1     
FIRE CODE AMENDMENTS

2     
2015 GENERAL SESSION

3     
STATE OF UTAH

4     
Chief Sponsor: Curtis S. Bramble

5     
House Sponsor: James A. Dunnigan

6     

7     LONG TITLE
8     Committee Note:
9          The Business and Labor Interim Committee recommended this bill.
10     General Description:
11          This bill modifies provisions of the State Fire Code relating to carbon monoxide
12     detection.
13     Highlighted Provisions:
14          This bill:
15          ▸     modifies references to certain standards established by Underwriters Laboratories,
16     Inc. that relate to carbon monoxide detection systems.
17     Money Appropriated in this Bill:
18          None
19     Other Special Clauses:
20          None
21     Utah Code Sections Affected:
22     AMENDS:
23          15A-5-204, as last amended by Laws of Utah 2014, Chapters 74 and 243
24     

25     Be it enacted by the Legislature of the state of Utah:
26          Section 1. Section 15A-5-204 is amended to read:
27          15A-5-204. Amendments and additions to IFC related to fire protection systems.

28          For IFC, Fire Protection Systems:
29          (1) IFC, Chapter 9, Section 901.2, Construction Documents, is amended to add the
30     following at the end of the section: "The code official has the authority to request record
31     drawings ("as builts") to verify any modifications to the previously approved construction
32     documents."
33          (2) IFC, Chapter 9, Section 901.4.6, Pump and Riser Room Size, is deleted and
34     replaced with the following: "Pump and Riser Room Size. Fire pump and automatic sprinkler
35     system riser rooms shall be designed with adequate space for all installed equipment necessary
36     for the installation and to provide sufficient working space around the stationary equipment.
37     Clearances around equipment shall be in accordance with manufacturer requirements and not
38     less than the following minimum elements:
39          901.4.6.1 A minimum clear and unobstructed distance of 12 inches shall be provided
40     from the installed equipment to the elements of permanent construction.
41          901.4.6.2 A minimum clear and unobstructed distance of 12 inches shall be provided
42     between all other installed equipment and appliances.
43          901.4.6.3 A clear and unobstructed width of 36 inches shall be provided in front of all
44     installed equipment and appliances, to allow for inspection, service, repair or replacement
45     without removing such elements of permanent construction or disabling the function of a
46     required fire-resistance-rated assembly.
47          901.4.6.4 Automatic sprinkler system riser rooms shall be provided with a clear and
48     unobstructed passageway to the riser room of not less than 36 inches, and openings into the
49     room shall be clear and unobstructed, with doors swinging in the outward direction from the
50     room and the opening providing a clear width of not less than 34 inches and a clear height of
51     the door opening shall not be less than 80 inches.
52          901.4.6.5 Fire pump rooms shall be provided with a clear and unobstructed
53     passageway to the fire pump room of not less than 72 inches, and openings into the room shall
54     be clear, unobstructed and large enough to allow for the removal of the largest piece of
55     equipment, with doors swinging in the outward direction from the room and the opening
56     providing a clear width of not less than 68 inches and a clear height of the door opening shall
57     not be less than 80 inches."
58          (3) IFC, Chapter 9, Section 903.2.1.2, Group A-2, is amended to add the following

59     subsection: "4. An automatic fire sprinkler system shall be provided throughout Group A-2
60     occupancies where indoor pyrotechnics are used."
61          (4) IFC, Chapter 9, Section 903.2.2, Ambulatory Health Care Facilities, is amended as
62     follows: On line two delete the words "all fire areas floor" and replace with the word
63     "buildings" and delete the last paragraph.
64          (5) IFC, Chapter 9, Section 903.2.4, Group F-1, Subsection 2, is deleted and rewritten
65     as follows: "A Group F-1 fire area is located more than three stories above the lowest level of
66     fire department vehicle access."
67          (6) IFC, Chapter 9, Section 903.2.7, Group M, Subsection 2, is deleted and rewritten as
68     follows: "A Group M fire area is located more than three stories above the lowest level of fire
69     department vehicle access."
70          (7) IFC, Chapter 9, Section 903.2.8 Group R, is amended to add the following:
71     "Exception: Detached one- and two-family dwellings and multiple single-family dwellings
72     (townhouses) constructed in accordance with the International Residential Code for one- and
73     two-family dwellings."
74          (8) IFC, Chapter 9, Section 903.2.8, Group R, is amended to add a second exception as
75     follows: "Exception: Group R-4 fire areas not more than 4,500 gross square feet and not
76     containing more than 16 residents, provided the building is equipped throughout with an
77     approved fire alarm system that is interconnected and receives its primary power from the
78     building wiring and a commercial power system."
79          (9) IFC, Chapter 9, Section 903.2.8 Group R, is amended to add a third exception as
80     follows: "Exception: Single story group R-1 occupancies with fire areas not more than 2,000
81     square feet that contain no installed plumbing or heating, where no cooking occurs, and
82     constructed of Type I-A, I-B, II-A, or II-B construction."
83          (10) IFC, Chapter 9, Section 903.2.9, Group S-1, Subsection 2, is deleted and rewritten
84     as follows: "A Group S-1 fire area is located more than three stories above the lowest level of
85     fire department vehicle access."
86          (11) IFC, Chapter 9, Section 903.3.1.1 is amended by adding the following subsection:
87     "903.3.1.1.2 Antifreeze Limitations. Antifreeze used in a new automatic sprinkler system
88     installed in accordance with NFPA 13 may not exceed a maximum concentration of 38%
89     premixed propylene glycol or 48% premixed glycerin, and the capacity of the system may not

90     exceed 150 gallons."
91          (12) IFC, Chapter 9, Section 903.3.1.2 is amended by adding the following subsection:
92     "903.3.1.2.2 Antifreeze Limitations. Antifreeze used in a new automatic sprinkler system
93     installed in accordance with NFPA 13R may not exceed a maximum concentration of 38%
94     premixed propylene glycol or 48% premixed glycerin, and the capacity of the system may not
95     exceed 150 gallons."
96          (13) IFC, Chapter 9, Section 903.3.1.3 is amended by adding the following subsection:
97     "903.3.1.3.1 Antifreeze Limitations. Antifreeze used in a new automatic sprinkler system
98     installed in accordance with NFPA 13D may not exceed a maximum concentration of 38%
99     premixed propylene glycol or 48% premixed glycerin, and the capacity of the system may not
100     exceed 150 gallons."
101          (14) IFC, Chapter 9, Section 903.3.5, Water supplies, is amended as follows: On line
102     six, after the word "Code", add "and as amended in Utah's State Construction Code".
103          (15) IFC, Chapter 9, Section 903.5 is amended to add the following subsection:
104     "903.5.1 Tag and Information. A tag shall be attached to the riser indicating the date the
105     antifreeze solution was tested. The tag shall also indicate the type and concentration of
106     antifreeze solution by volume with which the system is filled, the name of the contractor that
107     tested the antifreeze solution, the contractor's license number, and a warning to test the
108     concentration of the antifreeze solutions at yearly intervals."
109          (16) IFC, Chapter 9, Section 904.11, Commercial cooking systems, is deleted and
110     rewritten as follows: "The automatic fire extinguishing system for commercial cooking systems
111     shall be of a type recognized for protection of commercial cooking equipment and exhaust
112     systems. Pre-engineered automatic extinguishing systems shall be tested in accordance with
113     UL300 and listed and labeled for the intended application. The system shall be installed in
114     accordance with this code, its listing and the manufacturer's installation instructions. The
115     exception in Section 904.11 is not deleted and shall remain as currently written in the IFC."
116          (17) IFC, Chapter 9, Section 904.11.3, Carbon dioxide systems, and Section
117     904.11.3.1, Ventilation system, are deleted and rewritten as follows:
118          (a) "Existing automatic fire extinguishing systems used for commercial cooking that
119     use dry chemical are prohibited and shall be removed from service."
120          (b) "Existing wet chemical fire extinguishing systems used for commercial cooking

121     that are not UL300 listed and labeled are prohibited and shall be either removed or upgraded to
122     a UL300 listed and labeled system."
123          (18) IFC, Chapter 9, Section 904.11.4, Special provisions for automatic sprinkler
124     systems, is amended to add the following subsection: "904.11.4.2 Existing automatic fire
125     sprinkler systems protecting commercial cooking equipment, hood, and exhaust systems that
126     generate appreciable depth of cooking oils shall be replaced with a UL300 system that is listed
127     and labeled for the intended application."
128          (19) IFC, Chapter 9, Section 904.11.6.2, Extinguishing system service, is amended to
129     add the following: "Exception: Automatic fire extinguishing systems located in occupancies
130     where usage is limited and less than six consecutive months may be serviced annually if the
131     annual service is conducted immediately before the period of usage, and approval is received
132     from the AHJ."
133          (20) IFC, Chapter 9, Section 905.3.9 is a new subsection as follows: "Open Parking
134     Garages. Open parking garages shall be equipped with an approved Class I manual standpipe
135     system when fire department access is not provided for firefighting operations to within 150
136     feet of all portions of the open parking garage as measured from the approved fire department
137     vehicle access. Class I manual standpipe shall be accessible throughout the parking garage
138     such that all portions of the parking structure are protected within 150 feet of a hose
139     connection.
140          Exception: Open parking garages equipped throughout with an automatic sprinkler
141     system in accordance with Section 903.3.1.1."
142          (21) IFC, Chapter 9, Section 905.8, Dry Standpipes, Exception is deleted and rewritten
143     as follows: "Where subject to freezing conditions and approved by the fire code official."
144          (22) IFC, Chapter 9, Section 905.11, Existing buildings, and IFC, Chapter 11, Section
145     1103.6, Standpipes, are deleted.
146          (23) In IFC, Chapter 9, Section 906.1, Where Required, the exception under paragraph
147     1 is deleted and rewritten to read: "Exception: In new and existing Group A, B, and E
148     occupancies equipped with quick response sprinklers, portable fire extinguishers shall be
149     required only in locations specified in items 2 through 6.
150          (24) IFC, Chapter 9, Section 907.2.3 Group E:
151          (a) The first sentence is deleted and rewritten as follows: "A manual fire alarm system

152     that initiates the occupant notification system in accordance with Section 907.5 and installed in
153     accordance with Section 907.6 shall be installed in Group E occupancies."
154          (b) Exception number 3, on line five, delete the words, "emergency voice/alarm
155     communication system" and replace with "occupant notification system."
156          (25) IFC, Chapter 9, 907.8, Inspection, testing, and maintenance, is amended to add the
157     following sentences at the end of the section: "Increases in nuisance alarms shall require the
158     fire alarm system to be tested for sensitivity. Fire alarm systems that continue after sensitivity
159     testing with unwarranted nuisance alarms shall be replaced as directed by the AHJ."
160          (26) IFC, Chapter 9, Section 908.7, Carbon Monoxide Alarms, is deleted and rewritten
161     as follows:
162          "908.7 Carbon Monoxide Detection.
163          908.7.1 Groups R-1, R-2, R-3, R-4, I-1, and I-4. Carbon monoxide detection shall be
164     installed on each habitable level of a dwelling unit or a sleeping unit in Groups R-1, R-2, R-3,
165     R-4, I-1, and I-4 occupancies that are equipped with a fuel-burning appliance.
166          908.7.1.1 If more than one carbon monoxide detector is required, the carbon monoxide
167     detectors shall be interconnected as required in IFC, Chapter 9, Section 907.2.11.3.
168          908.7.1.2 In new construction, a carbon monoxide detector shall receive its primary
169     power as required under IFC, Chapter 9, Section 907.2.11.4.
170          908.7.1.3 Upon completion of the installation, a carbon monoxide detector system
171     shall meet the requirements listed in NFPA 720, Installation of Carbon Monoxide Detection
172     and Warning Equipment and [UL 2034, Standard for Single and Multiple Carbon Monoxide
173     Alarms] UL 2075, Standard for Gas and Vapor Detectors and Sensors.
174          908.7.2 Group E. A carbon monoxide detection system shall be installed in new
175     buildings that contain Group E occupancies in accordance with IFC, Chapter 9, Sections
176     908.7.2.1 through 908.7.2.6. A carbon monoxide detection system shall be installed in existing
177     buildings that contain Group E occupancies in accordance with IFC, Chapter 11, Section
178     1103.9.
179          908.7.2.1 Where required. In Group E occupancies, a carbon monoxide detection
180     system shall be provided where a fuel-burning appliance, a fuel-burning fireplace, or a
181     fuel-burning forced air furnace is present.
182          908.7.2.2 Detection equipment. Each carbon monoxide detection system shall be

183     installed in accordance with NFPA 720 and the manufacturer's instructions, and be listed as
184     complying with [UL 2034 and] UL 2075.
185          908.7.2.3 Locations. Each carbon monoxide detection system shall be installed in the
186     locations specified in NFPA 720.
187          908.7.2.4 Combination detectors. A combination carbon monoxide/smoke detector is
188     an acceptable alternative to a carbon monoxide detection system if the combination carbon
189     monoxide/smoke detector is listed in accordance with UL 2075 and UL 268.
190          908.7.2.5 Power source. Each carbon monoxide detection system shall receive primary
191     power from the building wiring if the wiring is served from a commercial source. If primary
192     power is interrupted, each carbon monoxide detection system shall receive power from a
193     battery. Wiring shall be permanent and without a disconnecting switch other than that required
194     for over-current protection.
195          908.7.2.6 Maintenance. Each carbon monoxide detection system shall be maintained
196     in accordance with NFPA 720. A carbon monoxide detection system that becomes inoperable
197     or begins to produce end-of-life signals shall be replaced."
198          (27) IFC Section 908.7.1 is renumbered to 908.7.3.






Legislative Review Note
     as of 10-17-14 3:15 PM


Office of Legislative Research and General Counsel