the first sentence is deleted and replaced as
follows: "Groups R-1, R-2, R-3, R-4, I-1, and I-4 occupancies";
the exceptions are
deleted and the following sentence is
530
added after the first sentence: "A minimum of one carbon monoxide alarm shall be
installed on
531
each habitable level."
4. Page
32, Lines 928 through 932
:
928
Section 11.
Section
15A-3-113
is amended to read:
929
15A-3-113. Amendments to Chapters 32 through 35 of IBC.
930
(1) A new section IBC, Section
{
3401.6
}
3401.7
, is added as follows:
"
{
3401.6
}
3401.7
Parapet bracing,
931
wall anchors, and other appendages. Until June 30, 2014, a building constructed before
1975
932
shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers,
5. Page
74, Lines 1740 through 1742
:
1740
[(8)] (10) In IPC, Section 608.6, the following sentence is added at the end of the
1741
paragraph: "Any connection between potable water piping and sewer-connected waste
shall be
1742
protected by an air gap in accordance with Section
{
308.13.1
}
608.13.1
."
6. Page
79, Lines 1900 through 1901
:
1900
terminate out the roof. The flow control device shall be installed in accordance with the
1901
manufacturers instructions."
Section 25. Section 15A-3-311 is amended to read:
15A-3-311
.
Amendments to Chapter 11 of IPC.
(1) IPC, Section 1104.2, is deleted and replaced with the following: "1104.2
Combining storm and sanitary drainage prohibited. The combining of sanitary and storm
drainage systems is prohibited."
(2) IPC, Section
{
1108
}
1109
, is deleted.
Renumber remaining sections accordingly.
The motion passed unanimously with Rep. Bird absent for the vote.
MOTION: Rep. Wiley moved to amend the bill as follows:
1. Page
2, Lines 41 through 43
:
41
15A-3-307, as enacted by Laws of Utah 2011, Chapter 14
42
{
15A-3-308, as enacted by Laws of Utah 2011, Chapter 14
}
43
15A-3-309, as enacted by Laws of Utah 2011, Chapter 14
2. Page
77, Line 1835 through Page 78, Line 1857
:
1835
{
Section 22.
Section
15A-3-308
is amended to read:
1836
15A-3-308. Amendments to Chapter 8 of IPC.
1837
[IPC, Chapter 8, is not amended.]
1838
(1) In IPC, Section 802.1.8, the words "or directly connect" are added after the
word
1839
"break".
1840
(2) In IPC, Section 802, a new Section 802.1.8.1 is added as follows: "802.1.8.1
1841
Gravity grease interceptor connection: Those sinks or appliances draining into a
gravity grease
1842
interceptor shall discharge directly or indirectly through an air gap or air break into
a floor
1843
sink."
1844
(3) In IPC, Section 802, a new Section 802.1.8.2 is added as follows: "802.1.8.2
1845
Hydromechanical grease interceptor connection. Those sinks used for washing and
primary
1846
rinsing of utensils, dishes, pots, pans or service ware and draining through a
hydromechanical
1847
interceptor shall be directly connected to the interceptor. The sinks shall be trapped
and vented
1848
to prevent odors from the grease interceptor escaping through the sinks into the
building. A
1849
flow control device furnished by the manufacturer shall be installed on the inlet side
of the
1850
interceptor and in accordance with the manufacturers installation instructions. A
floor sink
1851
shall be installed within five (5') feet downstream of the interceptor outlet. A
dedicated branch
1852
drain shall be provided to serve the hydromechanical interceptor and the floor sink
only. No
1853
connections of any kind shall be permitted between the outlet of the interceptor and
the
1854
connection of the floor sink."
1855
(4) In IPC, Section 802, a new Section 802.1.9 is added as follows: "802.1.9
Sanitizing
1856
sinks. Sinks used for the sanitizing of utensils, dishes, pots, pans, or service ware
shall
1857
discharge indirectly through an air gap or air break to the drainage system."
}
3. Page
79, Lines 1891 through 1901
:
1891
{
(2) In IPC, Section 1003.3.4, the following sentence is added before the last
sentence:
1892
"Hydrochemical grease interceptors and automatic grease removal devices shall not
indirectly
1893
discharge into a floor sink or any other indirect waste receptor, but shall directly
connect to the
1894
drainage system."
1895
(3) IPC, Section 1003.3.4.2, is deleted and replaced with the following:
"1003.3.4.2
1896
Rate of flow controls. Hydromechanical grease interceptors shall be equipped with
devices to
1897
control the rate of water flow so that the water flow does not exceed the rated flow.
The flow
1898
control device shall be vented. The vent from the flow control device shall connect
to the
1899
plumbing vent system within the building or an approved and listed air admittance
valve or
1900
terminate out the roof. The flow control device shall be installed in accordance with
the
1901
manufacturers instructions."
}
The motion passed unanimously with Rep. Bird absent for the vote.
Rep. Wilson presented the bill to the committee, distributing a handout concerning the second
amendment, and being assisted by Kerry Cramer, Salt Lake Valley Health Department, and Scott
Adams, Park City Fire District.
Scott Marsell, Building Official of Sandy City, spoke in favor of the bill.
MOTION: Rep. Wiley moved to transmit H.B. 310 with a favorable recommendation. The
motion passed unanimously with Rep. Bird absent for the vote.
MOTION: Rep. Wiley moved to place H.B. 210 on the Consent Calendar. The motion failed
with Rep. Layton and Rep. Peterson voting in opposition and Rep. Bird absent for the vote.
H.B. 202 Energy Conservation Code Amendments (Rep. B. Wilson)
MOTION: Rep. Wilson moved to amend H.B. 202 as follows:
1. Page
10, Lines 269 through 273
:
269
Section 4. Study on improving residential energy efficiency.
270
(1) During the 2013 interim, the Architectural Advisory Committee of the Uniform
271
Building Code Commission, in consultation with the Mechanical Advisory Committee of
the
272
Uniform Building Code Commission, shall study and make recommendations
increase residential energy efficiency by 5% by January 1, 2015
}
regarding
increasing residential energy performance
.
The motion passed unanimously with Rep. Bird and Rep. Froerer absent for the vote.
Rep. Wilson explained the bill to the committee assisted by Ron McArthur of the Architectural
Code Committee. Roger Evans, Park City Building Department, spoke to the bill.
The following individuals spoke in favor of the bill:
Kevin Emerson Utah Clean Energy
Chris Kyler Utah Realtors
Mitch Richardson Utah Home Performance Association
Steve Erickson Crossroads Urban Center
Taz Biesinger Utah Homebuilders Association
The following individuals spoke in opposition to the bill:
Robert Bader consulting engineer
Greg Curtis American Chemistry Council (2 handouts)
MOTION: Rep. Duckworth moved to transmit H.B. 202 with a favorable recommendation.
SUBSTITUTE MOTION: Rep. Peterson moved to adjourn. The motion failed with Rep.
Layton, Rep. Peterson, and Rep. Roberts voting in favor and Rep. Froerer and Rep. Dunnigan
absent for the vote.
The original motion passed with Rep. Peterson, Rep. Roberts, and Rep. Stanard voting in
opposition and Rep. Froerer and Rep. Dunnigan absent for the vote.
MOTION: Rep. Stanard moved to adjourn. The motion passed unanimously with Rep.
Froerer and Rep. Dunnigan absent for the vote.
Vice Chair Pitcher adjourned the meeting at 9:53 a.m.
________________________________
Rep. James Dunnigan, Chair