H.B.
310
CONSTRUCTION CODE AMENDMENTS
House Committee
Amendments
Amendment 3 February 20, 2013 6:25 PM
Representative Larry B. Wiley
proposes the following amendments:
1. Page
2, Lines 41 through 43
:
41
15A-3-307, as enacted by Laws of Utah 2011, Chapter 14
42
{
15A-3-308, as enacted by Laws of Utah 2011, Chapter 14
}
43
15A-3-309, as enacted by Laws of Utah 2011, Chapter 14
2. Page
77, Line 1835 through Page 78, Line 1857
:
1835
{
Section 22.
Section
15A-3-308
is amended to read:
1836
15A-3-308. Amendments to Chapter 8 of IPC.
1837
[IPC, Chapter 8, is not amended.]
1838
(1) In IPC, Section 802.1.8, the words "or directly connect" are added after the word
1839
"break".
1840
(2) In IPC, Section 802, a new Section 802.1.8.1 is added as follows: "802.1.8.1
1841
Gravity grease interceptor connection: Those sinks or appliances draining into a gravity grease
1842
interceptor shall discharge directly or indirectly through an air gap or air break into a floor
1843
sink."
1844
(3) In IPC, Section 802, a new Section 802.1.8.2 is added as follows: "802.1.8.2
1845
Hydromechanical grease interceptor connection. Those sinks used for washing and primary
1846
rinsing of utensils, dishes, pots, pans or service ware and draining through a hydromechanical
1847
interceptor shall be directly connected to the interceptor. The sinks shall be trapped and vented
1848
to prevent odors from the grease interceptor escaping through the sinks into the building. A
1849
flow control device furnished by the manufacturer shall be installed on the inlet side of the
1850
interceptor and in accordance with the manufacturers installation instructions. A floor sink
1851
shall be installed within five (5') feet downstream of the interceptor outlet. A dedicated branch
1852
drain shall be provided to serve the hydromechanical interceptor and the floor sink only. No
1853
connections of any kind shall be permitted between the outlet of the interceptor and the
1854
connection of the floor sink."
1855
(4) In IPC, Section 802, a new Section 802.1.9 is added as follows: "802.1.9 Sanitizing
1856
sinks. Sinks used for the sanitizing of utensils, dishes, pots, pans, or service ware shall
1857
discharge indirectly through an air gap or air break to the drainage system."
}
3. Page
79, Lines 1891 through 1901
:
1891
{
(2) In IPC, Section 1003.3.4, the following sentence is added before the last sentence:
1892
"Hydrochemical grease interceptors and automatic grease removal devices shall not indirectly
1893
discharge into a floor sink or any other indirect waste receptor, but shall directly connect to the
1894
drainage system."
1895
(3) IPC, Section 1003.3.4.2, is deleted and replaced with the following: "1003.3.4.2
1896
Rate of flow controls. Hydromechanical grease interceptors shall be equipped with devices to
1897
control the rate of water flow so that the water flow does not exceed the rated flow. The flow
1898
control device shall be vented. The vent from the flow control device shall connect to the
1899
plumbing vent system within the building or an approved and listed air admittance valve or
1900
terminate out the roof. The flow control device shall be installed in accordance with the
1901
manufacturers instructions."
}
Page 1 of 2
LRGC
bhowe
bhowe