1     
FIRE CODE AMENDMENTS

2     
2015 GENERAL SESSION

3     
STATE OF UTAH

4     
Chief Sponsor: Curtis S. Bramble

5     
House Sponsor: James A. Dunnigan

6     

7     LONG TITLE
8     General Description:
9          This bill modifies provisions of the State Fire Code relating to carbon monoxide
10     detection.
11     Highlighted Provisions:
12          This bill:
13          ▸     modifies references to certain standards established by Underwriters Laboratories,
14     Inc. that relate to carbon monoxide detection systems.
15     Money Appropriated in this Bill:
16          None
17     Other Special Clauses:
18          None
19     Utah Code Sections Affected:
20     AMENDS:
21          15A-5-204, as last amended by Laws of Utah 2014, Chapters 74 and 243
22     

23     Be it enacted by the Legislature of the state of Utah:
24          Section 1. Section 15A-5-204 is amended to read:
25          15A-5-204. Amendments and additions to IFC related to fire protection systems.
26          For IFC, Fire Protection Systems:
27          (1) IFC, Chapter 9, Section 901.2, Construction Documents, is amended to add the
28     following at the end of the section: "The code official has the authority to request record
29     drawings ("as builts") to verify any modifications to the previously approved construction

30     documents."
31          (2) IFC, Chapter 9, Section 901.4.6, Pump and Riser Room Size, is deleted and
32     replaced with the following: "Pump and Riser Room Size. Fire pump and automatic sprinkler
33     system riser rooms shall be designed with adequate space for all installed equipment necessary
34     for the installation and to provide sufficient working space around the stationary equipment.
35     Clearances around equipment shall be in accordance with manufacturer requirements and not
36     less than the following minimum elements:
37          901.4.6.1 A minimum clear and unobstructed distance of 12 inches shall be provided
38     from the installed equipment to the elements of permanent construction.
39          901.4.6.2 A minimum clear and unobstructed distance of 12 inches shall be provided
40     between all other installed equipment and appliances.
41          901.4.6.3 A clear and unobstructed width of 36 inches shall be provided in front of all
42     installed equipment and appliances, to allow for inspection, service, repair or replacement
43     without removing such elements of permanent construction or disabling the function of a
44     required fire-resistance-rated assembly.
45          901.4.6.4 Automatic sprinkler system riser rooms shall be provided with a clear and
46     unobstructed passageway to the riser room of not less than 36 inches, and openings into the
47     room shall be clear and unobstructed, with doors swinging in the outward direction from the
48     room and the opening providing a clear width of not less than 34 inches and a clear height of
49     the door opening shall not be less than 80 inches.
50          901.4.6.5 Fire pump rooms shall be provided with a clear and unobstructed
51     passageway to the fire pump room of not less than 72 inches, and openings into the room shall
52     be clear, unobstructed and large enough to allow for the removal of the largest piece of
53     equipment, with doors swinging in the outward direction from the room and the opening
54     providing a clear width of not less than 68 inches and a clear height of the door opening shall
55     not be less than 80 inches."
56          (3) IFC, Chapter 9, Section 903.2.1.2, Group A-2, is amended to add the following
57     subsection: "4. An automatic fire sprinkler system shall be provided throughout Group A-2

58     occupancies where indoor pyrotechnics are used."
59          (4) IFC, Chapter 9, Section 903.2.2, Ambulatory Health Care Facilities, is amended as
60     follows: On line two delete the words "all fire areas floor" and replace with the word
61     "buildings" and delete the last paragraph.
62          (5) IFC, Chapter 9, Section 903.2.4, Group F-1, Subsection 2, is deleted and rewritten
63     as follows: "A Group F-1 fire area is located more than three stories above the lowest level of
64     fire department vehicle access."
65          (6) IFC, Chapter 9, Section 903.2.7, Group M, Subsection 2, is deleted and rewritten as
66     follows: "A Group M fire area is located more than three stories above the lowest level of fire
67     department vehicle access."
68          (7) IFC, Chapter 9, Section 903.2.8 Group R, is amended to add the following:
69     "Exception: Detached one- and two-family dwellings and multiple single-family dwellings
70     (townhouses) constructed in accordance with the International Residential Code for one- and
71     two-family dwellings."
72          (8) IFC, Chapter 9, Section 903.2.8, Group R, is amended to add a second exception as
73     follows: "Exception: Group R-4 fire areas not more than 4,500 gross square feet and not
74     containing more than 16 residents, provided the building is equipped throughout with an
75     approved fire alarm system that is interconnected and receives its primary power from the
76     building wiring and a commercial power system."
77          (9) IFC, Chapter 9, Section 903.2.8 Group R, is amended to add a third exception as
78     follows: "Exception: Single story group R-1 occupancies with fire areas not more than 2,000
79     square feet that contain no installed plumbing or heating, where no cooking occurs, and
80     constructed of Type I-A, I-B, II-A, or II-B construction."
81          (10) IFC, Chapter 9, Section 903.2.9, Group S-1, Subsection 2, is deleted and rewritten
82     as follows: "A Group S-1 fire area is located more than three stories above the lowest level of
83     fire department vehicle access."
84          (11) IFC, Chapter 9, Section 903.3.1.1 is amended by adding the following subsection:
85     "903.3.1.1.2 Antifreeze Limitations. Antifreeze used in a new automatic sprinkler system

86     installed in accordance with NFPA 13 may not exceed a maximum concentration of 38%
87     premixed propylene glycol or 48% premixed glycerin, and the capacity of the system may not
88     exceed 150 gallons."
89          (12) IFC, Chapter 9, Section 903.3.1.2 is amended by adding the following subsection:
90     "903.3.1.2.2 Antifreeze Limitations. Antifreeze used in a new automatic sprinkler system
91     installed in accordance with NFPA 13R may not exceed a maximum concentration of 38%
92     premixed propylene glycol or 48% premixed glycerin, and the capacity of the system may not
93     exceed 150 gallons."
94          (13) IFC, Chapter 9, Section 903.3.1.3 is amended by adding the following subsection:
95     "903.3.1.3.1 Antifreeze Limitations. Antifreeze used in a new automatic sprinkler system
96     installed in accordance with NFPA 13D may not exceed a maximum concentration of 38%
97     premixed propylene glycol or 48% premixed glycerin, and the capacity of the system may not
98     exceed 150 gallons."
99          (14) IFC, Chapter 9, Section 903.3.5, Water supplies, is amended as follows: On line
100     six, after the word "Code", add "and as amended in Utah's State Construction Code".
101          (15) IFC, Chapter 9, Section 903.5 is amended to add the following subsection:
102     "903.5.1 Tag and Information. A tag shall be attached to the riser indicating the date the
103     antifreeze solution was tested. The tag shall also indicate the type and concentration of
104     antifreeze solution by volume with which the system is filled, the name of the contractor that
105     tested the antifreeze solution, the contractor's license number, and a warning to test the
106     concentration of the antifreeze solutions at yearly intervals."
107          (16) IFC, Chapter 9, Section 904.11, Commercial cooking systems, is deleted and
108     rewritten as follows: "The automatic fire extinguishing system for commercial cooking systems
109     shall be of a type recognized for protection of commercial cooking equipment and exhaust
110     systems. Pre-engineered automatic extinguishing systems shall be tested in accordance with
111     UL300 and listed and labeled for the intended application. The system shall be installed in
112     accordance with this code, its listing and the manufacturer's installation instructions. The
113     exception in Section 904.11 is not deleted and shall remain as currently written in the IFC."

114          (17) IFC, Chapter 9, Section 904.11.3, Carbon dioxide systems, and Section
115     904.11.3.1, Ventilation system, are deleted and rewritten as follows:
116          (a) "Existing automatic fire extinguishing systems used for commercial cooking that
117     use dry chemical are prohibited and shall be removed from service."
118          (b) "Existing wet chemical fire extinguishing systems used for commercial cooking
119     that are not UL300 listed and labeled are prohibited and shall be either removed or upgraded to
120     a UL300 listed and labeled system."
121          (18) IFC, Chapter 9, Section 904.11.4, Special provisions for automatic sprinkler
122     systems, is amended to add the following subsection: "904.11.4.2 Existing automatic fire
123     sprinkler systems protecting commercial cooking equipment, hood, and exhaust systems that
124     generate appreciable depth of cooking oils shall be replaced with a UL300 system that is listed
125     and labeled for the intended application."
126          (19) IFC, Chapter 9, Section 904.11.6.2, Extinguishing system service, is amended to
127     add the following: "Exception: Automatic fire extinguishing systems located in occupancies
128     where usage is limited and less than six consecutive months may be serviced annually if the
129     annual service is conducted immediately before the period of usage, and approval is received
130     from the AHJ."
131          (20) IFC, Chapter 9, Section 905.3.9 is a new subsection as follows: "Open Parking
132     Garages. Open parking garages shall be equipped with an approved Class I manual standpipe
133     system when fire department access is not provided for firefighting operations to within 150
134     feet of all portions of the open parking garage as measured from the approved fire department
135     vehicle access. Class I manual standpipe shall be accessible throughout the parking garage
136     such that all portions of the parking structure are protected within 150 feet of a hose
137     connection.
138          Exception: Open parking garages equipped throughout with an automatic sprinkler
139     system in accordance with Section 903.3.1.1."
140          (21) IFC, Chapter 9, Section 905.8, Dry Standpipes, Exception is deleted and rewritten
141     as follows: "Where subject to freezing conditions and approved by the fire code official."

142          (22) IFC, Chapter 9, Section 905.11, Existing buildings, and IFC, Chapter 11, Section
143     1103.6, Standpipes, are deleted.
144          (23) In IFC, Chapter 9, Section 906.1, Where Required, the exception under paragraph
145     1 is deleted and rewritten to read: "Exception: In new and existing Group A, B, and E
146     occupancies equipped with quick response sprinklers, portable fire extinguishers shall be
147     required only in locations specified in items 2 through 6.
148          (24) IFC, Chapter 9, Section 907.2.3 Group E:
149          (a) The first sentence is deleted and rewritten as follows: "A manual fire alarm system
150     that initiates the occupant notification system in accordance with Section 907.5 and installed in
151     accordance with Section 907.6 shall be installed in Group E occupancies."
152          (b) Exception number 3, on line five, delete the words, "emergency voice/alarm
153     communication system" and replace with "occupant notification system."
154          (25) IFC, Chapter 9, 907.8, Inspection, testing, and maintenance, is amended to add the
155     following sentences at the end of the section: "Increases in nuisance alarms shall require the
156     fire alarm system to be tested for sensitivity. Fire alarm systems that continue after sensitivity
157     testing with unwarranted nuisance alarms shall be replaced as directed by the AHJ."
158          (26) IFC, Chapter 9, Section 908.7, Carbon Monoxide Alarms, is deleted and rewritten
159     as follows:
160          "908.7 Carbon Monoxide Detection.
161          908.7.1 Groups R-1, R-2, R-3, R-4, I-1, and I-4. Carbon monoxide detection shall be
162     installed on each habitable level of a dwelling unit or a sleeping unit in Groups R-1, R-2, R-3,
163     R-4, I-1, and I-4 occupancies that are equipped with a fuel-burning appliance.
164          908.7.1.1 If more than one carbon monoxide detector is required, the carbon monoxide
165     detectors shall be interconnected as required in IFC, Chapter 9, Section 907.2.11.3.
166          908.7.1.2 In new construction, a carbon monoxide detector shall receive its primary
167     power as required under IFC, Chapter 9, Section 907.2.11.4.
168          908.7.1.3 Upon completion of the installation, a carbon monoxide detector system
169     shall meet the requirements listed in NFPA 720, Installation of Carbon Monoxide Detection

170     and Warning Equipment and [UL 2034, Standard for Single and Multiple Carbon Monoxide
171     Alarms] UL 2075, Standard for Gas and Vapor Detectors and Sensors.
172          908.7.2 Group E. A carbon monoxide detection system shall be installed in new
173     buildings that contain Group E occupancies in accordance with IFC, Chapter 9, Sections
174     908.7.2.1 through 908.7.2.6. A carbon monoxide detection system shall be installed in existing
175     buildings that contain Group E occupancies in accordance with IFC, Chapter 11, Section
176     1103.9.
177          908.7.2.1 Where required. In Group E occupancies, a carbon monoxide detection
178     system shall be provided where a fuel-burning appliance, a fuel-burning fireplace, or a
179     fuel-burning forced air furnace is present.
180          908.7.2.2 Detection equipment. Each carbon monoxide detection system shall be
181     installed in accordance with NFPA 720 and the manufacturer's instructions, and be listed as
182     complying with [UL 2034 and] UL 2075.
183          908.7.2.3 Locations. Each carbon monoxide detection system shall be installed in the
184     locations specified in NFPA 720.
185          908.7.2.4 Combination detectors. A combination carbon monoxide/smoke detector is
186     an acceptable alternative to a carbon monoxide detection system if the combination carbon
187     monoxide/smoke detector is listed in accordance with UL 2075 and UL 268.
188          908.7.2.5 Power source. Each carbon monoxide detection system shall receive primary
189     power from the building wiring if the wiring is served from a commercial source. If primary
190     power is interrupted, each carbon monoxide detection system shall receive power from a
191     battery. Wiring shall be permanent and without a disconnecting switch other than that required
192     for over-current protection.
193          908.7.2.6 Maintenance. Each carbon monoxide detection system shall be maintained
194     in accordance with NFPA 720. A carbon monoxide detection system that becomes inoperable
195     or begins to produce end-of-life signals shall be replaced."
196          (27) IFC Section 908.7.1 is renumbered to 908.7.3.