief valve on
             1023      (ASSE 1047, USC-                                each RP assembly
             1024      FCCCHR)                                    shall not be
             1025                                              directly connected
             1026                                              to any waste
             1027                                              disposal line,
             1028                                              including sanitary


             1029                                              sewer, storm drains,
             1030                                              or vents.
             1031                                              d. The assembly shall
             1032                                              be installed in a
             1033                                              horizontal position
             1034                                              only unless listed
             1035                                              or approved for
             1036                                              vertical installation.
             1037      Double Check            Low        Backpressure or        a. If installed in a
             1038      Backflow                    Backsiphonage        pit, the DC assembly
             1039      Prevention                    1/2" - 16"            shall be installed
             1040      Assembly                                    with a minimum of
             1041      (AWWA C510,                                12 inches of
             1042      USC-FCCCHR,                                clearance between
             1043      ASSE 1015)                                    all sides of the
             1044      Double Check                                    vault including
             1045      Detector Assembly                                the floor and roof
             1046      Backflow Preventer                                or ceiling with
             1047      (ASSE 1048,                                    adequate room for
             1048      USC-FCCCHR)                                testing and
             1049                                              maintenance.
             1050                                              b. Shall be installed
             1051                                              in a horizontal
             1052                                              position unless
             1053                                              listed or approved
             1054                                              for vertical
             1055                                              installation.
             1056      Pressure            High or    Backsiphonage        a. Shall not be
             1057      Vacuum            Low        1/2" - 2"            installed in an
             1058      Breaker                                    area that could be
             1059      Assembly                                    subjected to


             1060      (ASSE 1020,                                    backpressure or
             1061      USC-FCCCHR)                                back drainage
             1062                                              conditions.
             1063                                              b. Shall be installed
             1064                                              a minimum of 12
             1065                                              inches above all
             1066                                              downstream piping
             1067                                              and the highest
             1068                                              point of use.
             1069                                              c. Shall not be
             1070                                              installed below
             1071                                              ground or in a
             1072                                              vault or pit.
             1073                                              d. Shall be installed
             1074                                              in a vertical position
             1075                                              only.
             1076      Spill                High or    Backsiphonage        a. Shall not be
             1077      Resistant            Low        1/4" - 2"            installed in an
             1078      Vacuum                                    area that could
             1079      Breaker                                    be subjected to
             1080      (ASSE 1056,                                    backpressure or
             1081      USC-FCCCHR)                                back drainage
             1082                                              conditions.
             1083                                              b. Shall be installed
             1084                                              a minimum of 12
             1085                                              inches above all
             1086                                              downstream piping
             1087                                              and the highest
             1088                                              point of use.
             1089                                              c. Shall not be
             1090                                              installed below


             1091                                              ground or in a
             1092                                              vault or pit.
             1093                                              d. Shall be installed
             1094                                              in a vertical position
             1095                                              only.
             1096      General                                    The assembly owner,
             1097      Installation                                    when necessary,
             1098      Criteria                                    shall provide devices
             1099                                              or structures to
             1100                                              facilitate testing,     
             1101                                              repair, and/or    
             1102                                              maintenance and
             1103                                              to ensure the safety of
             1104                                              the backflow     
             1105                                              technician.
             1106                                              Assemblies shall not
             1107                                              be installed more than
             1108                                              five feet off the floor
             1109                                              unless a permanent
             1110                                              platform is installed.
             1111                                              The body of the
             1112                                              assembly shall not be
             1113                                              closer than 12 inches
             1114                                              to any wall, ceiling or
             1115                                              encumbrance, and
             1116                                              shall be accessible for
             1117                                              testing, repair and/or
             1118                                              maintenance.
             1119                                              In cold climates,
             1120                                              assemblies shall be
             1121                                              protected from    


             1122                                              freezing by a means
             1123                                              acceptable to the code
             1124                                              official.
             1125                                              Assemblies shall be
             1126                                              maintained as an intact
             1127                                              assembly."
             1128          (29) IRC, Table 2902.3a, is added as follows:
             1129     
"TABLE 2902.3a

             1130     
Specialty Backflow Devices for low hazard use only

             1131      Device            Degree of    Application            Applicable
             1132                      Hazard                    Standard
             1133      Air Gap            High or    Backsiphonage        See Table P2902.3.1
             1134                      Low                        ASME A112.1.2
             1135      Antisiphon-type        Low        Backsiphonage        ASSE 1002
             1136      Water Closet Flush                                CSA CAN/
             1137      Tank Ball Cock                                CSA-B125
             1138      Atmospheric            High or    Backsiphonage        ASSE 1001
             1139      Vacuum            Low        a. Shall not be            USC-FCCCHR,
             1140      Breaker                    installed in an            CSA         
             1141                              area that could be        CAN/CSA-B64.1.1
             1142                              subjected to
             1143                              backpressure or back
             1144                              drainage conditions.
             1145                              b. Shall not be installed
             1146                              where it may be subjected
             1147                              to continuous pressure
             1148                              for more than 12 consecutive
             1149                              hours at any time.
             1150                              c. Shall be installed a
             1151                              minimum of six inches above
             1152                              all downstream piping and


             1153                              the highest point of use.
             1154                              d. Shall be installed on the
             1155                              discharge (downstream) side
             1156                              of any valves.
             1157                              e. The AVB shall be installed
             1158                              in a vertical position only.
             1159      Dual check valve        Low        Backsiphonage        ASSE 1024
             1160      Backflow Preventer                or Backpressure
             1161                              1/4" - 1"
             1162      Backflow Preventer        Low        Backsiphonage        ASSE 1012
             1163      with Intermediate        Residential    or Backpressure         CSA CAN/
             1164      Atmospheric Vent        Boiler        1/4" - 3/4"            CSA-B64.3
             1165      Dual check valve        Low        Backsiphonage        ASSE 1022
             1166      type Backflow                or Backpressure
             1167      Preventer for                    1/4" - 3/8"
             1168      Carbonated Beverage
             1169      Dispensers/Post
             1170      Mix Type
             1171      Hose-connection        Low        Backsiphonage        ASSE 1011
             1172      Vacuum Breaker                1/2", 3/4", 1"            CSA CAN/
             1173                                              CSA-B64.2
             1174      Vacuum Breaker        Low        Backsiphonage        ASSE 1019
             1175      Wall Hydrants,                3/4", 1"            CSA CAN/
             1176      Frost-resistant,                                CSA-B64.2.2
             1177      Automatic Draining
             1178      Type
             1179      Laboratory Faucet        Low        Backsiphonage        ASSE 1035
             1180      Backflow Preventer                                CSA CAN/
             1181                                              CSA-B64.7
             1182      Hose Connection        Low        Backsiphonage        ASSE 1052
             1183      Backflow Preventer                1/2" - 1"


             1184      Installation Guidelines: The above specialty devices shall be installed in accordance with their
             1185      listing and the manufacturer's instructions and the specific provisions of this chapter."
             1186          (30) In IRC, Section P3103.6, the following sentence is added at the end of the
             1187      paragraph: "Vents extending through the wall shall terminate not less than 12 inches from the
             1188      wall with an elbow pointing downward."
             1189          (31) In IRC, Section P3104.4, the following sentence is added at the end of the
             1190      paragraph: "Horizontal dry vents below the flood level rim shall be permitted for floor drain
             1191      and floor sink installations when installed below grade in accordance with Chapter 30, and
             1192      Sections P3104.2 and P3104.3. A wall cleanout shall be provided in the vertical vent."
             1193          (32) In IRC, Section E3902.11, the following words are deleted: "family rooms, dining
             1194      rooms, living rooms, parlors, libraries, dens, sunrooms, recreations rooms, closets, hallways,
             1195      and similar rooms or areas".
             1196          (33) IRC, Chapter 44, is amended by adding the following reference standard:
             1197              "Standard
             1198              reference                            Referenced in code
             1199              number    Title                        Section number
             1200              USC-        Foundation for Cross-Connection        Table P2902.3
             1201              FCCCHR    Control and Hydraulic Research
             1202              9th        University of Southern California
             1203              Edition    Kaprielian Hall 300
             1204              Manual    Los Angeles CA 90089-2531
             1205              of Cross
             1206              Connection
             1207              Control"    
             1208          (34) In IRC, Chapter 44, the following standard is added under NFPA as follows:
             1209              Standard
             1210              reference                            Referenced in code
             1211              number    Title                        section number
             1212              720-09    Standard for the Installation            R315.3
             1213                      of Carbon Monoxide (CO) Detection
             1214                      and Warning Equipment"    


             1215          (35) IRC, Appendix O, Gray Water Recycling Systems, is deleted and replaced with
             1216      Appendix C of the International Plumbing Code as amended by the state construction code.
             1217      Section 203. Statewide Amendments to the IPC.
             1218          The following are adopted as amendments to the IPC to be applicable statewide:
             1219          (1) A new IPC, Section 101.2, is added as follows: "For clarification, the International
             1220      Private Sewage Disposal Code is not part of the plumbing code even though it is in the same
             1221      printed volume."
             1222          (2) In IPC, Section 202, the definition for "Backflow Backpressure, Low Head" is
             1223      deleted.
             1224          (3) In IPC, Section 202, the following definition is added: "Certified Backflow
             1225      Preventer Assembly Tester. A person who has shown competence to test Backflow prevention
             1226      assemblies to the satisfaction of the authority having jurisdiction under Utah Code, Subsection
             1227      19-4-104(4)."
             1228          (4) In IPC, Section 202, the definition for "Cross Connection" is deleted and replaced
             1229      with the following: "Cross Connection. Any physical connection or potential connection or
             1230      arrangement between two otherwise separate piping systems, one of which contains potable
             1231      water and the other either water of unknown or questionable safety or steam, gas, or chemical,
             1232      whereby there exists the possibility for flow from one system to the other, with the direction of
             1233      flow depending on the pressure differential between the two systems (see "Backflow")."
             1234          (5) In IPC, Section 202, the definition for "Potable Water" is deleted and replaced with
             1235      the following: "Potable Water. Water free from impurities present in amounts sufficient to
             1236      cause disease or harmful physiological effects and conforming to the Utah Code, Title 19,
             1237      Chapters 4 and 5, and the regulations of the public health authority having jurisdiction."
             1238          (6) In IPC, Table 303.4, the item listed as "Backflow prevention devises" is modified
             1239      as follows:
             1240          (a) in the Third-Party Certified field, after the word "Required" add "See footnote 1";
             1241          (b) in the Third-Party Tested field the following is added: "Required see footnote 1";
             1242      and
             1243          (c) a new footnote 1 is added as follows: "1. Third party certification will consist of
             1244      any combination of two certifications, laboratory or field. Acceptable third party laboratory
             1245      certifying agencies are ASSE, IAPMO, and USC-FCCCHR. USC-FCCCHR currently provides


             1246      the only field testing of backflow protection assemblies. Also see www.drinkingwater.utah.gov
             1247      and Division of Drinking Water Rule R309-305-6."
             1248          (7) IPC, Section 304.3, Meter Boxes, is deleted.
             1249          (8) IPC, Section 311.1, is deleted.
             1250          (9) IPC, Sections 312.10 through 312.10.2, are deleted and replaced with the
             1251      following: "312.10 Backflow assembly testing. The premise owner or his designee shall have
             1252      backflow prevention assemblies operation tested at the time of installation, repair, and
             1253      relocation and at least on an annual basis thereafter, or more frequently as required by the
             1254      authority having jurisdiction. Testing shall be performed by a Certified Backflow Preventer
             1255      Assembly Tester. The assemblies that are subject to this paragraph are the Spill Resistant
             1256      Vacuum Breaker, the Pressure Vacuum Breaker Assembly, the Double Check Backflow
             1257      Prevention Assembly, the Double Check Detector Assembly Backflow Preventer, the Reduced
             1258      Pressure Principle Backflow Preventer, and Reduced Pressure Detector Assembly."
             1259          (10) In IPC, Section 403.1, a new footnote g is added as follows: "FOOTNOTE: g.
             1260      When provided, in public toilet facilities there shall be an equal number of diaper changing
             1261      facilities in male toilet rooms and female toilet rooms."
             1262          (11) A new IPC, Section 406.4, is added as follows: "406.4 Automatic clothes washer
             1263      safe pans. Safe pans, when installed under automatic clothes washers, shall be installed in
             1264      accordance with Section 504.7."
             1265          (12) A new IPC, Section 412.5, is added as follows: "412.5 Public toilet rooms. All
             1266      public toilet rooms shall be equipped with at least one floor drain."
             1267          (13) In IPC, Section 504.7.2, the following is added at the end of the section: "When
             1268      permitted by the code official, the pan drain may be directly connected to a soil stack, waste
             1269      stack, or branch drain. The pan drain shall be individually trapped and vented as required in
             1270      Section 907.1. The pan drain shall not be directly or indirectly connected to any vent. The trap
             1271      shall be provided with a trap primer conforming to ASSE 1018 or ASSE 1044."
             1272          (14) A new IPC, Section 504.7.3, is added as follows: "504.7.3 Pan Designation. A
             1273      water heater pan shall be considered an emergency receptor designated to receive the discharge
             1274      of water from the water heater only and shall not receive the discharge from any other fixtures,
             1275      devises or equipment."
             1276          (15) IPC, Section 602.3, is deleted and replaced with the following: "602.3 Individual


             1277      water supply. Where a potable public water supply is not available, individual sources of
             1278      potable water supply shall be utilized provided that the source has been developed in
             1279      accordance with Utah Code, Sections 73-3-1, 73-3-3, and 73-3-25, as administered by the
             1280      Department of Natural Resources, Division of Water Rights. In addition, the quality of the
             1281      water shall be approved by the local health department having jurisdiction. The source shall
             1282      supply sufficient quantity of water to comply with the requirements of this chapter."
             1283          (16) IPC, Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4, 602.3.5, and 602.3.5.1, are
             1284      deleted.
             1285          (17) A new IPC, Section 604.4.1, is added as follows: "604.4.1 Manually operated
             1286      metering faucets. Self closing or manually operated metering faucets shall provide a flow of
             1287      water for at least 15 seconds without the need to reactivate the faucet."
             1288          (18) IPC, Section 606.5, is deleted and replaced with the following: "606.5 Water
             1289      pressure booster systems. Water pressure booster systems shall be provided as required by
             1290      Section 606.5.1 through 606.5.11."
             1291          (19) A new IPC, Section 606.5.11, is added as follows: "606.5.11 Prohibited
             1292      installation. In no case shall a booster pump be allowed that will lower the pressure in the
             1293      public main to less than 20 psi."
             1294          (20) IPC, Table 608.1, is deleted and replaced with the following:
             1295     
"TABLE 608.1

             1296     
General Methods of Protection

             1297      Assembly        Degree        Application        Installation Criteria
             1298      (applicable        of
             1299      standard)        Hazard
             1300      Reduced        High or        Backpressure or    a. The bottom of each
             1301      Pressure        Low            Backsiphonage    RP assembly shall
             1302      Principle Backflow                1/2" - 16"        be a minimum of 12
             1303      Preventer (AWWA                            inches above the
             1304      C511, USC-FCCCHR,                        ground or floor.
             1305      ASSE 1013                                b. RP assemblies shall
             1306      CSA CNA/CSA-B64.4)                        NOT be installed in
             1307      and Reduced Pressure                        a pit.


             1308      Detector Assembly                            c. The relief valve on
             1309      (ASSE 1047, USC-                            each RP assembly
             1310      FCCCHR)                                shall not be directly    
             1311                                          connected to any waste
             1312                                          disposal line, including
             1313                                          sanitary sewer, storm rains,
             1314                                          or vents.
             1315                                          d. The assembly shall be
             1316                                          installed in a horizontal
             1317                                          position only unless listed
             1318                                          or approved for vertical
             1319                                          installation.
             1320      Double Check    Low            Backpressure or        a. If installed in a pit,
             1321      Backflow                Backsiphonage        the DC assembly
             1322      Prevention                1/2" - 16"            shall be installed
             1323      Assembly                                 with a minimum of
             1324      (AWWA C510,                            12 inches of
             1325      USC-FCCCHR,                            clearance between
             1326      ASSE 1015)                                all sides of the
             1327      Double Check                                vault including the
             1328      Detector Assembly                            floor and roof or
             1329      Backflow Preventer                            ceiling with adequate
             1330      (ASSE 1048,                                room for testing and
             1331      USC-FCCCHR)                            maintenance.
             1332                                          b. Shall be installed in a
             1333                                          horizontal position unless
             1334                                          listed or approved for
             1335                                          vertical installation.
             1336      Pressure        High or    Backsiphonage        a. Shall not be installed
             1337      Vacuum        Low        1/2" - 2"            in an area that could be
             1338      Breaker                                subjected to


             1339      Assembly                                backpressure or
             1340      (ASSE 1020,                                back drainage
             1341      USC-FCCCHR)                            conditions.
             1342                                          b. Shall be installed a
             1343                                          minimum of 12 inches
             1344                                          above all downstream
             1345                                          piping and the highest point
             1346                                          of use.
             1347                                          c. Shall not be installed
             1348                                          below ground or in a vault
             1349                                          or pit.
             1350                                          d. Shall be installed in a
             1351                                          vertical position only.
             1352      Spill            High or    Backsiphonage        a. Shall not be
             1353      Resistant        Low        1/4" - 2"            installed in an
             1354      Vacuum                                area that could
             1355      Breaker                                be subjected to
             1356      (ASSE 1056,                                backpressure or
             1357      USC-FCCCHR)                            back drainage
             1358                                          conditions.
             1359           &n