1     
BUILDING CONSTRUCTION AMENDMENTS

2     
2020 GENERAL SESSION

3     
STATE OF UTAH

4     
Chief Sponsor: Casey Snider

5     
Senate Sponsor: Curtis S. Bramble

6     

7     LONG TITLE
8     Committee Note:
9          The Business and Labor Interim Committee recommended this bill.
10               Legislative Vote:     12 voting for     0 voting against     8 absent
11     General Description:
12          This bill amends the State Construction and Fire Codes Act and enacts provisions
13     regarding the use of mass timber products.
14     Highlighted Provisions:
15          This bill:
16          ▸     amends the definition of the State Construction Code to include standards for the
17     use of mass timber products;
18          ▸     enacts building standards for the use of mass timber products for residential and
19     commercial building construction; and
20          ▸     makes technical and conforming changes.
21     Money Appropriated in this Bill:
22          None
23     Other Special Clauses:
24          None
25     Utah Code Sections Affected:
26     AMENDS:
27          15A-1-102, as enacted by Laws of Utah 2011, Chapter 14

28          15A-2-101, as enacted by Laws of Utah 2011, Chapter 14
29          15A-2-102, as last amended by Laws of Utah 2016, Chapter 249
30     ENACTS:
31          15A-2a-101, Utah Code Annotated 1953
32          15A-2a-102, Utah Code Annotated 1953
33          15A-2a-201, Utah Code Annotated 1953
34          15A-2a-202, Utah Code Annotated 1953
35          15A-2a-203, Utah Code Annotated 1953
36          15A-2a-204, Utah Code Annotated 1953
37          15A-2a-301, Utah Code Annotated 1953
38          15A-2a-302, Utah Code Annotated 1953
39          15A-2a-401, Utah Code Annotated 1953
40     

41     Be it enacted by the Legislature of the state of Utah:
42          Section 1. Section 15A-1-102 is amended to read:
43          15A-1-102. Definitions.
44          As used in this title:
45          (1) "Board" means the Utah Fire Prevention Board created in Section 53-7-203.
46          (2) "Division" means the Division of Occupational and Professional Licensing created
47     in Section 58-1-103, except as provided in:
48          (a) Part 4, State Fire Code Administration Act; and
49          (b) Chapter 5, State Fire Code Act.
50          (3) "State Construction Code" means the State Construction Code adopted by:
51          (a) Chapter 2, Adoption of State Construction Code;
52          (b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as
53     Part of State Construction Code;
54          [(b)] (c) Chapter 3, Statewide Amendments Incorporated as Part of State Construction
55     Code; [and]
56          [(c)] (d) Chapter 4, Local Amendments Incorporated as Part of State Construction
57     Code[.]; and
58          (e) Chapter 6, Additional Construction Requirements.

59          (4) "State Fire Code" means the State Fire Code adopted by Chapter 5, State Fire Code
60     Act.
61          (5) "Utah Code" means the Utah Code Annotated (1953), as amended.
62          Section 2. Section 15A-2-101 is amended to read:
63          15A-2-101. Title -- Adoption of code.
64          (1) This chapter is known as the "Adoption of State Construction Code."
65          (2) In accordance with Chapter 1, Part 2, State Construction Code Administration Act,
66     the Legislature repeals the State Construction Code in effect on July 1, 2010, and adopts the
67     following as the State Construction Code:
68          (a) this chapter;
69          (b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as
70     Part of State Construction Code;
71          [(b)] (c) Chapter 3, Statewide Amendments Incorporated as Part of State Construction
72     Code; [and]
73          [(c)] (d) Chapter 4, Local Amendments Incorporated as Part of State Construction
74     Code[.]; and
75          (e) Chapter 6, Additional Construction Requirements.
76          Section 3. Section 15A-2-102 is amended to read:
77          15A-2-102. Definitions.
78          As used in this chapter [and], Chapter 2a, Tall Wood Buildings of Mass Timber
79     Construction Incorporated as Part of State Construction Code, Chapter 3, Statewide
80     Amendments Incorporated as Part of State Construction Code, and Chapter 4, Local
81     Amendments Incorporated as Part of State Construction Code:
82          (1) "HUD Code" means the Federal Manufactured Housing Construction and Safety
83     Standards Act, as issued by the Department of Housing and Urban Development and published
84     in 24 C.F.R. Parts 3280 and 3282 (as revised April 1, 1990).
85          (2) "IBC" means the edition of the International Building Code adopted under Section
86     15A-2-103.
87          (3) "IEBC" means the edition of the International Existing Building Code adopted
88     under Section 15A-2-103.
89          (4) "IECC" means the edition of the International Energy Conservation Code adopted

90     under Section 15A-2-103.
91          (5) "IFGC" means the edition of the International Fuel Gas Code adopted under
92     Section 15A-2-103.
93          (6) "IMC" means the edition of the International Mechanical Code adopted under
94     Section 15A-2-103.
95          (7) "IPC" means the edition of the International Plumbing Code adopted under Section
96     15A-2-103.
97          (8) "IRC" means the edition of the International Residential Code adopted under
98     Section 15A-2-103.
99          (9) "NEC" means the edition of the National Electrical Code adopted under Section
100     15A-2-103.
101          (10) "UWUI" means the edition of the Utah Wildland Urban Interface Code adopted
102     under Section 15A-2-103.
103          Section 4. Section 15A-2a-101 is enacted to read:
104     
CHAPTER 2a. TALL WOOD BUILDINGS OF MASS TIMBER CONSTRUCTION

105     
INCORPORATED AS PART OF STATE CONSTRUCTION CODE

106     
Part 1. General Provisions

107          15A-2a-101. Title.
108          (1) This chapter is known as "Tall Wood Buildings of Mass Timber Construction
109     Incorporated as Part of State Construction Code."
110          (2) This chapter establishes building standards for the use of mass timber products in
111     residential and commercial building construction and is applicable statewide.
112          (3) Where this chapter replaces a section of the IBC that Chapter 3, Statewide
113     Amendments Incorporated as Part of State Construction Code, or Chapter 4, Local
114     Amendments Incorporated as Part of State Construction Code, amends, the amendment in
115     Chapter 3 or 4 shall apply to the IBC replacement in this chapter.
116          Section 5. Section 15A-2a-102 is enacted to read:
117          15A-2a-102. Definitions.
118          As used in this chapter:
119          (1) "Mass timber" means a structural element of Type IV construction primarily of
120     solid, built-up, panelized or engineered wood products that meet minimum cross section

121     dimensions of Type IV construction.
122          (2) "Non-combustible protection" (for mass timber) means non-combustible material in
123     accordance with IBC Section 703.5, designed to increase the fire-resistance rating and delay the
124     combustion of mass timber.
125          (3) "Wall, load-bearing" means any wall meeting either of the following classifications:
126          (a) any metal or wood stud wall that supports more than 100 pounds per linear foot
127     (1459 N/m) of vertical load in addition to its own weight; or
128          (b) any masonry or concrete, or mass timber wall that supports more than 200 pounds
129     per linear foot (2919 N/m) of vertical load in addition to its own weight.
130          Section 6. Section 15A-2a-201 is enacted to read:
131     
Part 2. Statewide Amendments to International Building Code

132          15A-2a-201. Amendments to Chapter 4 of IBC.
133          In IBC, Section 403.3.2, is deleted and replaced with the following: "403.3.3 Water
134     supply to required fire pumps. In all buildings that are more than 420 feet (128m) in building
135     height, and buildings of Type IV-A and IV-B construction that are more than 120 feet in
136     building height, required fire pumps shall be supplied by connections to not fewer than two
137     water mains located in different streets. Separate supply piping shall be provided between each
138     connection to the water main and the pumps. Each connection and the supply piping between
139     the connection and the pumps shall be sized to supply the flow and pressure required for the
140     pumps to operate.
141          Exception: Two connections to the same main shall be permitted provided that the main
142     is valved such that an interruption can be isolated so that the water supply will continue
143     without interruption through not fewer than one of the connections."
144          Section 7. Section 15A-2a-202 is enacted to read:
145          15A-2a-202. Amendments to Chapter 5 of IBC.
146          (1) In IBC, Table 504.3, is deleted and replaced with the following: "Table 504.3
147     ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE
148      OCCUPANCY
CLASSIFICATION
TYPE OF CONSTRUCTION
SEE
FOOTNOTES
TYPE ITYPE
II
TYPE
III
TYPE IVTYPE V
ABABABABCHTAB
149     A, B, E, F, M, S, UNSbUL16065556555656565655040
SUL1808575857518012085857060
150      H-1, H-2, H-3, H-5NSc, dUL160655565551209065655040
S
151      H-4NSc, dUL16065556555656565655040
SUL1808575857514010085857060
152      I-1 Condition 1, I-3NSd, eUL16065556555656565655040
SUL1808575857518012085857060
153      I-1 Condition 2, I-2NSd, e, fUL16065556555656565655040
SUL18085
154      I-4NSd, gUL16065556555656565655040
SUL1808575857518012085857060
155      RhNSdUL16065556555656565655040
S13D606060606060606060605040
S13R606060606060606060606060
SUL1808575857518012085857060
156     For SI: 1 foot = 304.8 mm
157          UL = Unlimited; NS = Buildings not equipped throughout with an automatic sprinkler
158     system; S = Buildings equipped throughout with an automatic sprinkler system installed in
159     accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic
160     sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped
161     throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
162          a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
163          b. See Section 903.2 for the minimum thresholds for protection by an automatic
164     sprinkler system for specific occupancies.
165          c. New Group H occupancies are required to be protected by an automatic sprinkler
166     system in accordance with Section 903.2.5.
167          d. The NS value is only for use in evaluation of existing building area in accordance
168     with the IEBC.
169          e. New Group I-1 and I-3 occupancies are required to be protected by an automatic
170     sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies,
171     Condition 1, see Exception 1 of Section 903.2.6.
172          f. New and existing Group I-2 occupancies are required to be protected by an automatic
173     sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire      174      Code.

175          g. New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6.
176          h. New Group R occupancies are required to be protected by an automatic sprinkler
177     system in accordance with Section 903.2.8."
178          (2) In IBC, Table 504.4, "Allowable Number of Stories Above Grade Planea, b" delete
179     Type IV and replace it with the following, in relation to the occupancy classification and
180     footnotes as indicated:
181      OCCUPANCY CLASSIFICATIONTYPE OF CONSTRUCTION
SEE FOOTNOTESTYPE IV
ABCHT
182      A-1NS3333
S9644
183      A-2NS3333
S181264
184      A-3NS3333
S181264
185      A-4NS3333
S181264
186      A-5NS111UL
SULULULUL
187      BNS5555
S181296
188      ENS3333
S9644
189      F-1NS3334
S10755
190      F-2NS5555
S12866
191      H-1NSc, dNPNPNP1
S111
192      H-2NSc, d1112
S222
193      H-3NSc, d3334
S444
194      H-4NSc, d5555
S8766
195      H-5NSc, d2223
S333
196      I-1 Condition 1NSd, e4444
S10755
197      I-1 Condition 2NSd, e3334
S1064
198      I-2NSd, fNPNPNP1
S751
199      I-3NSd, e2222
S7533
200      I-4NSd, g3333
S9644
201      MNS4444
S12865
202     

R-1h

NSd4444
S13R
S181285
203      R-2hNSd4444
S13R
S181285
204      R-3hNSd4444
S13D
S13R
S181255
205      R-4hNSd4444
S13D
S13R
S181255
206      S-1NS4444
207      S10755
208      S-2NS4444
209      S12855
210      UNS4444
211      S9655
212     
     UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an
213     automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler
214     system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout
215     with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D =
216     Buildings equipped throughout with an automatic sprinkler system installed in accordance with
217     Section 903.3.1.3.
218          a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
219          b. See Section 903.2 for the minimum thresholds for protection by an automatic
220     sprinkler system for specific occupancies.
221          c. New Group H occupancies are required to be protected by an automatic sprinkler
222     system in accordance with Section 903.2.5.
223          d. The NS value is only for use in evaluation of existing building height in accordance
224     with the IEBC.

225          e. New Group I-1 and I-3 occupancies are required to be protected by an automatic
226     sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies,
227     Condition 1, see Exception 1 of Section 903.2.6.
228          f. New and existing Group I-2 occupancies are required to be protected by an automatic
229     sprinkler system in accordance with Sections 903.2.6 and 1103.5 of the International Fire
230     Code.
231          g. For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6.
232          h. New Group R occupancies are required to be protected by an automatic sprinkler
233     system in accordance with Section 903.2.8."
234          (3) In IBC, Table 506.2, "Allowable Area Factor (At = NS, S1, S13R, S13D or SM, as
235     applicable) in Square Feeta, b" delete Type IV and replace it with the following, in relation to the
236     occupancy classification and footnotes as indicated:
237      "OCCUPANCY
CLASSIFICATION
SEE
FOOTNOTES
TYPE OF CONSTRUCTION
TYPE IV
A
BCHT
238      A-1NS
45,000
30,00018,75015,000
S1
180,00
0
120,00075,00060,000
SM
135,00
0
90,00056,25045,000
239      A-2NS
45,000
30,00018,75015,000
S1
180,00
0
120,00075,00060,000
SM
135,00
0
90,00056,25045,000
240      A-3NS
45,000
30,00018,75015,000
S1
180,00
0
120,00075,00060,000
SM
135,00
0
90,00056,25045,000
241      A-4NS
45,000
30,00018,75015,000
S1
180,00
0
120,00075,00060,000
SM
135,00
0
90,00056,25045,000
242      A-5NS
UL
ULULUL
S1
SM
243      BNS
108,00
0
72,00045,00036,000
S1
432,00
0
288,000180,000144,000
SM
324,00
0
216,000135,000108,000
244      ENS
76,500
51,00031,87525,500
S1
306,00
0
204,000127,500102,000
SM
229,50
0
153,00095,62576,500
245      F-1NS
100,50
0
67,00041,87533,500
S1
402,00
0
268,000167,500134,000
SM
301,50
0
201,000125,625100,500
246      F-2NS
151,50
0
101,00063,12550,500
S1
606,00
0
404,000252,500202,000
SM
454,50
0
303,000189,375151,500
247      H-1NSc
10,500
10,50010,50010,500
S1
248      H-2NSc
10,500
10,50010,50010,500
S1
SM
249      H-3NSc
25,500
25,50025,50025,500
S1
SM
250      H-4NSc, d
72,000
54,00040,50036,000
S1
288,00
0
216,000162,000144,000
SM
216,00
0
162,000121,500108,000
251      H-5NSc, d
72,000
54,00040,50036,000
S1
288,00
0
216,000162,000144,000
SM
216,00
0
162,000121,500108,000
252      I-1NSd, e
54,000
36,00018,00018,000
S1
216,00
0
144,00072,00072,000
SM
162,00
0
108,00054,00054,000
253      I-2NSd, f
36,000
24,00012,00012,000
S1
144,00
0
96,00048,00048,000
SM
108,00
0
72,00036,00036,000
254      I-3NSd, e
36,000
24,00012,00012,000
S1
144,00
0
96,00048,00048,000
SM
108,00
0
72,00036,00036,000
255      I-4NSd, g
76,500
51,00025,50025,500
S1
306,00
0
204,000102,000102,000
SM
229,00
0
153,00076,50076,500
256      MNS
61,500
41,00025,62520,500
S1
246,00
0
164,000102,50082,000
SM
184,50
0
123,00076,87561,500
257      R-1hNSd
61,500
41,00025,62520,500
S13R
S1
246,00
0
164,000102,50082,000
SM
184,50
0
123,00076,87561,500
258      R-2hNSd
61,500
41,00025,62520,500
S13R
S1
246,00
0
164,000102,50082,000
SM
184,50
0
123,00076,87561,500
259      R-3hNSd
UL
ULULUL
S13D
S13R
S1
SM
260      R-4hNSd
61,500
41,00025,62520,500
S13D
S13R
S1
246,00
0
164,000102,50082,000
SM
184,50
0
123,00076,87561,500
261      S-1NS
76,500
51,00031,87525,500
S1
306,00
0
204,000127,500102,000
SM
229,50
0
153,00095,62576,500
262      S-2NS
115,50
0
77,00048,12538,500
S1
462,00
0
308,000192,500154,000
SM
346,50
0
308,000144,375115,500
263      UNSi
54,000
36,00022,50018,000
S1
216,00
0
144,00090,00072,000
SM
162,00
0
108,00067,50054,000"
264          For SI: 1 square foot = 0.0929 m2.
265          UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an
266     automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane
267     equipped throughout with an automatic sprinkler system installed in accordance with Section
268     903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an
269     automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings
270     equipped throughout with an automatic sprinkler system installed in accordance with Section
271     903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed
272     in accordance with Section 903.3.1.3.
273          a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
274          b. See Section 903.2 for the minimum thresholds for protection by an automatic
275     sprinkler system for specific occupancies.
276          c. New Group H occupancies are required to be protected by an automatic sprinkler
277     system in accordance with Section 903.2.5.
278          d. The NS value is only for use in evaluation of existing building area in accordance
279     with the IEBC.
280          e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler      281      system in accordance with Section 903.2.6. For new Group I-1 occupancies,

282     Condition 1, see Exception 1 of Section 903.2.6.
283          f. New and existing Group I-2 occupancies are required to be protected by an automatic
284     sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International
285     Fire Code.
286          g. For New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6.
287          h. New Group R occupancies are required to be protected by an automatic sprinkler
288     system in accordance with Section 903.2.8.
289          i. The maximum allowable area for a single-story nonsprinklered Group U greenhouse
290     is permitted to be 9,000 square feet, or the allowable area shall be permitted to comply with
291     Table C102.1 of Appendix C."
292          (4) In IBC, Section 508.4.4 is deleted and replaced with the following: "508.4.4
293     Separation. Individual occupancies shall be separated from adjacent occupancies in accordance
294     with Table 508.4."
295          (5) In IBC, Section 508.4.4.1 is deleted and replaced with the following: "508.4.4.1
296     Construction. Required separations shall be fire barriers constructed in accordance with Section
297     707 or horizontal assemblies constructed in accordance with Section 711, or both, so as to
298     completely separate adjacent occupancies. Mass timber elements serving as fire barriers or
299     horizontal assemblies to separate occupancies in Type IV-B or IV-C construction shall be
300     separated from the interior of the building with an approved thermal barrier consisting of a
301     minimum of 1/2 inch (12.7 mm) gypsum board or a material that is tested in accordance with
302     and meets the acceptance criteria of both the Temperature Transmission Fire Test and the
303     Integrity Fire Test of NFPA 275."
304          (6) In IBC, Section 509, a new section is added as follows: "509.4.1.1 Type IV-B and
305     IV-C construction. Where Table 509 specifies a fire-resistance-rated separation, mass timber
306     elements serving as fire barriers or a horizontal assembly in Type IV-B or IV-C construction
307     shall be separated from the interior of the incidental use with an approved thermal barrier
308     consisting of a minimum of 1/2 inch (12.7 mm) gypsum board or a material that is tested in
309     accordance with and meets the acceptance criteria of both the Temperature Transmission Fire
310     Test and the Integrity Fire Test of NFPA 275."
311          Section 8. Section 15A-2a-203 is enacted to read:
312          15A-2a-203. Amendments to Chapter 6 of IBC.

313          (1) In IBC, Table 601 is deleted and replaced with the following:
314          "TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING
315     ELEMENTS (HOURS)
316      BUILDING ELEMENTTYPE ITYPE IITYPE IIITYPE IVTYPE V
ABABABABCHTAB
317      Primary structural framef
(see Section 202)
3a, b2a, b1b01b03a2a2aHT1b0
318      Bearing walls
Exterior
e, f
Interior

3


3
a

2


2a

1


1

0


0

2


1

2


0

3


3

2


2

2


2

2


1/HT

1


1

0


0
319      Nonbearing walls and
partitions Exterior
See Table 602
0
320      Nonbearing walls and
partitions Interior
d

0

0

0

0

0

0

0

0

0
See
Section

2304.1

1.2

0

0
321      Floor construction and
associated secondary

members (see Section

202)

2

2

1

0

1

0

2

2

2

HT

1

0
322      Roof construction and
associated secondary

members (see Section

202)
11
/ b

2
1b, c1b, c0 c1b, c011/11HT1b, c0
323     
For SI: 1 foot = 304.8 mm.
324          a. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls
325     are permitted to be reduced by 1 hour where supporting a roof only.
326          b. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural
327     members in roof construction shall not be required, including protection of primary structural
328     frame members, roof framing and decking where every part of the roof construction is 20 feet
329     or more above any floor immediately below. Fire-retardant-treated wood members shall be
330     allowed to be used for such unprotected members.
331          c. In all occupancies, heavy timber complying with Section 2304.11 shall be allowed
332     where a 1-hour or less fire-resistance rating is required.

333          d. Not less than the fire-resistance rating required by other sections of this code.
334          e. Not less than the fire-resistance rating based on fire separation distance (see Table
335     602).
336          f. Not less than the fire-resistance rating as referenced in Section 704.10."
337          (2) In IBC, Table 602 is deleted and replaced with the following:
338     "TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
339     BASED ON FIRE SEPARATION DISTANCE a, d, g

340      Fire Separation
Distance = X

(feet)
TYPE OF
CONSTRUCTI

ON
OCCUPANC
Y GROUP He
OCCUPANCY
GROUP F-1, M,

S-1f
OCCUPANCY
GROUP A, B,

F-2, I, Ri, S-2,

Uh
341      < 5bAll321
342      5 ≤ X < 10IA, IVA
Others
3
2
2
1
11
343      10 ≤ X < 30IA, IB, IVA,
IVB

IIB, VB

Others
2
1

1
1
0

1
1c
0

1c
344      X ≥ 30All000
345     
For SI: 1 foot = 304.8 mm.
346          a. Load-bearing exterior walls shall also comply with the fire-resistance rating
347     requirements of Table 601.
348          b. See Section 706.1.1 for party walls.
349          c. Open parking garages complying with Section 406 shall not be required to have a
350     fire-resistance rating.
351          d. The fire-resistance rating of an exterior wall is determined based upon the fire
352     separation distance of the exterior wall and the story in which the wall is located.
353          e. For special requirements for Group H occupancies, see Section 415.6.
354          f. For special requirements for Group S aircraft hangars, see Section 412.3.1.
355          g. Where Table 705.8 permits nonbearing exterior walls with unlimited area of

356     unprotected openings, the required fire-resistance rating for the exterior walls is 0 hours.
357          h. For a building containing only a Group U occupancy private garage or carport, the
358     exterior wall shall not be required to have a fire-resistance rating where the fire separation
359     distance is 5 feet (1523 mm) or greater.
360          i. For a Group R-3 building of Type II-B or Type V-B construction, the exterior wall
361     shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet
362     (1523 mm) or greater."
363          (3) In IBC, Section 602.4 is deleted and replaced with the following: "602.4 Type IV.
364     Type IV construction is that type of construction in which the building elements are mass
365     timber or non-combustible materials and have fire-resistance ratings in accordance with Table
366     601. Mass timber elements shall meet the fire-resistance rating requirements of this section
367     based on either the fire-resistance rating of the non-combustible protection, the mass timber, or
368     a combination of both and shall be determined in accordance with Section 703.2 or 703.3. The
369     minimum dimensions and permitted materials for building elements shall comply with the
370     provisions of this section and Section 2304.11. Mass timber elements of Types IV-A, IV-B and
371     IV-C construction shall be protected with non-combustible protection applied directly to the
372     mass timber in accordance with Sections 602.4.1 through 602.4.3. The time assigned to the
373     non-combustible protection shall be determined in accordance with Section 703.8 and comply
374     with Section 722.7.
375          Cross-laminated timber shall be labeled as conforming to PRG 320-18 as referenced in
376     Section 2303.1.4.
377          Exterior load-bearing walls and nonload-bearing walls shall be mass timber
378     construction, or shall be of non-combustible construction.
379          Exception: Exterior load-bearing walls and nonload-bearing walls of Type IV-HT
380     Construction in accordance with Section 602.4.4.
381          The interior building elements, including nonload-bearing walls and partitions, shall be
382     of mass timber construction or of non-combustible construction.
383          Exception: Interior building elements and nonload-bearing walls and partitions of Type
384     IV-HT Construction in accordance with Section 602.4.4.
385          Combustible concealed spaces are not permitted except as otherwise indicated in
386     Sections 602.4.1 through 602.4.4. Combustible stud spaces within light frame walls of Type

387     IV-HT construction shall not be considered concealed spaces, but shall comply with Section
388     718.
389          In buildings of Type IV-A, B, and C, construction with an occupied floor located more
390     than 75 feet above the lowest level of fire department access, up to and including 12 stories or
391     180 feet above grade plane, mass timber interior exit and elevator hoistway enclosures shall be
392     protected in accordance with Section 602.4.1.2. In buildings greater than 12 stories or 180 feet
393     above grade plane, interior exit and elevator hoistway enclosures shall be constructed of
394     non-combustible materials."
395          (4) In IBC, Section 602.4.1 is deleted and replaced with the following: "602.4.1 Type
396     IV-A. Building elements in Type IV-A construction shall be protected in accordance with
397     Sections 602.4.1.1 through 602.4.1.6. The required fire-resistance rating of non-combustible
398     elements and protected mass timber elements shall be determined in accordance with Section
399     703.2 or Section 703.3."
400          (5) In IBC, Section 602, a new section is added as follows: "602.4.1.1 Exterior
401     Protection. The outside face of exterior walls of mass timber construction shall be protected
402     with non-combustible protection with a minimum assigned time of 40 minutes as determined
403     in Section 722.7.1. All components of the exterior wall covering shall be on non-combustible
404     material except water resistive barriers having a peak heat release rate of less than 150 kW/m2,
405     a total heat release of less than 20 MJ/m2 and an effective heat of combustion of less than 18
406     MJ/kg as determined in accordance with ASTM E1354 and having a flame spread index of 25
407     or less and a smoke-developed index of 450 or less as determined in accordance with ASTM
408     E84 or UL723. The ASTM E1354 test shall be conducted on specimens at the thickness
409     intended for use, in the horizontal orientation and at an incident radiant heat flux of 50
410     kW/m2."
411          (6) In IBC, Section 602, a new section is added as follows: "602.4.1.2 Interior
412     Protection. Interior faces of all mass timber elements, including the inside faces of exterior
413     mass timber walls and mass timber roofs, shall be protected with materials complying with
414     Section 703.5."
415          (7) In IBC, Section 602, a new section is added as follows: "602.4.1.2.1 Protection
416     Time. Non-combustible protection shall contribute a time equal to or greater than times
417     assigned in Table 722.7.1(1), but not less than 80 minutes. The use of materials and their

418     respective protection contributions listed in Table 722.7.1(2) shall be permitted to be used for
419     compliance with Section 722.7.1."
420          (8) In IBC, Section 602, a new section is added as follows: "602.4.1.3 Floors. The floor
421     assembly shall contain a non-combustible material not less than one inch in thickness above the
422     mass timber. Floor finishes in accordance with Section 804 shall be permitted on top of the
423     non-combustible material. The underside of floor assemblies shall be protected in accordance
424     with Section 602.4.1.2."
425          (9) In IBC, Section 602, a new section is added as follows: "602.4.1.4 Roofs. The
426     interior surfaces of roof assemblies shall be protected in accordance with Section 602.4.1.2.
427     Roof coverings in accordance with Chapter 15 shall be permitted on the outside surface of the
428     roof assembly."
429          (10) In IBC, Section 602, a new section is added as follows: "602.4.1.5 Concealed
430     spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire
431     protection, or plumbing materials and equipment permitted in plenums in accordance with
432     Section 602 of the IMC, and shall comply with all applicable provisions of Section 718.
433     Combustible construction forming concealed spaces shall be protected in accordance with
434     Section 602.4.1.2."
435          (11) In IBC, Section 602, a new section is added as follows: "602.4.1.6 Shafts. Shafts
436     shall be permitted in accordance with Sections 713 and 718. Both the shaft side and room side
437     of mass timber elements shall be protected in accordance with Section 602.4.1.2."
438          (12) In IBC, Section 602.4.2 is deleted and replaced with the following: "602.4.2 Type
439     IV-B. Building elements in Type IV-B construction shall be protected in accordance with
440     Sections 602.4.2.1 through 602.4.2.6. The required fire resistance rating of non-combustible
441     elements or mass timber elements shall be determined in accordance with Section 703.2 or
442     Section 703.3."
443          (13) In IBC, Section 602, a new section is added as follows: "602.4.2.1 Exterior
444     protection. The outside face of exterior walls of mass timber construction shall be protected
445     with non-combustible protection with a minimum assigned time of 40 minutes as determined
446     in Section 722.7.1. All components of the exterior wall covering shall be of non-combustible
447     material except water resistive barriers having a peak heat release rate of less than 150 kW/m2,
448     a total heat release of less than 20 MJ/m2 and an effective heat of combustion of less than

449     18MJ/kg as determined in accordance with ASTM E1354, and having a flame spread index of
450     25 or less and a smoke-developed index of 450 or less as determined in accordance with
451     ASTM E84 or UL 723. The ASTM E1354 test shall be conducted on specimens at the
452     thickness intended for use, in the horizontal orientation and at an incident radiant heat flux of
453     50 kW/m2."
454          (14) In IBC, Section 602, a new section is added as follows: "602.4.2.2 Interior
455     protection. Interior faces of all mass timber elements, including the inside face of exterior mass
456     timber walls and mass timber roofs, shall be protected, as required by this section, with
457     materials complying with Section 703.5."
458          (15) In IBC, Section 602, a new section is added as follows: "602.4.2.2.1 Protection
459     time. Non-combustible protection shall contribute a time equal to or greater than times
460     assigned in Table 722.7.1(1), but not less than 80 minutes. The use of materials and their
461     respective protection contributions listed in Table 722.7.1(2) shall be permitted to be used for
462     compliance with Section 722.7.1."
463          (16) In IBC, Section 602, a new section is added as follows: "602.4.2.2.2 Protected
464     area. All interior faces of all mass timber elements shall be protected in accordance with
465     Section 602.4.2.2.1, including the inside face of exterior mass timber walls and mass timber
466     roofs.
467          Exceptions: Unprotected portions of mass timber ceilings and walls complying with
468     Section 602.4.2.2.4 and the following:
469          1. Unprotected portions of mass timber:
470          (a) ceilings, including attached beams, shall be permitted and shall be limited to an
471     area equal to 20% of the floor area in any dwelling unit or fire area;
472          (b) walls, including attached columns, shall be permitted and shall be limited to an area
473     equal to 40% of the floor area in any dwelling unit or fire area; or
474          (c) walls and ceilings, including attached columns and beams, in any dwelling unit or
475     fire area shall be permitted in accordance with Section 602.4.2.2.3.
476          2. Mass timber columns and beams which are not an integral portion of walls or
477     ceilings, respectively, shall be permitted to be unprotected without restriction of either
478     aggregate area or separation from one another."
479          (17) In IBC, Section 602, a new section is added as follows: "602.4.2.2.3 Mixed

480     unprotected areas. In each dwelling unit or fire area, where both portions of ceilings and
481     portions of walls are unprotected, the total allowable unprotected area shall be determined in
482     accordance with Equation 6-1.
483          (Utc/Ua c) + (Utw/Ua w) 1 (Equation 6-1) where:
484          Utc = Total unprotected mass timber ceiling areas
485          Ua c = Allowable unprotected mass timber ceiling area conforming to Section      
486               602.4.2.2.2, Exception 1
487          Utw = Total unprotected mass timber wall areas
488          Ua w = Allowable unprotected mass timber wall area conforming to Section      
489               602.4.2.2.2, Exception 2."
490          (18) In IBC, Section 602, a new section is added as follows: "602.4.2.2.4 Separation
491     distance between unprotected mass timber elements. In each dwelling unit or fire area,
492     unprotected portions of mass timber walls and ceilings shall be not less than 15 feet from
493     unprotected portions of other walls and ceilings, measured horizontally along the ceiling and
494     from other unprotected portions of walls measured horizontally along the floor."
495          (19) In IBC, Section 602, a new section is added as follows: "602.4.2.3 Floors. The
496     floor assembly shall contain a non-combustible material not less than one inch in thickness
497     above the mass timber. Floor finishes in accordance with Section 804 shall be permitted on top
498     of the non-combustible material. The underside of floor assemblies shall be protected in
499     accordance with Section 602.4.1.2."
500          (20) In IBC, Section 602, a new section is added as follows: "602.4.2.4 Roofs. The
501     interior surfaces of roof assemblies shall be protected in accordance with Section 602.4.2.2
502     except, in non-occupiable spaces, they shall be treated as a concealed space with no portion left
503     unprotected. Roof coverings in accordance with Chapter 15 shall be permitted on the outside
504     surface of the roof assembly."
505          (21) In IBC, Section 602, a new section is added as follows: "602.4.2.5 Concealed
506     spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire
507     protection, or plumbing materials and equipment permitted in plenums in accordance with
508     Section 602 of the IMC, and shall comply with all applicable provisions of Section 718.
509     Combustible construction forming concealed spaces shall be protected in accordance with
510     Section 602.4.1.2."

511          (22) In IBC, Section 602, a new section is added as follows: "602.4.2.6 Shafts. Shafts
512     shall be permitted in accordance with Section 713 and Section 718. Both the shaft side and
513     room side of mass timber elements shall be protected in accordance with Section 602.4.1.2."
514          (23) In IBC, Section 602.4.3 is deleted and replaced with the following: "602.4.3 Type
515     IV-C. Building elements in Type IV-C construction shall be protected in accordance with
516     Sections 602.4.3.1 through 602.4.3.6. The required fire-resistance rating of building elements
517     shall be determined in accordance with Section 703.2 or Section 703.3."
518          (24) In IBC, Section 602, a new section is added as follows: "602.4.3.1 Exterior
519     Protection. The exterior side of walls of combustible construction shall be protected with
520     non-combustible protection with a minimum assigned time of 40 minutes as determined in
521     Section 722.7.1. All components of the exterior wall covering shall be of non-combustible
522     material except water resistive barriers having a peak heat release rate of less than 150 kW/m2,
523     a total heat release of less than 20 MJ/m2 and an effective heat of combustion of less than
524     18MJ/kg as determined in accordance with ASTM E1354 and having a flame spread index of
525     25 or less and a smoke-developed index of 450 or less as determined in accordance with
526     ASTM E84 or UL723. The ASTM E1354 test shall be conducted on specimens at the thickness
527     intended for use, in the horizontal orientation and at an incident radiant heat flux of 50
528     kW/m2."
529          (25) In IBC, Section 602, a new section is added as follows: "602.4.3.2 Interior
530     protection. Mass timber elements are permitted to be unprotected."
531          (26) In IBC, Section 602, a new section is added as follows: "602.4.3.3 Floors. Floor
532     finishes in accordance with Section 804 shall be permitted on top of the floor construction."
533          (27) In IBC, Section 602, a new section is added as follows: "602.4.3.4 Roofs. Roof
534     coverings in accordance with Chapter 15 shall be permitted on the outside surface of the roof
535     assembly."
536          (28) In IBC, Section 602, a new section is added as follows: "602.4.3.5 Concealed
537     spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire
538     protection, or plumbing materials and equipment permitted in plenums in accordance with
539     Section 602 of the IMC, and shall comply with all applicable provisions of Section 718.
540     Combustible construction forming concealed spaces shall be protected with non-combustible
541     protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1."

542          (29) In IBC, Section 602, a new section is added as follows: "602.4.3.6 Shafts. Shafts
543     shall be permitted in accordance with Section 713 and Section 718. Shafts and elevator
544     hoistway and interior exit stairway enclosures shall be protected with non-combustible
545     protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1, on
546     both the inside of the shaft and the outside of the shaft."
547          (30) In IBC, Section 602, a new section is added as follows: "602.4.4 Type IV-HT.
548     Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior
549     walls are of non-combustible materials and the interior building elements are of solid wood,
550     laminated heavy timber or structural composite lumber (SCL), without concealed spaces. The
551     minimum dimensions for permitted materials including solid timber, glued-laminated timber,
552     structural composite lumber (SCL) and cross laminated timber (CLT) and details of Type IV
553     construction shall comply with the provisions of this section and Section 2304.11. Exterior
554     walls complying with Section 602.4.4.1 or 602.4.4.2 shall be permitted. Interior walls and
555     partitions not less than one-hour fire-resistance rating or heavy timber conforming with Section
556     2304.11.2.2 shall be permitted."
557          (31) In IBC, Section 602, a new section is added as follows: "602.4.4.1
558     Fire-retardant-treated wood in exterior walls. Fire-retardant-treated wood framing and
559     sheathing complying with Section 2303.2 shall be permitted within exterior wall assemblies
560     not less than 6 inches (152 mm) in thickness with a two-hour rating or less."
561          (32) In IBC, Section 602, a new section is added as follows: "602.4.4.2
562     Cross-laminated timber in exterior walls. Cross-laminated timber complying with Section
563     2303.1.4 shall be permitted within exterior wall assemblies not less than 6 inches (152 mm) in
564     thickness with a two-hour rating or less, provided the exterior surface of the cross-laminated
565     timber is protected by one the following:
566          1. fire-retardant-treated wood sheathing complying with Section 2303.2 and not less
567     than 15/32 inch (12 mm) thick;
568          2. gypsum board not less than 1/2 inch (12.7 mm) thick; or
569          3. a non-combustible material."
570          (33) In IBC, Section 602, a new section is added as follows: "602.4.4.3 Exterior
571     structural members. Where a horizontal separation of 20 feet (6096 mm) or more is provided,
572     wood columns and arches conforming to heavy timber sizes complying with Section 2304.11

573     shall be permitted to be used externally."
574          Section 9. Section 15A-2a-204 is enacted to read:
575          15A-2a-204. Amendments to Chapter 7 of IBC.
576          (1) In IBC, Section 703, a new section is added as follows: "703.8 Determination of
577     non-combustible protection time contribution. The time, in minutes, contributed to the
578     fire-resistance rating by the non-combustible protection of mass timber building elements,
579     components, or assemblies, shall be established through a comparison of assemblies tested
580     using procedures set forth in ASTM E119 or UL263. The test assemblies shall be identical in
581     construction, loading, and materials, other than the non-combustible protection. The two test
582     assemblies shall be tested to the same criteria of structural failure.
583          (a) Test Assembly 1 shall be without protection.
584          (b) Test Assembly 2 shall include the representative non-combustible protection. The
585     protection shall be fully defined in terms of configuration details, attachment details, joint
586     sealing details, accessories and all other relevant details.
587          The non-combustible protection time contribution shall be determined by subtracting
588     the fire-resistance time, in minutes, of Test Assembly 1 from the fire-resistance time, in
589     minutes, of Test Assembly 2."
590          (2) In IBC, Section 703, a new section is added as follows: "703.9 Sealing of adjacent
591     mass timber elements. In buildings of Type IV-A, IV-B, and IV-C construction, sealant or
592     adhesive shall be provided to resist the passage of air in the following locations:
593          1. At abutting edges and intersections of mass timber building elements required to be
594     fire-resistance-rated.
595          2. At abutting intersections of mass timber building elements and building elements of
596     other materials where both are required to be fire-resistance-rated.
597          Sealants shall meet the requirements of ASTM C920. Adhesives shall meet the
598     requirements of ASTM D3498.
599          Exception: Sealants or adhesives need not be provided where they are not a required
600     component of a tested fire-resistance-rated assembly."
601          (3) In IBC, Section 718.2.1 is deleted and replaced with the following: "718.2.1
602     Fireblocking materials. Fireblocking shall consist of the following materials:
603          1. Two-inch (51 mm) nominal lumber.

604          2. Two thicknesses of 1-inch (25 mm) nominal lumber with broken lap joints.
605          3. One thickness of 0.719-inch (18.3 mm) wood structural panels with joints backed by
606     0.719-inch (18.3 mm) wood structural panels.
607          4. One thickness of 0.75-inch (19.1 mm) particleboard with joints backed by 0.75-inch
608     (19 mm) particleboard.
609          5. 1/2 inch (12.7 mm) gypsum board.
610          6. 1/4 inch (6.4 mm) cement-based millboard.
611          7. Batts or blankets of mineral wool, mineral fiber or other approved materials installed
612     in such a manner as to be securely retained in place.
613          8. Cellulose insulation installed as tested for the specific application.
614          9. Mass timber complying with Section 2304.11."
615          (4) In IBC, Section 722, a new section is added as follows: "722.7 Fire-Resistance
616     rating of mass timber. The required fire resistance of mass timber elements in Section 602.4
617     shall be determined in accordance with Section 703.2 or Section 703.3. The fire-resistance
618     rating of building elements shall be as required in Tables 601 and 602 and as specified
619     elsewhere in this code. The fire-resistance rating of the mass timber elements shall consist of
620     the fire-resistance of the unprotected element added to the protection time of the
621     non-combustible protection."
622          (5) In IBC, Section 722, a new section is added as follows: "722.7.1 Minimum required
623     protection. Where required by Sections 602.4.1 through 602.4.3, non-combustible protection
624     shall be provided for mass timber building elements in accordance with Table 722.7.1(1). The
625     rating, in minutes, contributed by the non-combustible protection of mass timber building
626     elements, components, or assemblies, shall be established in accordance with Section 703.8.
627     The protection contributions indicated in Table 722.7.1(2) and Section 722.7.2 shall be deemed
628     to comply with this requirement when installed and fastened in accordance with Section
629     722.7.2."
630          (6) In IBC, Section 722, a new table is added as follows: "TABLE 722.7.1(1)
631          PROTECTION REQUIRED FROM NON-COMBUSTIBLE COVERING MATERIAL
632      Required Fire Resistance Rating of
Building Element per Tables 601 and 602

(hours)
Minimum Protection Required from
Non-combustible
633      140
634      280
635      3 or more120"
636          (7) In IBC, Section 722, a new table is added as follows: "TABLE 722.7.1(2)
637          PROTECTION PROVIDED BY NON-COMBUSTIBLE COVERING MATERIAL
638      Non-combustible ProtectionProtection
(minutes)
639      1/2 inch Type X Gypsum
640      25
641      5 /8 inch Type X Gypsum
642      Board40"
643     
     (8) In IBC, Section 722, a new section is added as follows: "722.7.2 Installation of
644     gypsum board non-combustible protection. Gypsum board complying with Table 722.7.1(2)
645     shall be installed in accordance with this section."
646          (9) In IBC, Section 722, a new section is added as follows: "722.7.2.1 Interior surfaces.
647     Layers of Type X gypsum board serving as non-combustible protection for interior surfaces of
648     wall and ceiling assemblies determined in accordance with Table 722.7.1(1) shall be installed
649     in accordance with the following:
650          1. Each layer shall be attached with Type S drywall screws of sufficient length to
651     penetrate the mass timber at least 1 inch when driven flush with the paper surface of the
652     gypsum board.
653          Exception: The third layer, where determined necessary by Section 722.7, shall be
654     permitted to be attached with 1 inch #6 Type S drywall screws to furring channels in
655     accordance with ASTM C645.
656          2. Screws for attaching the base layer shall be 12 inches on center in both directions.
657          3. Screws for each layer after the base layer shall be 12 inches on center in both
658     directions and offset from the screws of the previous layers by 4 inches in both directions.
659          4. All panel edges of any layer shall be offset 18 inches from those of the previous
660     layer.
661          5. All panel edges shall be attached with screws sized and offset as in items 1 through

662     4 above and placed at least 1 inch but not more than 2 inches from the panel edge.
663          6. All panels installed at wall-to-ceiling intersections shall be installed such that ceiling
664     panels are installed first and the wall panels are installed after the ceiling panel has been
665     installed and is fitted tight to the ceiling panel. Where multiple layers are required, each layer
666     shall repeat this process.
667          7. All panels installed at a wall-to-wall intersection shall be installed such that the
668     panels covering an exterior wall or a wall with a greater fire resistance rating shall be installed
669     first and the panels covering the other wall shall be fitted tight to the panel covering the first
670     wall. Where multiple layers are required, each layer shall repeat this process.
671          8. Panel edges of the face layer shall be taped and finished with joint compound.
672     Fastener heads shall be covered with joint compound.
673          9. Panel edges protecting mass timber elements adjacent to unprotected mass timber
674     elements in accordance with Section 602.4.2.2 shall be covered with 1-1/4 inch metal corner
675     bead and finished with joint compound."
676          (10) In IBC, Section 722, a new section is added as follows: "722.7.2.2 Exterior
677     surfaces. Layers of Type X gypsum board serving as non-combustible protection for the outside
678     of the exterior heavy timber walls determined in accordance with Table 722.7.1(1) shall be
679     fastened 12 inches on center each way and 6 inches on center at all joints or ends. All panel
680     edges shall be attached with fasteners located at least 1 inch but not more than 2 inches from
681     the panel edge. Fasteners shall comply with one of the following:
682          1. Galvanized nails of minimum 12 guage with a 7/16 inch head of sufficient length to
683     penetrate the mass timber a minimum of 1 inch.
684          2. Screws which comply with ASTM C1002 (Type S, Type W, or Type G) of sufficient
685     length to penetrate the mass timber a minimum of 1 inch."
686          (11) In IBC, Section 1705, a new section is added as follows: "1705.19 Sealing of mass
687     timber. Periodic special inspections of sealants or adhesives shall be conducted where sealant
688     or adhesive required by Section 703.9 is applied to mass timber building elements as
689     designated in the approved construction documents."
690          (12) In IBC, Section 3102.3 is deleted and replaced with the following: "3102.3 Type
691     of construction. Non-combustible membrane structures shall be classified as Type IIB
692     construction. Non-combustible frame or cable-supported structures covered by an approved

693     membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction.
694     Heavy timber frame-supported structures covered by an approved membrane in accordance
695     with Section 3102.3.1 shall be classified as Type IV-HT construction. Other membrane
696     structures shall be classified as Type V construction.
697          Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses,
698     where occupancy by the general public is not authorized, and for aquaculture pond covers is
699     not required to meet the fire propagation performance criteria of Test Method 1 or Test Method
700     2, as appropriate, of NFPA 701."
701          (13) In IBC, Section 3102.6.1.1 is deleted and replaced with the following: "3102.6.1.1
702     Membrane. A membrane meeting the fire propagation performance criteria of Test Method 1 or
703     Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a
704     skylight on buildings of Type IIB, III, IV-HT and V construction, provided that the membrane
705     is not less than 20 feet (6096 mm) above any floor, balcony or gallery."
706          Section 10. Section 15A-2a-301 is enacted to read:
707     
Part 3. Statewide Amendments to International Fire Code

708          15A-2a-301. Amendments to Chapter 7 of IFC.
709          In IFC, Section 701.6 is deleted and replaced with the following: "701.6 Owner's
710     responsibility. The owner shall maintain an inventory of all required fire-resistance-rated
711     construction, construction installed to resist the passage of smoke and the construction included
712     in Sections 703 through 707 and Sections 602.4.1 and 602.4.2 of the International Building
713     Code. Such construction shall be visually inspected by the owner annually and properly
714     repaired, restored or replaced where damaged, altered, breached or penetrated. Records of
715     inspections and repairs shall be maintained. Where concealed, such elements shall not be
716     required to be visually inspected by the owner unless the concealed space is accessible by the
717     removal or movement of a panel, access door, ceiling tile or similar movable entry to the
718     space."
719          Section 11. Section 15A-2a-302 is enacted to read:
720          15A-2a-302. Amendments to Chapters 9 and 33 of IFC.
721          (1) In IFC, Section 914.3.1.2 is deleted and replaced with the following: "914.3.1.2
722     Water supply to required fire pumps. In all buildings that are more than 420 feet (128m) in
723     building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet

724     in building height, required fire pumps shall be supplied by connections to not fewer than two
725     water mains located in different streets. Separate supply piping shall be provided between the
726     connection and the pumps shall be sized to supply the flow and pressure required for the pumps
727     to operate.
728          Exception: Two connections to the same main shall be permitted provided that the main
729     is valved such that an interruption can be isolated so that the water supply will continue
730     without interruption through not fewer than one of the connections."
731          (2) In IFC, Section 3308, a new section is added as follows: "3308.9 Fire safety
732     requirements for buildings of Types IV-A, IV-B, and IV-C construction. Buildings of Types
733     IV-A, IV-B, and IV-C construction designed to be greater than six stories above grade plane
734     shall comply with the following requirements during construction unless otherwise approved
735     by the fire code official:
736          1. Standpipes shall be provided in accordance with Section 3313.
737          2. A water supply for fire department operations, as approved by the fire code official
738     and the fire chief.
739          3. Where building construction exceeds six stories above grade plane, at least one layer
740     of non-combustible protection where required by Section 602.4 of the International Building
741     Code shall be installed on all building elements more than 4 floor levels, including mezzanines,
742     below active mass timber construction before erecting additional floor levels.
743          Exception: Shafts and vertical exit enclosures shall not be considered a part of the
744     active mass timber construction.
745          4. Where building construction exceeds six stories above grade plane required exterior
746     wall coverings shall be installed on all floor levels more than 4 floor levels, including
747     mezzanines, below active mass timber construction before erecting additional floor level.
748          Exception: Shafts and vertical exit enclosures shall not be considered a part of the
749     active mass timber construction."
750          Section 12. Section 15A-2a-401 is enacted to read:
751     
Part 4. Reference Standards

752          15A-2a-401. Reference Standards.
753          ASTM
754          D3498-03(2011): Standard Specification for Adhesives for Field-Gluing Plywood to

755     Lumber Framing for Floor Systems
756          ASTM International
757          100 Barr Harbor Drive,
758          P.O. Box C700
759          West Conshohocken, PA 19428-2959