(22) In IFC, Chapter 9, Section 906.1, Where Required, the exception under paragraph 1 is
deleted and rewritten to read: "Exception: In new and existing Group A, B, and E occupancies equipped
with quick response sprinklers, portable fire extinguishers shall be required only in locations specified
in items 2 through 6."
{
(22)
}
(23)
IFC, Chapter 9, Section 907.2.3 Group E:
494
(a) The first sentence is deleted and rewritten as follows: "A manual fire alarm system
495
that initiates the occupant notification system in accordance with Section 907.5 and installed in
496
accordance with Section 907.6 shall be installed in Group E occupancies."
497
(b) Exception number 3, on line five, delete the words, "emergency voice/alarm
498
communication system" and replace with "occupant notification system."
5. Page
17, Lines 499 through 503
:
499
{
[
}
(24)
{
]
}
{
(23)
}
IFC, Chapter 9, [Section 907.9.5, Maintenance, inspection, and
testing]
500
907.8, Inspection, testing, and maintenance, is amended to add the following sentences at the
501
end of the section: "Increases in nuisance alarms shall require the fire alarm system to be tested
502
for sensitivity. Fire alarm systems that continue after sensitivity testing with unwarranted
503
nuisance alarms shall be replaced as directed by the AHJ."
6. Page
17, Lines 515 through 517
:
515
{
(24)
}
(25)
IFC, Chapter 9, Section 908.7, Carbon Monoxide Alarms, is
{
amended as
follows:
516
On line four after the word "alarms" insert the following sentence: "A minimum of one carbon
517
monoxide alarm shall be installed on each habitable level." The entire Exception is deleted
}
deleted
and rewritten as follows: "Carbon monoxide alarms shall be installed on each habitable level of a
dwelling unit or sleeping unit in Groups R-2, R-3, R-4, and I-1 equipped with fuel burning appliances.
908.7.1 If more than one carbon monoxide detector is required, they shall be interconnected as
required in IFC, Chapter 9, Section 907.2.11.3
908.7.2 In new construction, a carbon monoxide detectors shall recieve its primary power as
required under IFC, Chapter 9, Section, 907.2.11.4
908.7.3 Upon completion of the installation, the carbon monoxide detector system will meet the
requirements listed in NFPA 720, Installation of Carbon Monoxide Detection and Warning Equipment
and UL2034, Standard for Single and Multiple Carbon Monoxide Alarms
.
"
7. Page
20, Lines 596 through 604
:
596
(6) IFC, Chapter 11, Section 1103.9, Carbon Monoxide Alarms, is deleted and
597
rewritten as follows:
{
"Existing Group I or R occupancies located in a building containing a
598
fuel-burning appliance or a building which has an attached garage shall be equipped with
599
single-station carbon monoxide alarms. A minimum of one carbon monoxide alarm shall be
600
installed on each habitable level. The carbon monoxide alarms shall be listed as complying
601
with UL 2034, and be installed maintained in accordance with NFPA 720 and the
602
manufacturer's instructions. An open parking garage, as defined in the International Building
603
Code, or an enclosed parking garage ventilated in accordance with Section 404 of the
604
International Building Code shall not be deemed to be an attached garage
}
"Carbon monoxide
alarms shall be installed on each habitable level of a dwelling unit or sleeping unit in existing Groups
R-2, R-3, R-4, and I-1 equipped with fuel burning appliances.
908.7.1 If more than one carbon monoxide detector is required, they shall be interconnected as
required in IFC, Chapter 9, Section 907.2.11.3
908.7.2 In new construction, a carbon monoxide detectors shall recieve its primary power as
required under IFC, Chapter 9, Section, 907.2.11.4
908.7.3 Upon completion of the installation, the carbon monoxide detector system will meet the
requirements listed in NFPA 720, Installation of Carbon Monoxide Detection and Warning Equipment
and UL2034, Standard for Single and Multiple Carbon Monoxide Alarms
."