1     
BUILDING CONSTRUCTION AMENDMENTS

2     
2020 GENERAL SESSION

3     
STATE OF UTAH

4     
Chief Sponsor: Casey Snider

5     
Senate Sponsor: Curtis S. Bramble

6     

7     LONG TITLE
8     General Description:
9          This bill amends the State Construction and Fire Codes Act and enacts provisions
10     regarding the use of mass timber products.
11     Highlighted Provisions:
12          This bill:
13          ▸     amends the definition of the State Construction Code to include standards for the
14     use of mass timber products;
15          ▸     enacts building standards for the use of mass timber products for residential and
16     commercial building construction; and
17          ▸     makes technical and conforming changes.
18     Money Appropriated in this Bill:
19          None
20     Other Special Clauses:
21          None
22     Utah Code Sections Affected:
23     AMENDS:
24          15A-1-102, as enacted by Laws of Utah 2011, Chapter 14
25          15A-2-101, as enacted by Laws of Utah 2011, Chapter 14
26          15A-2-102, as last amended by Laws of Utah 2016, Chapter 249
27     ENACTS:
28          15A-2a-101, Utah Code Annotated 1953
29          15A-2a-102, Utah Code Annotated 1953

30          15A-2a-201, Utah Code Annotated 1953
31          15A-2a-202, Utah Code Annotated 1953
32          15A-2a-203, Utah Code Annotated 1953
33          15A-2a-204, Utah Code Annotated 1953
34          15A-2a-301, Utah Code Annotated 1953
35          15A-2a-302, Utah Code Annotated 1953
36          15A-2a-401, Utah Code Annotated 1953
37     

38     Be it enacted by the Legislature of the state of Utah:
39          Section 1. Section 15A-1-102 is amended to read:
40          15A-1-102. Definitions.
41          As used in this title:
42          (1) "Board" means the Utah Fire Prevention Board created in Section 53-7-203.
43          (2) "Division" means the Division of Occupational and Professional Licensing created
44     in Section 58-1-103, except as provided in:
45          (a) Part 4, State Fire Code Administration Act; and
46          (b) Chapter 5, State Fire Code Act.
47          (3) "State Construction Code" means the State Construction Code adopted by:
48          (a) Chapter 2, Adoption of State Construction Code;
49          (b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as
50     Part of State Construction Code;
51          [(b)] (c) Chapter 3, Statewide Amendments Incorporated as Part of State Construction
52     Code; [and]
53          [(c)] (d) Chapter 4, Local Amendments Incorporated as Part of State Construction
54     Code[.]; and
55          (e) Chapter 6, Additional Construction Requirements.
56          (4) "State Fire Code" means the State Fire Code adopted by Chapter 5, State Fire Code
57     Act.

58          (5) "Utah Code" means the Utah Code Annotated (1953), as amended.
59          Section 2. Section 15A-2-101 is amended to read:
60          15A-2-101. Title -- Adoption of code.
61          (1) This chapter is known as the "Adoption of State Construction Code."
62          (2) In accordance with Chapter 1, Part 2, State Construction Code Administration Act,
63     the Legislature repeals the State Construction Code in effect on July 1, 2010, and adopts the
64     following as the State Construction Code:
65          (a) this chapter;
66          (b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as
67     Part of State Construction Code;
68          [(b)] (c) Chapter 3, Statewide Amendments Incorporated as Part of State Construction
69     Code; [and]
70          [(c)] (d) Chapter 4, Local Amendments Incorporated as Part of State Construction
71     Code[.]; and
72          (e) Chapter 6, Additional Construction Requirements.
73          Section 3. Section 15A-2-102 is amended to read:
74          15A-2-102. Definitions.
75          As used in this chapter [and], Chapter 2a, Tall Wood Buildings of Mass Timber
76     Construction Incorporated as Part of State Construction Code, Chapter 3, Statewide
77     Amendments Incorporated as Part of State Construction Code, and Chapter 4, Local
78     Amendments Incorporated as Part of State Construction Code:
79          (1) "HUD Code" means the Federal Manufactured Housing Construction and Safety
80     Standards Act, as issued by the Department of Housing and Urban Development and published
81     in 24 C.F.R. Parts 3280 and 3282 (as revised April 1, 1990).
82          (2) "IBC" means the edition of the International Building Code adopted under Section
83     15A-2-103.
84          (3) "IEBC" means the edition of the International Existing Building Code adopted
85     under Section 15A-2-103.

86          (4) "IECC" means the edition of the International Energy Conservation Code adopted
87     under Section 15A-2-103.
88          (5) "IFGC" means the edition of the International Fuel Gas Code adopted under
89     Section 15A-2-103.
90          (6) "IMC" means the edition of the International Mechanical Code adopted under
91     Section 15A-2-103.
92          (7) "IPC" means the edition of the International Plumbing Code adopted under Section
93     15A-2-103.
94          (8) "IRC" means the edition of the International Residential Code adopted under
95     Section 15A-2-103.
96          (9) "NEC" means the edition of the National Electrical Code adopted under Section
97     15A-2-103.
98          (10) "UWUI" means the edition of the Utah Wildland Urban Interface Code adopted
99     under Section 15A-2-103.
100          Section 4. Section 15A-2a-101 is enacted to read:
101     
CHAPTER 2a. TALL WOOD BUILDINGS OF MASS TIMBER CONSTRUCTION

102     
INCORPORATED AS PART OF STATE CONSTRUCTION CODE

103     
Part 1. General Provisions

104          15A-2a-101. Title.
105          (1) This chapter is known as "Tall Wood Buildings of Mass Timber Construction
106     Incorporated as Part of State Construction Code."
107          (2) This chapter establishes building standards for the use of mass timber products in
108     residential and commercial building construction and is applicable statewide.
109          (3) Where this chapter replaces a section of the IBC that Chapter 3, Statewide
110     Amendments Incorporated as Part of State Construction Code, or Chapter 4, Local
111     Amendments Incorporated as Part of State Construction Code, amends, the amendment in
112     Chapter 3 or 4 shall apply to the IBC replacement in this chapter.
113          Section 5. Section 15A-2a-102 is enacted to read:

114          15A-2a-102. Definitions.
115          As used in this chapter:
116          (1) "Mass timber" means a structural element of Type IV construction primarily of
117     solid, built-up, panelized or engineered wood products that meet minimum cross section
118     dimensions of Type IV construction.
119          (2) "Non-combustible protection" (for mass timber) means non-combustible material in
120     accordance with IBC Section 703.5, designed to increase the fire-resistance rating and delay the
121     combustion of mass timber.
122          (3) "Wall, load-bearing" means any wall meeting either of the following classifications:
123          (a) any metal or wood stud wall that supports more than 100 pounds per linear foot
124     (1459 N/m) of vertical load in addition to its own weight; or
125          (b) any masonry or concrete, or mass timber wall that supports more than 200 pounds
126     per linear foot (2919 N/m) of vertical load in addition to its own weight.
127          Section 6. Section 15A-2a-201 is enacted to read:
128     
Part 2. Statewide Amendments to International Building Code

129          15A-2a-201. Amendments to Chapter 4 of IBC.
130          In IBC, Section 403.3.2, is deleted and replaced with the following: "403.3.3 Water
131     supply to required fire pumps. In all buildings that are more than 420 feet (128m) in building
132     height, and buildings of Type IV-A and IV-B construction that are more than 120 feet in
133     building height, required fire pumps shall be supplied by connections to not fewer than two
134     water mains located in different streets. Separate supply piping shall be provided between each
135     connection to the water main and the pumps. Each connection and the supply piping between
136     the connection and the pumps shall be sized to supply the flow and pressure required for the
137     pumps to operate.
138          Exception: Two connections to the same main shall be permitted provided that the main
139     is valved such that an interruption can be isolated so that the water supply will continue
140     without interruption through not fewer than one of the connections."
141          Section 7. Section 15A-2a-202 is enacted to read:

142          15A-2a-202. Amendments to Chapter 5 of IBC.
143          (1) In IBC, Table 504.3, is deleted and replaced with the following: "Table 504.3
144     ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE
145      OCCUPANCY
CLASSIFICATION
TYPE OF CONSTRUCTION
SEE
FOOTNOTES
TYPE ITYPE
II
TYPE
III
TYPE IVTYPE V
ABABABABCHTAB
146     A, B, E, F, M, S, UNSbUL16065556555656565655040
SUL1808575857518012085857060
147      H-1, H-2, H-3, H-5NSc, dUL160655565551209065655040
S
148      H-4NSc, dUL16065556555656565655040
SUL1808575857514010085857060
149      I-1 Condition 1, I-3NSd, eUL16065556555656565655040
SUL1808575857518012085857060
150      I-1 Condition 2, I-2NSd, e, fUL16065556555656565655040
SUL18085
151      I-4NSd, gUL16065556555656565655040
SUL1808575857518012085857060
152      RhNSdUL16065556555656565655040
S13D606060606060606060605040
S13R606060606060606060606060
SUL1808575857518012085857060
153     For SI: 1 foot = 304.8 mm
154          UL = Unlimited; NS = Buildings not equipped throughout with an automatic sprinkler
155     system; S = Buildings equipped throughout with an automatic sprinkler system installed in
156     accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic
157     sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped
158     throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
159          a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
160          b. See Section 903.2 for the minimum thresholds for protection by an automatic
161     sprinkler system for specific occupancies.

162          c. New Group H occupancies are required to be protected by an automatic sprinkler
163     system in accordance with Section 903.2.5.
164          d. The NS value is only for use in evaluation of existing building area in accordance
165     with the IEBC.
166          e. New Group I-1 and I-3 occupancies are required to be protected by an automatic
167     sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies,
168     Condition 1, see Exception 1 of Section 903.2.6.
169          f. New and existing Group I-2 occupancies are required to be protected by an automatic
170     sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International
171     Fire Code.
172          g. New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6.
173          h. New Group R occupancies are required to be protected by an automatic sprinkler
174     system in accordance with Section 903.2.8."
175          (2) In IBC, Table 504.4, "Allowable Number of Stories Above Grade Planea, b" delete
176     Type IV and replace it with the following, in relation to the occupancy classification and
177     footnotes as indicated:
178      OCCUPANCY CLASSIFICATIONTYPE OF CONSTRUCTION
SEE FOOTNOTESTYPE IV
ABCHT
179      A-1NS3333
S9644
180      A-2NS3333
S181264
181      A-3NS3333
S181264
182      A-4NS3333
S181264
183      A-5NS111UL
SULULULUL
184      BNS5555
S181296
185      ENS3333
S9644
186      F-1NS3334
S10755
187      F-2NS5555
S12866
188      H-1NSc, dNPNPNP1
S111
189      H-2NSc, d1112
S222
190      H-3NSc, d3334
S444
191      H-4NSc, d5555
S8766
192      H-5NSc, d2223
S333
193      I-1 Condition 1NSd, e4444
S10755
194      I-1 Condition 2NSd, e3334
S1064
195      I-2NSd, fNPNPNP1
S751
196      I-3NSd, e2222
S7533
197      I-4NSd, g3333
S9644
198      MNS4444
S12865
199     

R-1h

NSd4444
S13R
S181285
200      R-2hNSd4444
S13R
S181285
201      R-3hNSd4444
S13D
S13R
S181255
202      R-4hNSd4444
S13D
S13R
S181255
203      S-1NS4444
204      S10755
205      S-2NS4444
206      S12855
207      UNS4444
208      S9655
209     
     UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an
210     automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler
211     system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout
212     with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D =
213     Buildings equipped throughout with an automatic sprinkler system installed in accordance with
214     Section 903.3.1.3.
215          a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
216          b. See Section 903.2 for the minimum thresholds for protection by an automatic
217     sprinkler system for specific occupancies.
218          c. New Group H occupancies are required to be protected by an automatic sprinkler
219     system in accordance with Section 903.2.5.
220          d. The NS value is only for use in evaluation of existing building height in accordance
221     with the IEBC.
222          e. New Group I-1 and I-3 occupancies are required to be protected by an automatic
223     sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies,
224     Condition 1, see Exception 1 of Section 903.2.6.
225          f. New and existing Group I-2 occupancies are required to be protected by an automatic
226     sprinkler system in accordance with Sections 903.2.6 and 1103.5 of the International Fire
227     Code.
228          g. For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6.
229          h. New Group R occupancies are required to be protected by an automatic sprinkler
230     system in accordance with Section 903.2.8."
231          (3) In IBC, Table 506.2, "Allowable Area Factor (At = NS, S1, S13R, S13D or SM, as
232     applicable) in Square Feeta, b" delete Type IV and replace it with the following, in relation to the

233     occupancy classification and footnotes as indicated:
234      "OCCUPANCY
CLASSIFICATION
SEE
FOOTNOTES
TYPE OF CONSTRUCTION
TYPE IV
A
BCHT
235      A-1NS
45,00
0
30,00018,75015,000
S1
180,0
00
120,00075,00060,000
SM
135,0
00
90,00056,25045,000
236      A-2NS
45,00
0
30,00018,75015,000
S1
180,0
00
120,00075,00060,000
SM
135,0
00
90,00056,25045,000
237      A-3NS
45,00
0
30,00018,75015,000
S1
180,0
00
120,00075,00060,000
SM
135,0
00
90,00056,25045,000
238      A-4NS
45,00
0
30,00018,75015,000
S1
180,0
00
120,00075,00060,000
SM
135,0
00
90,00056,25045,000
239      A-5NS
UL
ULULUL
S1
SM
240      BNS
108,0
00
72,00045,00036,000
S1
432,0
00
288,000180,000144,000
SM
324,0
00
216,000135,000108,000
241      ENS
76,50
0
51,00031,87525,500
S1
306,0
00
204,000127,500102,000
SM
229,5
00
153,00095,62576,500
242      F-1NS
100,5
00
67,00041,87533,500
S1
402,0
00
268,000167,500134,000
SM
301,5
00
201,000125,625100,500
243      F-2NS
151,5
00
101,00063,12550,500
S1
606,0
00
404,000252,500202,000
SM
454,5
00
303,000189,375151,500
244      H-1NSc
10,50
0
10,50010,50010,500
S1
245      H-2NSc
10,50
0
10,50010,50010,500
S1
SM
246      H-3NSc
25,50
0
25,50025,50025,500
S1
SM
247      H-4NSc, d
72,00
0
54,00040,50036,000
S1
288,0
00
216,000162,000144,000
SM
216,0
00
162,000121,500108,000
248      H-5NSc, d
72,00
0
54,00040,50036,000
S1
288,0
00
216,000162,000144,000
SM
216,0
00
162,000121,500108,000
249      I-1NSd, e
54,00
0
36,00018,00018,000
S1
216,0
00
144,00072,00072,000
SM
162,0
00
108,00054,00054,000
250      I-2NSd, f
36,00
0
24,00012,00012,000
S1
144,0
00
96,00048,00048,000
SM
108,0
00
72,00036,00036,000
251      I-3NSd, e
36,00
0
24,00012,00012,000
S1
144,0
00
96,00048,00048,000
SM
108,0
00
72,00036,00036,000
252      I-4NSd, g
76,50
0
51,00025,50025,500
S1
306,0
00
204,000102,000102,000
SM
229,0
00
153,00076,50076,500
253      MNS
61,50
0
41,00025,62520,500
S1
246,0
00
164,000102,50082,000
SM
184,5
00
123,00076,87561,500
254      R-1hNSd
61,50
0
41,00025,62520,500
S13R
S1
246,0
00
164,000102,50082,000
SM
184,5
00
123,00076,87561,500
255      R-2hNSd
61,50
0
41,00025,62520,500
S13R
S1
246,0
00
164,000102,50082,000
SM
184,5
00
123,00076,87561,500
256      R-3hNSd
UL
ULULUL
S13D
S13R
S1
SM
257      R-4hNSd
61,50
0
41,00025,62520,500
S13D
S13R
S1
246,0
00
164,000102,50082,000
SM
184,5
00
123,00076,87561,500
258      S-1NS
76,50
0
51,00031,87525,500
S1
306,0
00
204,000127,500102,000
SM
229,5
00
153,00095,62576,500
259      S-2NS
115,5
00
77,00048,12538,500
S1
462,0
00
308,000192,500154,000
SM
346,5
00
308,000144,375115,500
260      UNSi
54,00
0
36,00022,50018,000
S1
216,0
00
144,00090,00072,000
SM
162,0
00
108,00067,50054,000
261          For SI: 1 square foot = 0.0929 m2.
262          UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an
263     automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane
264     equipped throughout with an automatic sprinkler system installed in accordance with Section
265     903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an
266     automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings
267     equipped throughout with an automatic sprinkler system installed in accordance with Section
268     903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed
269     in accordance with Section 903.3.1.3.
270          a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
271          b. See Section 903.2 for the minimum thresholds for protection by an automatic
272     sprinkler system for specific occupancies.
273          c. New Group H occupancies are required to be protected by an automatic sprinkler
274     system in accordance with Section 903.2.5.
275          d. The NS value is only for use in evaluation of existing building area in accordance
276     with the IEBC.
277          e. New Group I-1 and I-3 occupancies are required to be protected by an automatic
278     sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies,

279     Condition 1, see Exception 1 of Section 903.2.6.
280          f. New and existing Group I-2 occupancies are required to be protected by an automatic
281     sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International
282     Fire Code.
283          g. For New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6.
284          h. New Group R occupancies are required to be protected by an automatic sprinkler
285     system in accordance with Section 903.2.8.
286          i. The maximum allowable area for a single-story nonsprinklered Group U greenhouse
287     is permitted to be 9,000 square feet, or the allowable area shall be permitted to comply with
288     Table C102.1 of Appendix C."
289          (4) In IBC, Section 508.4.4 is deleted and replaced with the following: "508.4.4
290     Separation. Individual occupancies shall be separated from adjacent occupancies in accordance
291     with Table 508.4."
292          (5) In IBC, Section 508.4.4.1 is deleted and replaced with the following: "508.4.4.1
293     Construction. Required separations shall be fire barriers constructed in accordance with Section
294     707 or horizontal assemblies constructed in accordance with Section 711, or both, so as to
295     completely separate adjacent occupancies. Mass timber elements serving as fire barriers or
296     horizontal assemblies to separate occupancies in Type IV-B or IV-C construction shall be
297     separated from the interior of the building with an approved thermal barrier consisting of a
298     minimum of 1/2 inch (12.7 mm) gypsum board or a material that is tested in accordance with
299     and meets the acceptance criteria of both the Temperature Transmission Fire Test and the
300     Integrity Fire Test of NFPA 275."
301          (6) In IBC, Section 509, a new section is added as follows: "509.4.1.1 Type IV-B and
302     IV-C construction. Where Table 509 specifies a fire-resistance-rated separation, mass timber
303     elements serving as fire barriers or a horizontal assembly in Type IV-B or IV-C construction
304     shall be separated from the interior of the incidental use with an approved thermal barrier
305     consisting of a minimum of 1/2 inch (12.7 mm) gypsum board or a material that is tested in
306     accordance with and meets the acceptance criteria of both the Temperature Transmission Fire

307     Test and the Integrity Fire Test of NFPA 275."
308          Section 8. Section 15A-2a-203 is enacted to read:
309          15A-2a-203. Amendments to Chapter 6 of IBC.
310          (1) In IBC, Table 601 is deleted and replaced with the following:
311          "TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING
312     ELEMENTS (HOURS)
313      BUILDING ELEMENTTYPE ITYPE IITYPE IIITYPE IVTYPE V
ABABABABCHTAB
314      Primary structural framef
(see Section 202)
3a, b2a, b1b01b03a2a2aHT1b0
315      Bearing walls
Exterior
e, f
Interior

3


3
a

2


2a

1


1

0


0

2


1

2


0

3


3

2


2

2


2

2


1/HT

1


1

0


0
316      Nonbearing walls and
partitions Exterior
See Table 602
317      Nonbearing walls and
partitions Interior
d

0

0

0

0

0

0

0

0

0
See
Section

2304.1

1.2

0

0
318      Floor construction and
associated secondary

members (see Section

202)

2

2

1

0

1

0

2

2

2

HT

1

0
319      Roof construction and
associated secondary

members (see Section

202)
11/
2 b

1b, c1b, c0c1b, c011/211HT1b, c0
320     
For SI: 1 foot = 304.8 mm.
321          a. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls
322     are permitted to be reduced by 1 hour where supporting a roof only.

323          b. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural
324     members in roof construction shall not be required, including protection of primary structural
325     frame members, roof framing and decking where every part of the roof construction is 20 feet
326     or more above any floor immediately below. Fire-retardant-treated wood members shall be
327     allowed to be used for such unprotected members.
328          c. In all occupancies, heavy timber complying with Section 2304.11 shall be allowed
329     where a 1-hour or less fire-resistance rating is required.
330          d. Not less than the fire-resistance rating required by other sections of this code.
331          e. Not less than the fire-resistance rating based on fire separation distance (see Table
332     602).
333          f. Not less than the fire-resistance rating as referenced in Section 704.10."
334          (2) In IBC, Table 602 is deleted and replaced with the following:
335     "TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
336     BASED ON FIRE SEPARATION DISTANCE a, d, g

337      Fire Separation
Distance = X

(feet)
TYPE OF
CONSTRUCTI

ON
OCCUPANC
Y GROUP He
OCCUPANCY
GROUP F-1, M,

S-1f
OCCUPANCY
GROUP A, B,

F-2, I, Ri, S-2,

Uh
338      < 5bAll321
339      5 ≤ X < 10IA, IVA
Others
3
2
2
1
11
340      10 ≤ X < 30IA, IB, IVA,
IVB

IIB, VB

Others
2
1

1
1
0

1
1c
0

1
c
341      X ≥ 30All000
342     
For SI: 1 foot = 304.8 mm.

343          a. Load-bearing exterior walls shall also comply with the fire-resistance rating
344     requirements of Table 601.
345          b. See Section 706.1.1 for party walls.
346          c. Open parking garages complying with Section 406 shall not be required to have a
347     fire-resistance rating.
348          d. The fire-resistance rating of an exterior wall is determined based upon the fire
349     separation distance of the exterior wall and the story in which the wall is located.
350          e. For special requirements for Group H occupancies, see Section 415.6.
351          f. For special requirements for Group S aircraft hangars, see Section 412.3.1.
352          g. Where Table 705.8 permits nonbearing exterior walls with unlimited area of
353     unprotected openings, the required fire-resistance rating for the exterior walls is 0 hours.
354          h. For a building containing only a Group U occupancy private garage or carport, the
355     exterior wall shall not be required to have a fire-resistance rating where the fire separation
356     distance is 5 feet (1523 mm) or greater.
357          i. For a Group R-3 building of Type II-B or Type V-B construction, the exterior wall
358     shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet
359     (1523 mm) or greater."
360          (3) In IBC, Section 602.4 is deleted and replaced with the following: "602.4 Type IV.
361     Type IV construction is that type of construction in which the building elements are mass
362     timber or non-combustible materials and have fire-resistance ratings in accordance with Table
363     601. Mass timber elements shall meet the fire-resistance rating requirements of this section
364     based on either the fire-resistance rating of the non-combustible protection, the mass timber, or
365     a combination of both and shall be determined in accordance with Section 703.2 or 703.3. The
366     minimum dimensions and permitted materials for building elements shall comply with the
367     provisions of this section and Section 2304.11. Mass timber elements of Types IV-A, IV-B and
368     IV-C construction shall be protected with non-combustible protection applied directly to the
369     mass timber in accordance with Sections 602.4.1 through 602.4.3. The time assigned to the
370     non-combustible protection shall be determined in accordance with Section 703.8 and comply

371     with Section 722.7.
372          Cross-laminated timber shall be labeled as conforming to PRG 320-18 as referenced in
373     Section 2303.1.4.
374          Exterior load-bearing walls and nonload-bearing walls shall be mass timber
375     construction, or shall be of non-combustible construction.
376          Exception: Exterior load-bearing walls and nonload-bearing walls of Type IV-HT
377     Construction in accordance with Section 602.4.4.
378          The interior building elements, including nonload-bearing walls and partitions, shall be
379     of mass timber construction or of non-combustible construction.
380          Exception: Interior building elements and nonload-bearing walls and partitions of Type
381     IV-HT Construction in accordance with Section 602.4.4.
382          Combustible concealed spaces are not permitted except as otherwise indicated in
383     Sections 602.4.1 through 602.4.4. Combustible stud spaces within light frame walls of Type
384     IV-HT construction shall not be considered concealed spaces, but shall comply with Section
385     718.
386          In buildings of Type IV-A, B, and C, construction with an occupied floor located more
387     than 75 feet above the lowest level of fire department access, up to and including 12 stories or
388     180 feet above grade plane, mass timber interior exit and elevator hoistway enclosures shall be
389     protected in accordance with Section 602.4.1.2. In buildings greater than 12 stories or 180 feet
390     above grade plane, interior exit and elevator hoistway enclosures shall be constructed of
391     non-combustible materials."
392          (4) In IBC, Section 602.4.1 is deleted and replaced with the following: "602.4.1 Type
393     IV-A. Building elements in Type IV-A construction shall be protected in accordance with
394     Sections 602.4.1.1 through 602.4.1.6. The required fire-resistance rating of non-combustible
395     elements and protected mass timber elements shall be determined in accordance with Section
396     703.2 or Section 703.3."
397          (5) In IBC, Section 602, a new section is added as follows: "602.4.1.1 Exterior
398     Protection. The outside face of exterior walls of mass timber construction shall be protected

399     with non-combustible protection with a minimum assigned time of 40 minutes as determined
400     in Section 722.7.1. All components of the exterior wall covering shall be on non-combustible
401     material except water resistive barriers having a peak heat release rate of less than 150 kW/m2,
402     a total heat release of less than 20 MJ/m2 and an effective heat of combustion of less than 18
403     MJ/kg as determined in accordance with ASTM E1354 and having a flame spread index of 25
404     or less and a smoke-developed index of 450 or less as determined in accordance with ASTM
405     E84 or UL723. The ASTM E1354 test shall be conducted on specimens at the thickness
406     intended for use, in the horizontal orientation and at an incident radiant heat flux of 50
407     kW/m2."
408          (6) In IBC, Section 602, a new section is added as follows: "602.4.1.2 Interior
409     Protection. Interior faces of all mass timber elements, including the inside faces of exterior
410     mass timber walls and mass timber roofs, shall be protected with materials complying with
411     Section 703.5."
412          (7) In IBC, Section 602, a new section is added as follows: "602.4.1.2.1 Protection
413     Time. Non-combustible protection shall contribute a time equal to or greater than times
414     assigned in Table 722.7.1(1), but not less than 80 minutes. The use of materials and their
415     respective protection contributions listed in Table 722.7.1(2) shall be permitted to be used for
416     compliance with Section 722.7.1."
417          (8) In IBC, Section 602, a new section is added as follows: "602.4.1.3 Floors. The floor
418     assembly shall contain a non-combustible material not less than one inch in thickness above the
419     mass timber. Floor finishes in accordance with Section 804 shall be permitted on top of the
420     non-combustible material. The underside of floor assemblies shall be protected in accordance
421     with Section 602.4.1.2."
422          (9) In IBC, Section 602, a new section is added as follows: "602.4.1.4 Roofs. The
423     interior surfaces of roof assemblies shall be protected in accordance with Section 602.4.1.2.
424     Roof coverings in accordance with Chapter 15 shall be permitted on the outside surface of the
425     roof assembly."
426          (10) In IBC, Section 602, a new section is added as follows: "602.4.1.5 Concealed

427     spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire
428     protection, or plumbing materials and equipment permitted in plenums in accordance with
429     Section 602 of the IMC, and shall comply with all applicable provisions of Section 718.
430     Combustible construction forming concealed spaces shall be protected in accordance with
431     Section 602.4.1.2."
432          (11) In IBC, Section 602, a new section is added as follows: "602.4.1.6 Shafts. Shafts
433     shall be permitted in accordance with Sections 713 and 718. Both the shaft side and room side
434     of mass timber elements shall be protected in accordance with Section 602.4.1.2."
435          (12) In IBC, Section 602.4.2 is deleted and replaced with the following: "602.4.2 Type
436     IV-B. Building elements in Type IV-B construction shall be protected in accordance with
437     Sections 602.4.2.1 through 602.4.2.6. The required fire resistance rating of non-combustible
438     elements or mass timber elements shall be determined in accordance with Section 703.2 or
439     Section 703.3."
440          (13) In IBC, Section 602, a new section is added as follows: "602.4.2.1 Exterior
441     protection. The outside face of exterior walls of mass timber construction shall be protected
442     with non-combustible protection with a minimum assigned time of 40 minutes as determined
443     in Section 722.7.1. All components of the exterior wall covering shall be of non-combustible
444     material except water resistive barriers having a peak heat release rate of less than 150 kW/m2,
445     a total heat release of less than 20 MJ/m2 and an effective heat of combustion of less than
446     18MJ/kg as determined in accordance with ASTM E1354, and having a flame spread index of
447     25 or less and a smoke-developed index of 450 or less as determined in accordance with
448     ASTM E84 or UL 723. The ASTM E1354 test shall be conducted on specimens at the
449     thickness intended for use, in the horizontal orientation and at an incident radiant heat flux of
450     50 kW/m2."
451          (14) In IBC, Section 602, a new section is added as follows: "602.4.2.2 Interior
452     protection. Interior faces of all mass timber elements, including the inside face of exterior mass
453     timber walls and mass timber roofs, shall be protected, as required by this section, with
454     materials complying with Section 703.5."

455          (15) In IBC, Section 602, a new section is added as follows: "602.4.2.2.1 Protection
456     time. Non-combustible protection shall contribute a time equal to or greater than times
457     assigned in Table 722.7.1(1), but not less than 80 minutes. The use of materials and their
458     respective protection contributions listed in Table 722.7.1(2) shall be permitted to be used for
459     compliance with Section 722.7.1."
460          (16) In IBC, Section 602, a new section is added as follows: "602.4.2.2.2 Protected
461     area. All interior faces of all mass timber elements shall be protected in accordance with
462     Section 602.4.2.2.1, including the inside face of exterior mass timber walls and mass timber
463     roofs.
464          Exceptions: Unprotected portions of mass timber ceilings and walls complying with
465     Section 602.4.2.2.4 and the following:
466          1. Unprotected portions of mass timber:
467          (a) ceilings, including attached beams, shall be permitted and shall be limited to an
468     area equal to 20% of the floor area in any dwelling unit or fire area;
469          (b) walls, including attached columns, shall be permitted and shall be limited to an area
470     equal to 40% of the floor area in any dwelling unit or fire area; or
471          (c) walls and ceilings, including attached columns and beams, in any dwelling unit or
472     fire area shall be permitted in accordance with Section 602.4.2.2.3.
473          2. Mass timber columns and beams which are not an integral portion of walls or
474     ceilings, respectively, shall be permitted to be unprotected without restriction of either
475     aggregate area or separation from one another."
476          (17) In IBC, Section 602, a new section is added as follows: "602.4.2.2.3 Mixed
477     unprotected areas. In each dwelling unit or fire area, where both portions of ceilings and
478     portions of walls are unprotected, the total allowable unprotected area shall be determined in
479     accordance with Equation 6-1.
480          (Utc/Ua c) + (Utw/Ua w) 1 (Equation 6-1) where:
481          Utc = Total unprotected mass timber ceiling areas
482          Ua c = Allowable unprotected mass timber ceiling area conforming to Section      

483               602.4.2.2.2, Exception 1
484          Utw = Total unprotected mass timber wall areas
485          Ua w = Allowable unprotected mass timber wall area conforming to Section      
486               602.4.2.2.2, Exception 2."
487          (18) In IBC, Section 602, a new section is added as follows: "602.4.2.2.4 Separation
488     distance between unprotected mass timber elements. In each dwelling unit or fire area,
489     unprotected portions of mass timber walls and ceilings shall be not less than 15 feet from
490     unprotected portions of other walls and ceilings, measured horizontally along the ceiling and
491     from other unprotected portions of walls measured horizontally along the floor."
492          (19) In IBC, Section 602, a new section is added as follows: "602.4.2.3 Floors. The
493     floor assembly shall contain a non-combustible material not less than one inch in thickness
494     above the mass timber. Floor finishes in accordance with Section 804 shall be permitted on top
495     of the non-combustible material. The underside of floor assemblies shall be protected in
496     accordance with Section 602.4.1.2."
497          (20) In IBC, Section 602, a new section is added as follows: "602.4.2.4 Roofs. The
498     interior surfaces of roof assemblies shall be protected in accordance with Section 602.4.2.2
499     except, in non-occupiable spaces, they shall be treated as a concealed space with no portion left
500     unprotected. Roof coverings in accordance with Chapter 15 shall be permitted on the outside
501     surface of the roof assembly."
502          (21) In IBC, Section 602, a new section is added as follows: "602.4.2.5 Concealed
503     spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire
504     protection, or plumbing materials and equipment permitted in plenums in accordance with
505     Section 602 of the IMC, and shall comply with all applicable provisions of Section 718.
506     Combustible construction forming concealed spaces shall be protected in accordance with
507     Section 602.4.1.2."
508          (22) In IBC, Section 602, a new section is added as follows: "602.4.2.6 Shafts. Shafts
509     shall be permitted in accordance with Section 713 and Section 718. Both the shaft side and
510     room side of mass timber elements shall be protected in accordance with Section 602.4.1.2."

511          (23) In IBC, Section 602.4.3 is deleted and replaced with the following: "602.4.3 Type
512     IV-C. Building elements in Type IV-C construction shall be protected in accordance with
513     Sections 602.4.3.1 through 602.4.3.6. The required fire-resistance rating of building elements
514     shall be determined in accordance with Section 703.2 or Section 703.3."
515          (24) In IBC, Section 602, a new section is added as follows: "602.4.3.1 Exterior
516     Protection. The exterior side of walls of combustible construction shall be protected with
517     non-combustible protection with a minimum assigned time of 40 minutes as determined in
518     Section 722.7.1. All components of the exterior wall covering shall be of non-combustible
519     material except water resistive barriers having a peak heat release rate of less than 150 kW/m2,
520     a total heat release of less than 20 MJ/m2 and an effective heat of combustion of less than
521     18MJ/kg as determined in accordance with ASTM E1354 and having a flame spread index of
522     25 or less and a smoke-developed index of 450 or less as determined in accordance with
523     ASTM E84 or UL723. The ASTM E1354 test shall be conducted on specimens at the thickness
524     intended for use, in the horizontal orientation and at an incident radiant heat flux of 50
525     kW/m2."
526          (25) In IBC, Section 602, a new section is added as follows: "602.4.3.2 Interior
527     protection. Mass timber elements are permitted to be unprotected."
528          (26) In IBC, Section 602, a new section is added as follows: "602.4.3.3 Floors. Floor
529     finishes in accordance with Section 804 shall be permitted on top of the floor construction."
530          (27) In IBC, Section 602, a new section is added as follows: "602.4.3.4 Roofs. Roof
531     coverings in accordance with Chapter 15 shall be permitted on the outside surface of the roof
532     assembly."
533          (28) In IBC, Section 602, a new section is added as follows: "602.4.3.5 Concealed
534     spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire
535     protection, or plumbing materials and equipment permitted in plenums in accordance with
536     Section 602 of the IMC, and shall comply with all applicable provisions of Section 718.
537     Combustible construction forming concealed spaces shall be protected with non-combustible
538     protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1."

539          (29) In IBC, Section 602, a new section is added as follows: "602.4.3.6 Shafts. Shafts
540     shall be permitted in accordance with Section 713 and Section 718. Shafts and elevator
541     hoistway and interior exit stairway enclosures shall be protected with non-combustible
542     protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1, on
543     both the inside of the shaft and the outside of the shaft."
544          (30) In IBC, Section 602, a new section is added as follows: "602.4.4 Type IV-HT.
545     Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior
546     walls are of non-combustible materials and the interior building elements are of solid wood,
547     laminated heavy timber or structural composite lumber (SCL), without concealed spaces. The
548     minimum dimensions for permitted materials including solid timber, glued-laminated timber,
549     structural composite lumber (SCL) and cross laminated timber (CLT) and details of Type IV
550     construction shall comply with the provisions of this section and Section 2304.11. Exterior
551     walls complying with Section 602.4.4.1 or 602.4.4.2 shall be permitted. Interior walls and
552     partitions not less than one-hour fire-resistance rating or heavy timber conforming with Section
553     2304.11.2.2 shall be permitted."
554          (31) In IBC, Section 602, a new section is added as follows: "602.4.4.1
555     Fire-retardant-treated wood in exterior walls. Fire-retardant-treated wood framing and
556     sheathing complying with Section 2303.2 shall be permitted within exterior wall assemblies
557     not less than 6 inches (152 mm) in thickness with a two-hour rating or less."
558          (32) In IBC, Section 602, a new section is added as follows: "602.4.4.2
559     Cross-laminated timber in exterior walls. Cross-laminated timber complying with Section
560     2303.1.4 shall be permitted within exterior wall assemblies not less than 6 inches (152 mm) in
561     thickness with a two-hour rating or less, provided the exterior surface of the cross-laminated
562     timber is protected by one the following:
563          1. fire-retardant-treated wood sheathing complying with Section 2303.2 and not less
564     than 15/32 inch (12 mm) thick;
565          2. gypsum board not less than 1/2 inch (12.7 mm) thick; or
566          3. a non-combustible material."

567          (33) In IBC, Section 602, a new section is added as follows: "602.4.4.3 Exterior
568     structural members. Where a horizontal separation of 20 feet (6096 mm) or more is provided,
569     wood columns and arches conforming to heavy timber sizes complying with Section 2304.11
570     shall be permitted to be used externally."
571          Section 9. Section 15A-2a-204 is enacted to read:
572          15A-2a-204. Amendments to Chapter 7 of IBC.
573          (1) In IBC, Section 703, a new section is added as follows: "703.8 Determination of
574     non-combustible protection time contribution. The time, in minutes, contributed to the
575     fire-resistance rating by the non-combustible protection of mass timber building elements,
576     components, or assemblies, shall be established through a comparison of assemblies tested
577     using procedures set forth in ASTM E119 or UL263. The test assemblies shall be identical in
578     construction, loading, and materials, other than the non-combustible protection. The two test
579     assemblies shall be tested to the same criteria of structural failure.
580          (a) Test Assembly 1 shall be without protection.
581          (b) Test Assembly 2 shall include the representative non-combustible protection. The
582     protection shall be fully defined in terms of configuration details, attachment details, joint
583     sealing details, accessories and all other relevant details.
584          The non-combustible protection time contribution shall be determined by subtracting
585     the fire-resistance time, in minutes, of Test Assembly 1 from the fire-resistance time, in
586     minutes, of Test Assembly 2."
587          (2) In IBC, Section 703, a new section is added as follows: "703.9 Sealing of adjacent
588     mass timber elements. In buildings of Type IV-A, IV-B, and IV-C construction, sealant or
589     adhesive shall be provided to resist the passage of air in the following locations:
590          1. At abutting edges and intersections of mass timber building elements required to be
591     fire-resistance-rated.
592          2. At abutting intersections of mass timber building elements and building elements of
593     other materials where both are required to be fire-resistance-rated.
594          Sealants shall meet the requirements of ASTM C920. Adhesives shall meet the

595     requirements of ASTM D3498.
596          Exception: Sealants or adhesives need not be provided where they are not a required
597     component of a tested fire-resistance-rated assembly."
598          (3) In IBC, Section 718.2.1 is deleted and replaced with the following: "718.2.1
599     Fireblocking materials. Fireblocking shall consist of the following materials:
600          1. Two-inch (51 mm) nominal lumber.
601          2. Two thicknesses of 1-inch (25 mm) nominal lumber with broken lap joints.
602          3. One thickness of 0.719-inch (18.3 mm) wood structural panels with joints backed by
603     0.719-inch (18.3 mm) wood structural panels.
604          4. One thickness of 0.75-inch (19.1 mm) particleboard with joints backed by 0.75-inch
605     (19 mm) particleboard.
606          5. 1/2 inch (12.7 mm) gypsum board.
607          6. 1/4 inch (6.4 mm) cement-based millboard.
608          7. Batts or blankets of mineral wool, mineral fiber or other approved materials installed
609     in such a manner as to be securely retained in place.
610          8. Cellulose insulation installed as tested for the specific application.
611          9. Mass timber complying with Section 2304.11."
612          (4) In IBC, Section 722, a new section is added as follows: "722.7 Fire-Resistance
613     rating of mass timber. The required fire resistance of mass timber elements in Section 602.4
614     shall be determined in accordance with Section 703.2 or Section 703.3. The fire-resistance
615     rating of building elements shall be as required in Tables 601 and 602 and as specified
616     elsewhere in this code. The fire-resistance rating of the mass timber elements shall consist of
617     the fire-resistance of the unprotected element added to the protection time of the
618     non-combustible protection."
619          (5) In IBC, Section 722, a new section is added as follows: "722.7.1 Minimum required
620     protection. Where required by Sections 602.4.1 through 602.4.3, non-combustible protection
621     shall be provided for mass timber building elements in accordance with Table 722.7.1(1). The
622     rating, in minutes, contributed by the non-combustible protection of mass timber building

623     elements, components, or assemblies, shall be established in accordance with Section 703.8.
624     The protection contributions indicated in Table 722.7.1(2) and Section 722.7.2 shall be deemed
625     to comply with this requirement when installed and fastened in accordance with Section
626     722.7.2."
627          (6) In IBC, Section 722, a new table is added as follows: "TABLE 722.7.1(1)
628          PROTECTION REQUIRED FROM NON-COMBUSTIBLE COVERING MATERIAL
629      Required Fire Resistance Rating of
Building Element per Tables 601 and 602

(hours)
Minimum Protection Required from
Non-combustible
630      140
631      280
632      3 or more120"
633          (7) In IBC, Section 722, a new table is added as follows: "TABLE 722.7.1(2)
634          PROTECTION PROVIDED BY NON-COMBUSTIBLE COVERING MATERIAL
635      Non-combustible ProtectionProtection
(minutes)
636      1/2 inch Type X Gypsum
637      25
638      5 /8 inch Type X Gypsum
639      Board40"
640     
     (8) In IBC, Section 722, a new section is added as follows: "722.7.2 Installation of
641     gypsum board non-combustible protection. Gypsum board complying with Table 722.7.1(2)
642     shall be installed in accordance with this section."
643          (9) In IBC, Section 722, a new section is added as follows: "722.7.2.1 Interior surfaces.
644     Layers of Type X gypsum board serving as non-combustible protection for interior surfaces of
645     wall and ceiling assemblies determined in accordance with Table 722.7.1(1) shall be installed
646     in accordance with the following:

647          1. Each layer shall be attached with Type S drywall screws of sufficient length to
648     penetrate the mass timber at least 1 inch when driven flush with the paper surface of the
649     gypsum board.
650          Exception: The third layer, where determined necessary by Section 722.7, shall be
651     permitted to be attached with 1 inch #6 Type S drywall screws to furring channels in
652     accordance with ASTM C645.
653          2. Screws for attaching the base layer shall be 12 inches on center in both directions.
654          3. Screws for each layer after the base layer shall be 12 inches on center in both
655     directions and offset from the screws of the previous layers by 4 inches in both directions.
656          4. All panel edges of any layer shall be offset 18 inches from those of the previous
657     layer.
658          5. All panel edges shall be attached with screws sized and offset as in items 1 through
659     4 above and placed at least 1 inch but not more than 2 inches from the panel edge.
660          6. All panels installed at wall-to-ceiling intersections shall be installed such that ceiling
661     panels are installed first and the wall panels are installed after the ceiling panel has been
662     installed and is fitted tight to the ceiling panel. Where multiple layers are required, each layer
663     shall repeat this process.
664          7. All panels installed at a wall-to-wall intersection shall be installed such that the
665     panels covering an exterior wall or a wall with a greater fire resistance rating shall be installed
666     first and the panels covering the other wall shall be fitted tight to the panel covering the first
667     wall. Where multiple layers are required, each layer shall repeat this process.
668          8. Panel edges of the face layer shall be taped and finished with joint compound.
669     Fastener heads shall be covered with joint compound.
670          9. Panel edges protecting mass timber elements adjacent to unprotected mass timber
671     elements in accordance with Section 602.4.2.2 shall be covered with 1-1/4 inch metal corner
672     bead and finished with joint compound."
673          (10) In IBC, Section 722, a new section is added as follows: "722.7.2.2 Exterior
674     surfaces. Layers of Type X gypsum board serving as non-combustible protection for the outside

675     of the exterior heavy timber walls determined in accordance with Table 722.7.1(1) shall be
676     fastened 12 inches on center each way and 6 inches on center at all joints or ends. All panel
677     edges shall be attached with fasteners located at least 1 inch but not more than 2 inches from
678     the panel edge. Fasteners shall comply with one of the following:
679          1. Galvanized nails of minimum 12 guage with a 7/16 inch head of sufficient length to
680     penetrate the mass timber a minimum of 1 inch.
681          2. Screws which comply with ASTM C1002 (Type S, Type W, or Type G) of sufficient
682     length to penetrate the mass timber a minimum of 1 inch."
683          (11) In IBC, Section 1705, a new section is added as follows: "1705.19 Sealing of mass
684     timber. Periodic special inspections of sealants or adhesives shall be conducted where sealant
685     or adhesive required by Section 703.9 is applied to mass timber building elements as
686     designated in the approved construction documents."
687          (12) In IBC, Section 3102.3 is deleted and replaced with the following: "3102.3 Type
688     of construction. Non-combustible membrane structures shall be classified as Type IIB
689     construction. Non-combustible frame or cable-supported structures covered by an approved
690     membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction.
691     Heavy timber frame-supported structures covered by an approved membrane in accordance
692     with Section 3102.3.1 shall be classified as Type IV-HT construction. Other membrane
693     structures shall be classified as Type V construction.
694          Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses,
695     where occupancy by the general public is not authorized, and for aquaculture pond covers is
696     not required to meet the fire propagation performance criteria of Test Method 1 or Test Method
697     2, as appropriate, of NFPA 701."
698          (13) In IBC, Section 3102.6.1.1 is deleted and replaced with the following: "3102.6.1.1
699     Membrane. A membrane meeting the fire propagation performance criteria of Test Method 1 or
700     Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a
701     skylight on buildings of Type IIB, III, IV-HT and V construction, provided that the membrane
702     is not less than 20 feet (6096 mm) above any floor, balcony or gallery."

703          Section 10. Section 15A-2a-301 is enacted to read:
704     
Part 3. Statewide Amendments to International Fire Code

705          15A-2a-301. Amendments to Chapter 7 of IFC.
706          In IFC, Section 701.6 is deleted and replaced with the following: "701.6 Owner's
707     responsibility. The owner shall maintain an inventory of all required fire-resistance-rated
708     construction, construction installed to resist the passage of smoke and the construction included
709     in Sections 703 through 707 and Sections 602.4.1 and 602.4.2 of the International Building
710     Code. Such construction shall be visually inspected by the owner annually and properly
711     repaired, restored or replaced where damaged, altered, breached or penetrated. Records of
712     inspections and repairs shall be maintained. Where concealed, such elements shall not be
713     required to be visually inspected by the owner unless the concealed space is accessible by the
714     removal or movement of a panel, access door, ceiling tile or similar movable entry to the
715     space."
716          Section 11. Section 15A-2a-302 is enacted to read:
717          15A-2a-302. Amendments to Chapters 9 and 33 of IFC.
718          (1) In IFC, Section 914.3.1.2 is deleted and replaced with the following: "914.3.1.2
719     Water supply to required fire pumps. In all buildings that are more than 420 feet (128m) in
720     building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet
721     in building height, required fire pumps shall be supplied by connections to not fewer than two
722     water mains located in different streets. Separate supply piping shall be provided between the
723     connection and the pumps shall be sized to supply the flow and pressure required for the pumps
724     to operate.
725          Exception: Two connections to the same main shall be permitted provided that the main
726     is valved such that an interruption can be isolated so that the water supply will continue
727     without interruption through not fewer than one of the connections."
728          (2) In IFC, Section 3308, a new section is added as follows: "3308.9 Fire safety
729     requirements for buildings of Types IV-A, IV-B, and IV-C construction. Buildings of Types
730     IV-A, IV-B, and IV-C construction designed to be greater than six stories above grade plane

731     shall comply with the following requirements during construction unless otherwise approved
732     by the fire code official:
733          1. Standpipes shall be provided in accordance with Section 3313.
734          2. A water supply for fire department operations, as approved by the fire code official
735     and the fire chief.
736          3. Where building construction exceeds six stories above grade plane, at least one layer
737     of non-combustible protection where required by Section 602.4 of the International Building
738     Code shall be installed on all building elements more than 4 floor levels, including mezzanines,
739     below active mass timber construction before erecting additional floor levels.
740          Exception: Shafts and vertical exit enclosures shall not be considered a part of the
741     active mass timber construction.
742          4. Where building construction exceeds six stories above grade plane required exterior
743     wall coverings shall be installed on all floor levels more than 4 floor levels, including
744     mezzanines, below active mass timber construction before erecting additional floor level.
745          Exception: Shafts and vertical exit enclosures shall not be considered a part of the
746     active mass timber construction."
747          Section 12. Section 15A-2a-401 is enacted to read:
748     
Part 4. Reference Standards

749          15A-2a-401. Reference Standards.
750          ASTM
751          D3498-03(2011): Standard Specification for Adhesives for Field-Gluing Plywood to
752     Lumber Framing for Floor Systems
753          ASTM International
754          100 Barr Harbor Drive,
755          P.O. Box C700
756          West Conshohocken, PA 19428-2959