Title 15A Chapter 3 Part 7 Section 701
| << Previous Section (15A-3-601) | Download Options PDF | RTF | XML | Next Section (15A-3-801) >> |
| Index | Utah Code |
| Title 15A | State Construction and Fire Codes Act |
| Chapter 3 | Statewide Amendments Incorporated as Part of State Construction Code |
| Part 7 | Statewide Amendments to International Energy Conservation Code |
| Section 701 | General provisions.
(Effective 7/1/2026)
|
Effective 7/1/2026
15A-3-701. General provisions.
The following is adopted as an amendment to the IECC to be applicable statewide:
Amended by Chapter 47, 2026 General Session
15A-3-701. General provisions.
The following is adopted as an amendment to the IECC to be applicable statewide:
| (1) | In IECC, Section R102.1.1, a new section R102.1.1 is added as follows: "R102.1.1 National Green Building Standard complying with ICC 700-2020 National Green Building Standard and achieving the Gold rating level for the energy efficiency category shall be deemed to exceed the energy efficiency required by this code. The building shall also meet the requirements identified in table N1105.2 and the building thermal envelope efficiency is greater than or equal to levels of efficiency and solar heat gain coefficients (SHGC) in Tables N1102.2.2 and N1102.1.3 of the 2009 IRC." |
| (2) | In IECC, Section R103.2, all words after the words "herein governed," are deleted and replaced with the following: "Construction documents include all documentation required for building permits shall include only those items specified in Section 10-5-132(8) of the Utah Municipal Code." |
| (4) | In IECC, Section R303.3, all wording after the first sentence is deleted. |
| (5) | In IECC, Section R401.2, in the first sentence, the words "Section R401.13.5 and" are deleted. |
| (6) | In IECC, Section R401.2.5 is deleted. |
| (7) | In IECC, Section R401.3 Number 7, the words "and the compliance path used" are deleted. |
| (8) | In IECC Table R402.1.2, the following changes are made:
|
| (9) | In IECC, Table R402.1.3, the following changes are made:
|
| (10) | In IECC, a new subsection R402.1.5.1 is added as follows: "R402.1.5.1 RESCheck 2012 Utah Energy Conservation Code. Compliance with section N1102.1.5 (R402.1.5) may be satisfied using the software RESCheck 2012 Utah Energy Conservation Code, which shall satisfy the R-value and U-factor requirements of N1102.1, N1102.2, and N1102.3, provided the following conditions are met:
|
| (11) | In IECC, Section R402.2.1, a new section is added as follows: "R402.2.1.1. Unvented attic and unvented enclosed rafter assemblies. Unvented attic and unvented enclosed rafter assemblies conforming to Section R806.5 shall be provided with an R-value of R-22 (maximum U-Factor of 0.045) in Climate Zone 3-B or an R-value of R-26 (maximum U-factor of 0.038) in Climate Zones 5-B and 6-B shall be permitted provided all the following conditions are met: 1. The unvented attic assembly complies with the requirements of the International Residential Code, Section R806.5. 2. The house shall attain a blower door test result 2.5ACH 50. 3. The house shall require a whole house mechanical ventilation system that does not rely solely on a negative pressure strategy (shall be positive, balanced or hybrid). 4. Where insulation is installed below the roof deck and the exposed portion of roof rafters are not already covered by the R-20 depth of the air-impermeable insulation, the exposed portion of the roof rafters shall be wrapped (covered) by minimum R-3 unless directly covered by drywall/finished ceiling. Roof rafters are not required to be covered by minimum R-3 if a continuous insulation is installed above the roof deck. 5. Indoor heating, cooling and ventilation equipment (including ductwork) shall be inside the building thermal envelope." |
| (12) | A new IECC, Section R402.2.1.3 is added as follows: "R402.2.1.3 Walls with Air-Impermeable Insulation. Where IECC Table R402.1.2 requires R-20 for wood framed walls in climate zones 3-B and 5-B or R-20+5CI for climate zone 6-B, an air-impermeable insulation installed in the wall cavity with R-value of R-15 for climate zones 3-B and 5-B or R-20 for climate zone 6-B shall be deemed equivalent to the provisions in IECC Table R402.1.2, provided the home attains a blower door test 2.5ACH." |
| (13) | In IECC, Section R402.2.9.1, the numeral "(i)" is added before the words "cut at a 45 degree" and the following is added after the words "exterior wall:": "or (ii) lowered from top of slab 4" when a 4" thermal break material such as, but not limited to, felt or asphalt impregnated fiber board, with a minimum thickness of 1/4" is installed at the upper 4" of slab." |
| (14) | In IECC, Section R402.4.1, in the first sentence, the word "and" is deleted and replaced with the word "or." |
| (15) | In IECC, Section R402.4.1.1, the second and the last sentences are deleted and replaced with the following: "Where required by the code official, the builder shall certify compliance with criteria indicated in Table R1102.4.1 for items which are not readily visible during regularly scheduled inspections." |
| (16) | In IECC, Table R402.4.1.1 in the column titled "COMPONENT", the following changes are made:
|
| (17) | In IECC, Section R402.4.1.2, the following changes are made:
|
| (18) | In IECC, Section R402.4.1.3, the following changes are made:
|
| (19) | In IECC, Section R402.6 is deleted. |
| (20) | In IECC, Section R403.3.1 is deleted and replaced with the following: "Ducts located outside conditioned space. Supply and return ducts in attics shall be insulated to a minimum of R-8 where three inches (76.2 mm) in diameter and greater and R-6 where less than three inches (76.2 mm) in diameter. Supply and return ducts in other portions of the building shall be insulated to a minimum of R-6 where three inches (76.2 mm) in diameter or greater and R-4.2 where less than three inches (76.2 mm) in diameter. Exception: Ducts or portions thereof located completely inside the building thermal envelope." |
| (21) | In IECC, Section R403.3.3, is deleted. |
| (22) | In IECC, Section R403.3.3.1 is deleted. |
| (23) | In IECC, Section R403.3.5, the following changes are made:
|
| (24) | In IECC, Section N1103.3.6 (R403.3.6) the following changes are made:
|
| (25) | In IECC, Section N1103.3.7 (R403.3.7) the words "or plenums" are deleted. |
| (26) | In IECC, Section N1103.5.1.1 (R403.5.1.1) the words "Where installed" are added at the beginning of the first sentence. |
| (27) | IECC, Section R403.6.2, is deleted and replaced with the following: "R403.6.2 Whole-house mechanical ventilation system fan efficacy. Fans used to provide whole-house mechanical ventilation shall meet the efficacy requirements of Table R403.6.2. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole-house mechanical ventilation, the air handler shall be powered by an electronically commutated motor." |
| (28) | In IECC, Section R403.6.2, the table is deleted and replaced with the following: "TABLE R403.6.2 MECHANICAL VENTILATION SYSTEM FAN EFFICACY
|
| (29) | In IECC, Section R403.6.3 is deleted. |
| (30) | In IECC, Section R403.7, the word "approved" is deleted in the first sentence and the following is added after the word "methodologies": "complying with R403.7.1." |
| (31) | A new IECC, Section R403.7.1, is added as follows: "R403.7.1 Qualifications. An individual performing load calculations shall be qualified by completing HVAC training from one of the following: 1. HVAC load calculation education from ACCA; 2. A recognized educational institution; 3. HVAC equipment manufacturer's training; or 4. Other recognized industry certification." |
| (32) | In IECC, Section R404.1, the word "All" is replaced with "Not less than 90 percent of the lamps in." |
| (33) | In IECC, Section R404.1.1 is deleted. |
| (34) | In IECC, Section R404.2 is deleted. |
| (35) | In IECC, Section R404.3 is deleted. |
| (36) | In IECC, Section R405.2 the following changes are made:
|
| (37) | In IECC, Section R406.3 "Building thermal envelope" is deleted, and replaced with the following: "Building thermal envelope and on-site renewables. The proposed total building thermal envelope UA, which is the sum of U-factor times assembly area, shall be less than or equal to the building thermal envelope UA using the prescriptive U-factors From Table N1102.1.2 multiplied by 1.15 in accordance with Equation 11-4. The area-weighted maximum fenestration SHGC permitted in Climate Zones 0 through 3 shall be 0.30.UAProposed design = 1.15 x UAPrescriptive reference design (Equation 11-4)." |
| (38) | In IECC, Section R406.3.1 is deleted. |
| (39) | In IECC, Section R406.3.2 is deleted. |
| (40) | In IECC, Section R406.4 the following changes are made:
|
| (41) | In IECC, Section R406.5 in the column titled ENERGY RATING INDEX of Table R406.5, the following changes are made:
|
| (42) | In IECC, Section R408 is deleted.
|
Amended by Chapter 47, 2026 General Session
| << Previous Section (15A-3-601) | Download Options PDF | RTF | XML | Next Section (15A-3-801) >> |