1     
STATE CONSTRUCTION AND FIRE CODES AMENDMENTS

2     
2023 GENERAL SESSION

3     
STATE OF UTAH

4     
Chief Sponsor: Thomas W. Peterson

5     
Senate Sponsor: Curtis S. Bramble

6     

7     LONG TITLE
8     General Description:
9          This bill repeals and amends construction and fire codes under Title 15A, State
10     Construction and Fire Codes Act.
11     Highlighted Provisions:
12          This bill:
13          ▸     repeals Tall Wood Buildings of Mass Timber Construction Incorporated as Part of
14     State Construction Code;
15          ▸     adopts the 2021 edition of the International Fire Code, with amendments; and
16          ▸     adopts and amends certain National Fire Protection Association codes and
17     standards.
18     Money Appropriated in this Bill:
19          None
20     Other Special Clauses:
21          None
22     Utah Code Sections Affected:
23     AMENDS:
24          15A-2-101, as last amended by Laws of Utah 2020, Chapter 43
25          15A-2-102, as last amended by Laws of Utah 2020, Chapters 43, 441
26          15A-2-104, as last amended by Laws of Utah 2016, Chapter 249
27          15A-5-103, as last amended by Laws of Utah 2019, First Special Session, Chapter 5

28          15A-5-202, as last amended by Laws of Utah 2022, Chapter 28
29          15A-5-202.5, as last amended by Laws of Utah 2020, Sixth Special Session, Chapter 4
30          15A-5-203, as last amended by Laws of Utah 2022, Chapter 350
31          15A-5-204, as last amended by Laws of Utah 2019, Chapter 103
32          15A-5-205, as last amended by Laws of Utah 2019, Chapter 103
33          15A-5-205.5, as last amended by Laws of Utah 2019, Chapter 103
34          15A-5-205.6, as enacted by Laws of Utah 2018, Chapter 228
35          15A-5-206, as last amended by Laws of Utah 2019, Chapter 103
36          15A-5-302, as last amended by Laws of Utah 2022, Chapter 28
37          15A-5-304, as last amended by Laws of Utah 2019, Chapter 103
38     REPEALS:
39          15A-2a-101, as enacted by Laws of Utah 2020, Chapter 43
40          15A-2a-102, as enacted by Laws of Utah 2020, Chapter 43
41          15A-2a-201, as enacted by Laws of Utah 2020, Chapter 43
42          15A-2a-202, as enacted by Laws of Utah 2020, Chapter 43
43          15A-2a-203, as enacted by Laws of Utah 2020, Chapter 43
44          15A-2a-204, as enacted by Laws of Utah 2020, Chapter 43
45          15A-2a-301, as enacted by Laws of Utah 2020, Chapter 43
46          15A-2a-302, as enacted by Laws of Utah 2020, Chapter 43
47          15A-2a-401, as enacted by Laws of Utah 2020, Chapter 43
48     

49     Be it enacted by the Legislature of the state of Utah:
50          Section 1. Section 15A-2-101 is amended to read:
51          15A-2-101. Title -- Adoption of code.
52          (1) This chapter is known as the "Adoption of State Construction Code."
53          (2) In accordance with Chapter 1, Part 2, State Construction Code Administration Act,
54     the Legislature repeals the State Construction Code in effect on July 1, 2010, and adopts the
55     following as the State Construction Code:
56          (a) this chapter;
57          [(b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as
58     Part of State Construction Code;]

59          [(c)] (b) Chapter 3, Statewide Amendments Incorporated as Part of State Construction
60     Code;
61          [(d)] (c) Chapter 4, Local Amendments Incorporated as Part of State Construction
62     Code; and
63          [(e)] (d) Chapter 6, Additional Construction Requirements.
64          Section 2. Section 15A-2-102 is amended to read:
65          15A-2-102. Definitions.
66          As used in this chapter, [Chapter 2a, Tall Wood Buildings of Mass Timber
67     Construction Incorporated as Part of State Construction Code,] Chapter 3, Statewide
68     Amendments Incorporated as Part of State Construction Code, and Chapter 4, Local
69     Amendments Incorporated as Part of State Construction Code:
70          (1) "HUD Code" means the Federal Manufactured Housing Construction and Safety
71     Standards Act, as issued by the Department of Housing and Urban Development and published
72     in 24 C.F.R. Parts 3280 and 3282 (as revised April 1, 1990).
73          (2) "IBC" means the edition of the International Building Code adopted under Section
74     15A-2-103.
75          (3) "IEBC" means the edition of the International Existing Building Code adopted
76     under Section 15A-2-103.
77          (4) "IECC" means the edition of the International Energy Conservation Code adopted
78     under Section 15A-2-103.
79          (5) "IFGC" means the edition of the International Fuel Gas Code adopted under
80     Section 15A-2-103.
81          (6) "IMC" means the edition of the International Mechanical Code adopted under
82     Section 15A-2-103.
83          (7) "IPC" means the edition of the International Plumbing Code adopted under Section
84     15A-2-103.
85          (8) "IRC" means the edition of the International Residential Code adopted under
86     Section 15A-2-103.
87          (9) "ISPSC" means the edition of the International Swimming Pool and Spa Code
88     adopted under Section 15A-2-103.
89          (10) "NEC" means the edition of the National Electrical Code adopted under Section

90     15A-2-103.
91          (11) "UWUI" means the edition of the Utah Wildland Urban Interface Code adopted
92     under Section 15A-2-103.
93          Section 3. Section 15A-2-104 is amended to read:
94          15A-2-104. Installation standards for manufactured housing.
95          (1) The following are the installation standards for manufactured housing for new
96     installations or for existing manufactured or mobile homes that are subject to relocation,
97     building alteration, remodeling, or rehabilitation in the state:
98          (a) The manufacturer's installation instruction for the model being installed is the
99     primary standard.
100          (b) If the manufacturer's installation instruction for the model being installed is not
101     available or is incomplete, the following standards apply:
102          (i) Appendix E of the 2015 edition of the IRC, as issued by the International Code
103     Council for installations defined in Section AE101 of Appendix E; or
104          (ii) if an installation is beyond the scope of the [2015] 2021 edition of the IRC as
105     defined in Section AE101 of Appendix E, the 2005 edition of the NFPA 225 Model
106     Manufactured Home Installation Standard, issued by the National Fire Protection Association.
107          (c) A manufacturer, dealer, or homeowner is permitted to design for unusual
108     installation of a manufactured home not provided for in the manufacturer's standard installation
109     instruction, Appendix E of the [2015] 2021 edition of the IRC, or the 2005 edition of the
110     NFPA 225, if the design is approved in writing by a professional engineer or architect licensed
111     in Utah.
112          (d) For a mobile home built before June 15, 1976, the mobile home shall also comply
113     with the additional installation and safety requirements specified in Chapter 3, Part 8,
114     Statewide Amendments to International Existing Building Code.
115          (2) Pursuant to the HUD Code Section 604(d), a manufactured home may be installed
116     in the state that does not meet the local snow load requirements as specified in Chapter 3, Part
117     2, Statewide Amendments to International Residential Code, except that the manufactured
118     home shall have a protective structure built over the home that meets the IRC and the snow
119     load requirements under Chapter 3, Part 2, Statewide Amendments to International Residential
120     Code.

121          Section 4. Section 15A-5-103 is amended to read:
122          15A-5-103. Nationally recognized codes incorporated by reference.
123          The following codes are incorporated by reference into the State Fire Code:
124          (1) the International Fire Code, [2018] 2021 edition, excluding appendices, as issued
125     by the International Code Council, Inc., except as amended by Part 2, Statewide Amendments
126     and Additions to International Fire Code Incorporated as Part of State Fire Code;
127          [(2) National Fire Protection Association, NFPA 96, Standard for Ventilation Control
128     and Fire Protection of Commercial Cooking Operations, 2017 edition, except as amended by
129     Part 3, Amendments and Additions to National Fire Protection Association Incorporated as
130     Part of State Fire Code;]
131          [(3) National Fire Protection Association, NFPA 1403, Standard on Live Fire Training
132     Evolutions, 2012 edition, except as amended by Part 3, Amendments and Additions to National
133     Fire Protection Association Incorporated as Part of State Fire Code; and]
134          [(4)] (2) National Fire Protection Association, NFPA 1, Chapter 38, Marijuana
135     Growing, Processing, and Extraction Facilities, 2018 edition[.];
136          (3) National Fire Protection Association, NFPA 54, National Fuel Gas Code, 2021
137     edition; and
138          (4) National Fire Protection Association, NFPA 58, Liquefied Petroleum Gas Code,
139     2023 edition.
140          Section 5. Section 15A-5-202 is amended to read:
141          15A-5-202. Amendments and additions to IFC related to administration, permits,
142     definitions, and general and emergency planning.
143          (1) For IFC, Chapter 1, Scope and Administration:
144          (a) IFC, Chapter 1, Section 102.5, is deleted and rewritten as follows:
145          "102.5 Application of residential code.
146          If a structure is designed and constructed in accordance with the International
147     Residential Code, the provisions of this code apply only as follows:
148          1. The construction and design provisions of this code apply only to premises
149     identification, fire apparatus access, fire hydrants and water supplies, and construction permits
150     required by Section 105.7.
151          2. This code does not supercede the land use, subdivision, or development standards

152     established by a local jurisdiction.
153          3. The administrative, operational, and maintenance provisions of this code apply."
154          (b) IFC, Chapter 1, Section 102.9, is deleted and rewritten as follows:
155          "102.9 Matters not provided for.
156          Requirements that are essential for the public safety of an existing or proposed activity,
157     building or structure, or for the safety of the occupants thereof, which are not specifically
158     provided for by this code, shall be determined by the fire code official on an emergency basis
159     if:
160          (a) the facts known to the fire code official show that an immediate and significant
161     danger to the public health, safety, or welfare exists; and
162          (b) the threat requires immediate action by the fire code official.
163          102.9.1 Limitation of emergency order.
164          In issuing its emergency order, the fire code official shall:
165          (a) limit the order to require only the action necessary to prevent or avoid the danger to
166     the public health, safety, or welfare; and
167          (b) give immediate notice to the persons who are required to comply with the order,
168     that includes a brief statement of the reasons for the fire code official's order.
169          101.9.2 Right to appeal emergency order.
170          If the emergency order issued under this section will result in the continued
171     infringement or impairment of any legal right or interest of any party, the party shall have a
172     right to appeal the fire code official's order in accordance with IFC, Chapter 1, Section 109."
173          (c) IFC, Chapter 1, Section [105.4.1] 106.1, Submittals, is amended to add the
174     following after the last sentence:
175          "Fire sprinkler system layout [may] shall be prepared and submitted by a person
176     certified by the National Institute for Certification in Engineering Technologies at level III or
177     IV in Water-Based System Layout. Fire alarm system layout [may] shall be prepared and
178     submitted by a person certified by the National Institute for Certification in Engineering
179     Technologies at level III or IV in Fire Alarm Systems."
180          (d) IFC, Chapter 1, Section [105.6.16] 105.5.18, Flammable and combustible liquids,
181     is amended to add the following section: "12. The owner of an underground tank that is out of
182     service for longer than one year shall receive a Temporary Closure Notice from the Department

183     of Environmental Quality and a copy shall be given to the AHJ."
184          (e) [A new] In IFC, Chapter 1, Section [109.1.1, Application of residential code,]
185     102.5, a new subsection 3. is added as follows:
186          ["109.1.1 Application of residential code.]
187          "3. For development regulated by a local jurisdiction's land use authority, the fire code
188     official's interpretation of this code is subject to the advisory opinion process described in Utah
189     Code, Section 13-43-205, and to a land use appeal authority appointed under Utah Code,
190     Section 10-9a-701 or 17-27a-701."
191          (f) In IFC, Chapter 1, Section [109] 111, a new Section [109.4] 111.5, Notice of right
192     to appeal, is added as follows: "At the time a fire code official makes an order, decision, or
193     determination that relates to the application or interpretation of this chapter, the fire code
194     official shall inform the person affected by the order, decision, or determination of the person's
195     right to appeal under this section. Upon request, the fire code official shall provide a person
196     affected by an order, decision, or determination that relates to the application or interpretation
197     of this chapter a written notice that describes the person's right to appeal under this section."
198          [(g) IFC, Chapter 1, Section 110.3, Notice of violation, is deleted and rewritten as
199     follows:]
200          ["110.3 Notice of violation.]
201          [If the fire code official determines that a building, premises, vehicle, storage facility, or
202     outdoor area is in violation of this code or other pertinent laws or ordinances, the fire code
203     official is authorized to prepare a written notice of violation that describes the conditions
204     deemed unsafe and, absent immediate compliance, specifies a time for reinspection."]
205          (2) For IFC, Chapter 2, Definitions:
206          (a) IFC, Chapter 2, Section 202, General Definitions, the following definition is added
207     for Ambulatory Surgical Center: "AMBULATORY SURGICAL CENTER. A building or
208     portion of a building licensed by the Department of Health where procedures are performed
209     that may render patients incapable of self preservation where care is less than 24 hours. See
210     Utah Administrative Code, R432-13, Freestanding Ambulatory Surgical Center Construction
211     Rule."
212          (b) IFC, Chapter 2, Section 202, General Definitions, the following definition is added
213     for Assisted Living Facility, Residential Treatment and Support. "ASSISTED LIVING

214     FACILITY[. See Residential Treatment/Support Assisted Living Facility, Type I Assisted
215     Living Facility, and Type II Assisted Living Facility."], RESIDENTIAL TREATMENT AND
216     SUPPORT: A residential facility that provides a group living environment for four or more
217     residents licensed by the Department of Health and Human Services and provides a protected
218     living arrangement for ambulatory, non-restrained persons who are capable of achieving
219     mobility sufficient to exit the facility without the physical assistance of another person.
220          ASSISTED LIVING FACILITY, TYPE I. A residential facility licensed by the
221     Department of Health and Human Services that provides a protected living arrangement,
222     assistance with activities of daily living and social care to two or more ambulatory,
223     non-restrained persons who are capable of mobility sufficient to exit the facility without the
224     assistance of another person.
225          ASSISTED LIVING FACILITY, TYPE II. A residential facility licensed by the
226     Department of Health and Human Services that provides an array of coordinated supportive
227     personal and health care services to two or more residents who are:
228          A. Physically disabled but able to direct his or her own care; or
229          B. Cognitively impaired or physically disabled but able to evacuate from the facility, or
230     to a zone or area of safety, with the physical assistance of one person.
231          Subcategories are:
232          ASSISTED LIVING FACILITY, LIMITED CAPACITY: A Type I or Type II assisted
233     living facility having two to five residents.
234          ASSISTED LIVING FACILITY, SMALL: A Type I or Type II assisted living facility
235     having six to sixteen residents.
236          ASSISTED LIVING FACILITY, LARGE: A Type I or Type II assisted living facility
237     having more than sixteen residents."
238          (c) IFC, Chapter 2, Section 202, General Definitions, [FOSTER CARE FACILITIES is
239     amended as follows: The word "Foster" is changed to the word "Child."] the definition for
240     Child Care Facility is added as follows: "CHILD CARE FACILITY: A facility where care and
241     supervision is provided for four or more children for less than 24 hours a day and for direct or
242     indirect compensation in place of care ordinarily provided in their home."
243          (d) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
244     CLASSIFICATION, Educational Group E, Group E, day care facilities, is [amended as

245     follows] deleted and replaced with the following:
246          "Group E, Child Care Facilities. This group includes buildings and structures or
247     portions thereof occupied by four or more children 2 years of age or older who receive
248     educational, supervision, child care services or personal care services for fewer than 24 hours
249     per day. See Section 429, Day Care, for special requirements for day care.
250          Within Places of Religious Worship. Rooms and spaces within places of religious
251     worship providing such day care during religious functions shall be classified as part of the
252     primary occupancy.
253          Four or Fewer Children. A facility having four or fewer children receiving such day
254     care shall be classified as part of the primary occupancy.
255          Four or Fewer Children in a Dwelling Unit. A facility such as the above within a
256     dwelling unit and having four or fewer children receiving such day care shall be classified as a
257     Group R-3 occupancy or shall comply with the International Residential Code.
258          Child Day Care - Residential Child Care Certificate or a License. Areas used for child
259     day care purposes with a residential child care certificate, as described in Utah Administrative
260     Code, R430-50, Residential Certificate Child Care, or a residential child care license, as
261     described in Utah Administrative Code, R430-90, Licensed Family Child Care, may be located
262     in a Group R-2 or R-3 occupancy as provided in the International Building Code, Sections
263     310.3 and 310.4, or shall comply with the International Residential Code, Section R101.2.
264          Child Care Centers. Each of the following areas may be classified as accessory
265     occupancies, if the area complies with the International Building Code, Section 508.2:
266          1. Hourly child care center, as described in Utah Administrative Code, R381-60,
267     Hourly Child Care Centers;
268          2. Child care centers, as described in Utah Administrative Code, R381-100, Child Care
269     Centers;
270          3. Out-of-school-time programs, as described in Utah Administrative Code, R381-70,
271     Out of School Time Child Care Programs; and
272          4. Commercial preschools, as described in Utah Administrative Code, R381-40,
273     Commercial Preschool Programs."
274          [(i) On line three delete the word "five" and replace it with the word "four"; and]
275          [(ii) On line four after the word "supervision" add the words "child care centers."]

276          [(e) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
277     CLASSIFICATION, Educational Group E, Five or fewer children, is amended as follows: The
278     word "five" is deleted and replaced with the word "four" in both places.]
279          [(f) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
280     CLASSIFICATION, Educational Group E, Five or fewer children in a dwelling unit, is
281     amended as follows: The word "five" is deleted and replaced with the word "four" in both
282     places.]
283          [(g) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
284     CLASSIFICATION, Educational Group E, a new section is added as follows: "Child day care
285     -- residential child care certificate or a license. Areas used for child day care purposes with a
286     residential child care certificate, as described in Utah Administrative Code, R430-50,
287     Residential Certificate Child Care, or a residential child care license, as described in Utah
288     Administrative Code, R430-90, Licensed Family Child Care, may be located in a Group R-2 or
289     R-3 occupancy as provided in Residential Group R-3, or shall comply with the International
290     Residential Code in accordance with Section R101.2."]
291          [(h) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
292     CLASSIFICATION, Educational Group E, a new section is added as follows: "Child care
293     centers. Each of the following areas may be classified as accessory occupancies:]
294          [1. Hourly child care centers, as described in Utah Administrative Code, R381-60,
295     Hourly Child Care Centers;]
296          [2. Child care centers, as described in Utah Administrative Code, R381-100, Child
297     Care Centers; and]
298          [3. Out-of-school-time programs, as described in Utah Administrative Code, R381-70,
299     Out of School Time Child Care Programs."]
300          [(i)] (e) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
301     CLASSIFICATION, Institutional Group I-1, is amended as follows: [Insert "Type I" in front of
302     the words "Assisted living facilities".] In the list of items under "This group shall include," the
303     words "Type-I Large and Type-II Small, see the International Building Code, Section 308.2.5"
304     are added after "Assisted living facilities."
305          [(j)] (f) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
306     CLASSIFICATION, Institutional Group I-1, Five or fewer persons receiving custodial care is

307     amended as follows: On line four after "International Residential Code" the rest of the section
308     is deleted.
309          [(k)] (g) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
310     CLASSIFICATION, Institutional Group I-2, is [amended as follows:] deleted and replaced
311     with the following:
312          [(i) On line three delete the word "five" and insert the word "three";]
313          [(ii) On line six the word "foster" is deleted and replaced with the word "child"; and]
314          [(iii) On line 10, after the words "Psychiatric hospitals", add the following to the list:
315     "both intermediate nursing care and skilled nursing care facilities, ambulatory surgical centers
316     with five or more operating rooms, and Type II assisted living facilities. Type II assisted living
317     facilities with five or fewer persons shall be classified as a Group R-4. Type II assisted living
318     facilities with at least six and not more than 16 residents shall be classified as a Group I-1
319     facility".]
320          "Institutional Group I-2. Institutional Group I-2 occupancy shall include buildings and
321     structures used for medical care on a 24-hour basis for more than four persons who are
322     incapable of self-preservation. This group shall include, but not be limited to the following:
323          Assisted living facilities, Type-II Large, see Section 308.3.3
324          Child care facilities
325          Foster care facilities
326          Detoxification facilities
327          Hospitals
328          Nursing homes (both intermediate care facilities and skilled nursing facilities)
329          Psychiatric hospitals"
330          [(l)] (h) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
331     CLASSIFICATION, Institutional Group [I-4, day care facilities, Classification as Group E, is
332     amended as follows:] I-2, a new section is added as follows:
333          "Assisted Living Facilities. A Type I, Large assisted living facility is classified as
334     occupancy Group I-1, Condition 1. A Type II, Small assisted living facility is classified as
335     occupancy Group I-1, Condition 2. See Section 202 for definitions."
336          [(i) On line two delete the word "five" and replace it with the word "four"; and]
337          [(ii) On line three delete the words "2 1/2 years or less of age" and replace with the

338     words "under the age of two".]
339          [(m)] (i) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
340     CLASSIFICATION, Institutional Group I-4, day care facilities, [Five or fewer occupants
341     receiving care in a dwelling unit, is amended as follows: On lines one and three the word "five"
342     is deleted and replaced with the word "four".] Classification as Group E, Five or fewer persons
343     receiving care, and Five or fewer occupants receiving care in a dwelling unit are deleted and
344     replaced with the following:
345          "Classification as Group E. A child day care facility that provides care for five or more
346     but not more than 100 children under two years of age, where the rooms in which the children
347     are cared for are located on a level of exit discharge serving such rooms and each of these child
348     care rooms has an exit door directly to the exterior, shall be classified as a Group E. See the
349     International Building Code, Section 429 for special requirements for Day Care.
350          Four or Fewer Persons Receiving Care. A facility having four or fewer persons
351     receiving custodial care shall be classified as part of the primary occupancy. See the
352     International Building Code, Section 429, for special requirements for Day Care.
353          Four or Fewer Persons Receiving Care in a Dwelling Unit. A facility such as the above
354     within a dwelling unit and having four or fewer persons receiving custodial care shall be
355     classified as a Group R-3 occupancy or shall comply with the International Residential Code.
356     See the International Building Code, Section 429, for special requirements for Day Care."
357          [(n)] (j) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
358     CLASSIFICATION, Residential Group R-3, [the words "and single family dwellings
359     complying with the IRC" are added after the word "Residential Group R-3 occupancies".] is
360     deleted and replaced with the following:
361          "Residential Group R-3. Residential Group R-3 occupancies and single family
362     dwellings complying with the International Residential Code where the occupants are primarily
363     permanent in nature and not classified as Group R-1, R-2, R-4, or I occupancies, including:
364          Assisted Living Facilities, Type-I, limited capacity, see Section 310.5.3
365          Buildings that do not contain more than two dwellings
366          Care facilities, other than child care, that provide accommodations for five or fewer
367     persons receiving care
368          Congregate living facilities (nontransient) with 16 or fewer occupants

369          Boarding houses (nontransient)
370          Convents
371          Dormitories
372          Fraternities and sororities
373          Monasteries
374          Congregate living facilities (transient) with 10 or fewer occupants
375          Boarding houses (transient)
376          Lodging houses (transient) with five or fewer guest rooms and 10 or fewer occupants"
377          [(o)] (k) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
378     CLASSIFICATION, Residential Group R-3, Care facilities within a dwelling, [is amended as
379     follows: On line three after the word "dwelling" insert "other than child care".] is deleted and
380     replaced with the following: "Care Facilities within a Dwelling. Care facilities, other than child
381     care, for five or fewer persons receiving care that are within a single family dwelling are
382     permitted to comply with the International Residential Code. See the International Building
383     Code, Section 429, for special requirements for Child Day Care."
384          [(p)] (l) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
385     CLASSIFICATION, Residential Group R-3, a new section is added as follows: "Child Care.
386     Areas used for child care purposes may be located in a residential dwelling unit when all of the
387     following conditions are met:
388          1. Compliance with Utah Administrative Code, R710-8, Day Care Rules, as enacted
389     under the authority of the Utah Fire Prevention Board;
390          2. Use is approved by the Department of Health under the authority of Utah Code, Title
391     26, Chapter 39, Utah Child Care Licensing Act, and in any of the following categories:
392          1.1. Utah Administrative Code, R430-50, Residential Certificate Child Care; or
393          1.2. Utah Administrative Code, R430-90, Licensed Family Child Care; and
394          1.3 Compliance with all zoning regulations of the local regulator."
395          [(q) IFC, Chapter 2, Section 202, General Definitions, RECORD DRAWINGS, is
396     amended as follows: Delete the words "a fire alarm system" and replace them with "any fire
397     protection system".]
398          [(r) IFC, Chapter 2, Section 202, General Definitions, the following definition is added
399     for Residential Treatment/Support Assisted Living Facility. "RESIDENTIAL

400     TREATMENT/SUPPORT ASSISTED LIVING FACILITY. A residential facility that provides
401     a group living environment for four or more residents licensed by the Department of Human
402     Services, and provides a protected living arrangement for ambulatory, non-restrained persons
403     who are capable of achieving mobility sufficient to exit the facility without the physical
404     assistance of another person."]
405          [(s) IFC, Chapter 2, Section 202, General Definitions, the following definition is added
406     for Type I Assisted Living Facility. "TYPE I ASSISTED LIVING FACILITY. A residential
407     facility licensed by the Department of Health that provides a protected living arrangement,
408     assistance with activities of daily living and social care to two or more ambulatory,
409     non-restrained persons who are capable of mobility sufficient to exit the facility without the
410     assistance of another person. Subcategories are:]
411          [Limited Capacity: two to five residents;]
412          [Small: six to sixteen residents; and]
413          [Large: over sixteen residents."]
414          [(t) IFC, Chapter 2, Section 202, General Definitions, the following definition is added
415     for Type II Assisted Living Facility. "TYPE II ASSISTED LIVING FACILITY. A residential
416     facility licensed by the Department of Health that provides an array of coordinated supportive
417     personal and health care services to two or more residents who are:]
418          [A. Physically disabled but able to direct his or her own care; or]
419          [B. Cognitively impaired or physically disabled but able to evacuate from the facility, or
420     to a zone or area of safety, with the physical assistance of one person. Subcategories are:]
421          [Limited Capacity: two to five residents;]
422          [Small: six to sixteen residents; and]
423          [Large: over sixteen residents."]
424          (m) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
425     CLASSIFICATION, Residential Group R-3, a new section is added as follows:
426          "Assisted Living Facilities. Type I assisted living facilities with two to five residents are
427     Limited Capacity facilities classified as a Residential Group R-3 occupancy or are permitted to
428     comply with the International Residential Code. See Section 202 for definitions."
429          (n) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
430     CLASSIFICATION, Residential Group R-4, the words "Type II Limited Capacity and Type I

431     Small, see R-4 Assisted Living Facility Occupancy Groups" are added after the words
432     "Assisted Living Facilities."
433          (o) IFC, Chapter 2, Section 202, General Definitions, OCCUPANCY
434     CLASSIFICATION, Residential Group R-4, a new section is added as follows: "Group R-4 -
435     Assisted Living Facility Occupancy Groups. The following occupancy groups shall apply to
436     Assisted Living Facilities:
437          Type II Assisted Living Facilities with two to five residents are Limited Capacity
438     Facilities classified as a Residential Group R-4, Condition 2 occupancy.
439          Type I assisted living facilities with six to sixteen residents are Small Facilities
440     classified as Residential Group R-4, Condition 1 occupancies. See Section 202 for definitions."
441          Section 6. Section 15A-5-202.5 is amended to read:
442          15A-5-202.5. Amendments and additions to Chapters 3 and 4 of IFC.
443          (1) For IFC, Chapter 3, General Requirements:
444          (a) IFC, Chapter 3, Section 304.1.2, Vegetation, is amended as follows: Delete line six
445     and replace it with: "Utah Administrative Code, R652-122-1300, Minimum Standards for
446     County Wildland Fire Ordinance".
447          (b) IFC, Chapter 3, Section 310.8, Hazardous environmental conditions, is deleted and
448     rewritten as follows: "1. When the fire code official determines that existing or historical
449     hazardous environmental conditions necessitate controlled use of any ignition source, including
450     fireworks, lighters, matches, sky lanterns, and smoking materials, any of the following may
451     occur:
452          1.1. If the existing or historical hazardous environmental conditions exist in a
453     municipality, the legislative body of the municipality may prohibit the ignition or use of an
454     ignition source in:
455          1.1.1. mountainous, brush-covered, forest-covered, or dry grass-covered areas;
456          1.1.2. within 200 feet of waterways, trails, canyons, washes, ravines, or similar areas;
457          1.1.3. the wildland urban interface area, which means the line, area, or zone where
458     structures or other human development meet or intermingle with undeveloped wildland or land
459     being used for an agricultural purpose; or
460          1.1.4. a limited area outside the hazardous areas described in this paragraph 1.1 to
461     facilitate a readily identifiable closed area, in accordance with paragraph 2.

462          1.2. If the existing or historical hazardous environmental conditions exist in an
463     unincorporated area, the state forester may prohibit the ignition or use of an ignition source in
464     all or part of the areas described in paragraph 1.1 that are within the unincorporated area, after
465     consulting with the county fire code official who has jurisdiction over that area.
466          1.3. If the existing or historical hazardous environmental conditions exist in a metro
467     township created under Title 10, Chapter 2a, Part 4, Incorporation of Metro Townships and
468     Unincorporated Islands in a County of the First Class on and after May 12, 2015, the metro
469     township legislative body may prohibit the ignition or use of an ignition source in all or part of
470     the areas described in paragraph 1.1 that are within the township.
471          2. If a municipal legislative body, the state forester, or a metro township legislative
472     body closes an area to the discharge of fireworks under paragraph 1, the legislative body or
473     state forester shall:
474          2.1. designate the closed area along readily identifiable features like major roadways,
475     waterways, or geographic features;
476          2.2. ensure that the boundary of the designated closed area is as close as is practical to
477     the defined hazardous area, provided that the closed area may include areas outside of the
478     hazardous area to facilitate a readily identifiable line; and
479          2.3. identify the closed area through a written description or map that is readily
480     available to the public.
481          3. A municipal legislative body, the state forester, or a metro township legislative body
482     may close a defined area to the discharge of fireworks due to a historical hazardous
483     environmental condition under paragraph 1 if the legislative body or state forester:
484          3.1. makes a finding that the historical hazardous environmental condition has existed
485     in the defined area before July 1 of at least two of the preceding five years;
486          3.2. produces a map indicating the boundaries, in accordance with paragraph 2, of the
487     defined area described; and
488          3.3. before May 1 of each year the defined area is closed, provides the map described
489     in paragraph 3.2 to the county in which the defined area is located.
490          4. A municipal legislative body, the state forester, or a metro township legislative body
491     may not close an area to the discharge of fireworks due to a historical hazardous environmental
492     condition unless the legislative body or state forester provides a map, in accordance with

493     paragraph 3."
494          (c) IFC, Chapter 3, Section 311.1.1, Abandoned premises, is amended as follows: On
495     line 10 delete the words "International Property Maintenance Code and the".
496          (d) IFC, Chapter 3, Section 311.5, Placards, is amended as follows: On line three delete
497     the word "shall" and replace it with the word "may".
498          (2) IFC, Chapter 4, Emergency Planning and Preparedness:
499          (a) In IFC, Chapter 4, the following new Sections are added:
500          "401.3.1.1 Special Education Classrooms. Special education classrooms may shelter in
501     place, or delay evacuation when all of the following conditions are met:
502          401.3.1.1.1 There is no visible flame or evidence of products of combustion (smoke).
503          401.3.1.1.2 The building is completely protected by an approved fire sprinkler system.
504          401.3.1.1.3 The building is completely protected by an approved fire alarm system.
505          401.3.1.1.4 The classroom has a minimum of one approved exit that discharges
506     directly to the exterior.
507          401.3.1.1.5 The classroom has been approved to shelter in place by the fire code
508     official."
509          (b) In IFC, Chapter 4, Section 401.3.3, Delayed notification, a new exception is added:
510          "Exception: Group E Occupancies. Teachers may delay evacuation upon fire alarm
511     activation for up to 60 seconds when all of the following conditions are met:
512          A. There is no visible flame or evidence of products of combustion (smoke).
513          B. The building is protected throughout by an approved fire sprinkler system.
514          C. The building is protected throughout by an approved fire alarm system.
515          D. Students are in the safe zone of the room lined up and prepared for immediate
516     evacuation."
517          (c) IFC, Chapter 4, Section [403.10.2.1] 403.9.2.1, College and university buildings, is
518     deleted and replaced with the following:
519          ["403.10.2.1] "403.9.2.1 College and university buildings and fraternity and sorority
520     houses.
521          [(a)] (i) College and university buildings, including fraternity and sorority houses, shall
522     prepare an approved fire safety and evacuation plan, in accordance with Section 404.
523          [(b)] (ii) Group R-2 college and university buildings, including fraternity and sorority

524     houses, shall comply with Sections [403.10.2.1.1 and 403.10.2.1.2] 403.9.2.1.1 and
525     403.9.2.1.2."
526          [(b)] (d) IFC, Chapter 4, Section [405.2, Table 405.2] 405.3, Table 405.3, is amended
527     to add the following footnotes:
528          (i) ["e] "c. Secondary schools in Group E occupancies shall have an emergency
529     evacuation drill [for fire] conducted at least every two months, to a total of four emergency
530     evacuation drills during the nine-month school year. The first emergency evacuation drill [for
531     fire] shall be conducted within 10 school days after the beginning of classes. The third
532     emergency evacuation drill [for fire], weather permitting, shall be conducted 10 school days
533     after the beginning of the next calendar year. The second and fourth emergency evacuation
534     drills may be substituted by a security or safety drill to include shelter in place, earthquake drill,
535     or lock down for violence. If inclement weather causes a secondary school to miss the 10-day
536     deadline for the third emergency evacuation drill [for fire], the secondary school shall perform
537     the third emergency evacuation drill [for fire] as soon as practicable after the missed deadline."
538          (ii) ["f] "d. In Group E occupancies, excluding secondary schools, if the AHJ approves,
539     the monthly required emergency evacuation drill can be substituted by a security or safety drill
540     to include shelter in place, earthquake drill, or lock down for violence. The routine emergency
541     evacuation drill must be conducted at least every other drill."
542          (iii) ["g] "e. A-3 occupancies in academic buildings of institutions of higher learning
543     are required to have one emergency evacuation drill per year, provided the following conditions
544     are met:
545          (A) The building has a fire alarm system in accordance with Section 907.2.
546          (B) The rooms classified as assembly shall have fire safety floor plans as required in
547     Subsection 404.2.2(4) posted.
548          (C) The building is not classified a high-rise building.
549          (D) The building does not contain hazardous materials over the allowable quantities by
550     code."
551          [(iv) "h. Notwithstanding any other provision of law, during the 2020-2021 school
552     year, Group E occupancies are not required to conduct an emergency evacuation drill before
553     March 1, 2021. For the period beginning the first day of the 2020-2021 school year and ending
554     February 28, 2021, each calendar month, Group E occupancies shall provide in-class

555     instruction to students in an age-appropriate manner that describes the procedures for
556     emergency evacuation for fire. Group E occupancies shall complete the first monthly
557     instruction no later than 15 days after the day on which the 2020-2021 school year begins. In
558     addition to the monthly instruction, Group E occupancies may provide in-class security or
559     safety drills to include shelter in place, earthquake drill, or lock down for violence."]
560          [(v) "i. Notwithstanding any other provision of law, for the period beginning March 1,
561     2021, and ending the last day of the 2020-2021 school year, in Group E occupancies, if the
562     AHJ approves, the monthly required emergency evacuation drill can be substituted by a
563     security or safety drill to include shelter in place, earthquake drill, or lock down for violence.
564     The routine emergency evacuation drill must be conducted at least every other month."]
565          Section 7. Section 15A-5-203 is amended to read:
566          15A-5-203. Amendments and additions to IFC related to fire safety, building, and
567     site requirements.
568          (1) For IFC, Chapter 5, Fire Service Features:
569          (a) In IFC, Chapter 5, a new Section 501.5, Access grade and fire flow, is added as
570     follows: "An authority having jurisdiction over a structure built in accordance with the
571     requirements of the International Residential Code as adopted in the State Construction Code,
572     may require an automatic fire sprinkler system for the structure only by ordinance and only if
573     any of the following conditions exist:
574          (i) the structure:
575          (A) is located in an urban-wildland interface area as provided in the Utah Wildland
576     Urban Interface Code adopted as a construction code under the State Construction Code; and
577          (B) does not meet the requirements described in Utah Code, Subsection
578     65A-8-203(4)(a) and Utah Administrative Code, R652-122-1300, Minimum Standards for
579     County Wildland Fire Ordinance;
580          (ii) the structure is in an area where a public water distribution system with fire
581     hydrants does not exist as required in Utah Administrative Code, R309-550-5, Water Main
582     Design;
583          (iii) the only fire apparatus access road has a grade greater than 10% for more than 500
584     continual feet;
585          (iv) the total floor area of all floor levels within the exterior walls of the dwelling unit

586     exceeds 10,000 square feet; or
587          (v) the total floor area of all floor levels within the exterior walls of the dwelling unit is
588     double the average of the total floor area of all floor levels of unsprinkled homes in the
589     subdivision that are no larger than 10,000 square feet.
590          (vi) Exception: A single family dwelling does not require a fire sprinkler system if the
591     dwelling:
592          (A) is located outside the wildland urban interface;
593          (B) is built in a one-lot subdivision; and
594          (C) has 50 feet of defensible space on all sides that limits the propensity of fire
595     spreading from the dwelling to another property."
596          (b) In IFC, Chapter 5, Section 506.1, Where Required, is deleted and rewritten as
597     follows: "Where access to or within a structure or an area is restricted because of secured
598     openings or where immediate access is necessary for life-saving or fire-fighting purposes, the
599     fire code official, after consultation with the building owner, may require a key box to be
600     installed in an approved location. The key box shall contain keys to gain necessary access as
601     required by the fire code official. For each fire jurisdiction that has at least one building with a
602     required key box, the fire jurisdiction shall adopt an ordinance, resolution, or other operating
603     rule or policy that creates a process to ensure that each key to each key box is properly
604     accounted for and secure."
605          (c) In IFC, Chapter 5, a new Section 507.1.1, Isolated one- and two-family dwellings,
606     is added as follows: "Fire flow may be reduced for an isolated one- and two-family dwelling
607     when the authority having jurisdiction over the dwelling determines that the development of a
608     full fire-flow requirement is impractical."
609          (d) In IFC, Chapter 5, a new Section 507.1.2, Pre-existing subdivision lots, is added as
610     follows:
611           "507.1.2 Pre-existing subdivision lots.
612           The requirements for a pre-existing subdivision lot shall not exceed the requirements
613     described in Section 501.5."
614          (e) In IFC, Chapter 5, Section 507.5.1, here required, a new exception is added: "3.
615     One interior and one detached accessory dwelling unit on a single residential lot."
616          [(e)] (f) [In] IFC, Chapter 5, Section 510.1, Emergency responder [radio]

617     communication coverage in new buildings, is amended by adding: "When required by the fire
618     code official," at the beginning of the first paragraph.
619          (2) For IFC, Chapter 6, Building Services and Systems:
620          (a) [In] IFC, Chapter 6, Section [606.7] 604.6.1, Elevator key location, is deleted and
621     rewritten as follows: "Firefighter service keys shall be kept in a "Supra-Stor-a-key" elevator
622     key box or similar box with corresponding key system that is adjacent to the elevator for
623     immediate use by the fire department. The key box shall contain one key for each elevator, one
624     key for lobby control, and any other keys necessary for emergency service. The elevator key
625     box shall be accessed using a 6049 numbered key."
626          (b) [In] IFC, Chapter 6, Section [607.1] 606.1, General, is amended as follows: On line
627     three, after the word "Code", add the words "and NFPA 96".
628          (c) [In] IFC, Chapter 6, Section 607.2, a new exception 5 is added as follows: "5. A
629     Type 1 hood is not required for a cooking appliance in a microenterprise home kitchen, as that
630     term is defined in Utah Code, Section 26-15c-102, for which the operator obtains a permit in
631     accordance with Utah Code, Title 26, Chapter 15c, Microenterprise Home Kitchen Act."
632          (3) For IFC, Chapter 7, Fire and Smoke Protection Features, IFC, Chapter 7, Section
633     705.2, is amended to add the following: "Exception: In Group E Occupancies, where the
634     corridor serves an occupant load greater than 30 and the building does not have an automatic
635     fire sprinkler system installed, the door closers may be of the friction hold-open type on
636     classrooms' doors with a rating of 20 minutes or less only."
637          Section 8. Section 15A-5-204 is amended to read:
638          15A-5-204. Amendments and additions to IFC related to fire protection and life
639     safety systems.
640          For IFC, Chapter 9, Fire Protection and Life Safety Systems:
641          [(1) IFC, Chapter 9, Section 901.2, Construction documents, is amended to add the
642     following at the end of the section: "The code official has the authority to request record
643     drawings ("as builts") to verify any modifications to the previously approved construction
644     documents."]
645          [(2)] (1) IFC, Chapter 9, Section [901.4.6] 901.4.7, Pump and riser room size, is
646     deleted and replaced with the following: ["Pump and Riser Room Size. Fire pump and
647     automatic sprinkler system riser rooms shall be designed with adequate space for all installed

648     equipment necessary for the installation and to provide sufficient working space around the
649     stationary equipment. Clearances around equipment shall be in accordance with manufacturer
650     requirements and not less than the following minimum elements:]
651          [901.4.6.1 A minimum clear and unobstructed distance of 12 inches shall be provided
652     from the installed equipment to the elements of permanent construction.]
653          [901.4.6.2 A minimum clear and unobstructed distance of 12 inches shall be provided
654     between all other installed equipment and appliances.]
655          [901.4.6.3 A clear and unobstructed width of 36 inches shall be provided in front of all
656     installed equipment and appliances, to allow for inspection, service, repair or replacement
657     without removing such elements of permanent construction or disabling the function of a
658     required fire-resistance-rated assembly.]
659          [901.4.6.4 Automatic sprinkler system riser rooms shall be provided with a clear and
660     unobstructed passageway to the riser room of not less than 36 inches, and openings into the
661     room shall be clear and unobstructed, with doors swinging in the outward direction from the
662     room and the opening providing a clear width of not less than 34 inches and a clear height of
663     the door opening shall not be less than 80 inches.]
664          [901.4.6.5 Fire pump rooms shall be provided with a clear and unobstructed
665     passageway to the fire pump room of not less than 72 inches, and openings into the room shall
666     be clear, unobstructed and large enough to allow for the removal of the largest piece of
667     equipment, with doors swinging in the outward direction from the room and the opening
668     providing a clear width of not less than 68 inches and a clear height of the door opening shall
669     not be less than 80 inches."]
670          "901.4.7 Pump and Riser Room Size.
671          901.4.7.1 Fire pump rooms and automatic sprinkler system riser rooms shall be
672     designed with adequate space for all installed equipment necessary for the installation and to
673     provide sufficient working room around the stationary equipment. Clearances around
674     equipment to elements of permanent construction, including other installed equipment and
675     appliances, shall be sufficient to allow inspection, service, repair or replacement without
676     removing such elements of permanent construction or disabling the function of a required
677     fire-resistance-rated assembly and not less than the following minimum elements:
678          901.4.7.1.1 A minimum clear and unobstructed distance of 12 inches shall be provided

679     from the installed equipment to the elements of permanent construction.
680          901.4.7.1.2 A minimum clear and unobstructed distance of 12 inches shall be provided
681     between all other installed equipment and appliances.
682          901.4.7.1.3 A clear and unobstructed width of 36 inches shall be provided in front of all
683     installed equipment and appliances, to allow for inspection, service, repair or replacement
684     without removing such elements of permanent construction or disabling the function of a
685     required fire resistance-rated assembly.
686          901.4.7.2 Fire Pump Room. Fire pumps and controllers shall be provided with ready
687     access. Fire pump rooms shall be provided with doors and an unobstructed passageway large
688     enough to allow for the removal of the largest piece of equipment. The passageway shall have a
689     clear width not less than 72 inches. Openings into the room shall be clear and unobstructed,
690     with doors swinging in the outward direction from the fire pump room and the opening
691     providing a clear width of not less than 68 inches and a clear height of the door opening shall
692     not be less than 80 inches. The door shall be permitted to be locked provided that the key is
693     available at all times and located in a Key Box in accordance with IFC, Section 506.
694          901.4.7.3 Automatic Sprinkler Riser Room. Automatic sprinkler system risers shall be
695     provided with ready access. Automatic sprinkler system riser rooms shall be provided with
696     doors and an unobstructed passageway large enough to allow for the removal of the largest
697     piece of equipment. The passageway shall have a clear width not less than 36 inches. Openings
698     into the room shall be clear and unobstructed, with doors swinging in the outward direction
699     from the riser room and the opening providing a clear width of not less than 32 inches and a
700     clear height of the door opening shall not be less than 80 inches. The door shall be permitted to
701     be locked provided that the key is available at all times and located in a Key Box in accordance
702     with IFC, Section 506.
703          901.4.7.4 Marking on Access Doors. Access doors for automatic sprinkler system riser
704     rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be in
705     contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm)
706     with a minimum stroke of 3/8 inch (10 mm).
707          901.4.7.5 Environment. Automatic sprinkler system riser rooms and fire pump rooms
708     shall be maintained at a temperature of not less than 40 degrees F (4 degrees C). Heating units
709     shall be permanently installed.

710          902.6 Lighting. Permanently installed artificial illumination shall be provided in the
711     automatic sprinkler system riser rooms and fire pump rooms."
712          [(3)] (2) IFC, Chapter 9, Section 903.2.1.2, Group A-2, is amended to add the
713     following subsection: "4. An automatic fire sprinkler system shall be provided throughout
714     Group A-2 occupancies where indoor pyrotechnics are used."
715          [(4)] (3) IFC, Chapter 9, Section 903.2.2, Ambulatory care facilities, is amended as
716     follows: On line two delete the words "entire floor" and replace with the word "building" and
717     delete the last paragraph.
718          [(5)] (4) IFC, Chapter 9, Section 903.2.4, Group F-1, Subsection 2, is deleted and
719     rewritten as follows: "A Group F-1 fire area is located more than three stories above the lowest
720     level of fire department vehicle access."
721          [(6)] (5) IFC, Chapter 9, Section 903.2.7, Group M, Subsection 2, is deleted and
722     rewritten as follows: "A Group M fire area is located more than three stories above the lowest
723     level of fire department vehicle access."
724          [(7)] (6) IFC, Chapter 9, Section 903.2.8 Group R, including all subsections, is deleted
725     and rewritten as follows:
726          "903.2.8 Group R.
727          An automatic sprinkler system installed in accordance with Section 903.3 shall be
728     proved throughout all buildings with a Group R fire area.
729          Exceptions:
730          1. Detached one- and two-family dwellings and multiple single-family dwellings
731     (townhouses) constructed in accordance with the International Residential Code for One- and
732     Two-Family Dwellings.
733          2. Single story Group R-1 occupancies with fire areas not more than 2,000 square feet
734     that contain no installed plumbing or heating, where no cooking occurs, and constructed of
735     Type I-A, I-B, II-A, or II-B construction.
736          3. Group R-4 fire areas not more than 4,500 gross square feet and not containing more
737     than 16 residents, provided the building is equipped throughout with an approved fire alarm
738     system that is interconnected and receives its primary power from the building wiring and a
739     commercial power system."
740          [(8)] (7) IFC, Chapter 9, Section 903.2.9, Group S-1, Subsection 2, is deleted and

741     rewritten as follows: "A Group S-1 fire area is located more than three stories above the lowest
742     level of fire department vehicle access."
743          [(9)] (8) IFC, Chapter 9, Section 903.3.1.2.3, Attics, is amended by adding the
744     following: "Exception: Sprinkler protection in attics is not required in buildings that are not
745     required to be sprinklered by another section of this code."
746          [(10)] (9) IFC, Chapter 9, Section 903.3.5, Water supplies, is amended as follows: On
747     line six, after the word "Code", add "and as amended in the State Construction Code".
748          [(11)] (10) IFC, Chapter 9, Section 903.5, Testing and maintenance, is amended to add
749     the following subsection: "903.5.1 Tag and Information. A tag shall be attached to the riser
750     indicating the date the antifreeze solution was tested. The tag shall also indicate the type and
751     concentration of antifreeze solution by volume with which the system is filled, the name of the
752     contractor that tested the antifreeze solution, the contractor's license number, and a warning to
753     test the concentration of the antifreeze solutions at yearly intervals."
754          [(12) IFC, Chapter 9, Section 904.12, Commercial cooking systems, is deleted and
755     rewritten as follows: "The automatic fire extinguishing system for commercial cooking systems
756     shall be of a type recognized for protection of commercial cooking equipment and exhaust
757     systems. Pre-engineered automatic extinguishing systems shall be tested in accordance with
758     UL300 and listed and labeled for the intended application. The system shall be installed in
759     accordance with this code, its listing and the manufacturer's installation instructions." The
760     exception in Section 904.12 is not deleted and shall remain as currently written in the IFC.]
761          [(13) IFC, Chapter 9, Section 904.12.3, Carbon dioxide systems, and Section
762     904.12.3.1, Ventilation system, are deleted and rewritten as follows:]
763          ["904.12.3 existing automatic fire extinguishing systems used for commercial cooking.]
764          [Existing automatic fire extinguishing systems used for commercial cooking that use
765     dry chemical are prohibited and shall be removed from service.]
766          [904.12.3.1 UL300 listed and labeled existing wet chemical fire extinguishing system.]
767          [Existing wet chemical fire extinguishing systems used for commercial cooking that are
768     not UL300 listed and labeled are prohibited and shall be either removed or upgraded to a
769     UL300 listed and labeled system."]
770          [(14) IFC, Chapter 9, Section 904.12.4, Special provisions for automatic sprinkler
771     systems, is amended to add the following subsection: " 904.12.4.2 Existing automatic fire

772     sprinkler systems protecting commercial cooking equipment, hood, and exhaust systems that
773     generate appreciable depth of cooking oils shall be replaced with a UL300 system that is listed
774     and labeled for the intended application."]
775          [(15)] (11) IFC, Chapter 9, Section [904.12.5.2] 904.13.5.2, Extinguishing system
776     service, is amended to add the following: "Exception: Automatic fire extinguishing systems
777     located in occupancies where usage is limited and less than six consecutive months may be
778     serviced annually if the annual service is conducted immediately before the period of usage,
779     and approval is received from the AHJ."
780          [(16)] (12) IFC, Chapter 9, Section 905.3.9 is a new subsection as follows: "Open
781     Parking Garages. Open parking garages shall be equipped with an approved Class I manual
782     standpipe system when fire department access is not provided for firefighting operations to
783     within 150 feet of all portions of the open parking garage as measured from the approved fire
784     department vehicle access. Class I manual standpipe shall be accessible throughout the parking
785     garage such that all portions of the parking structure are protected within 150 feet of a hose
786     connection.
787          Exception: Open parking garages equipped throughout with an automatic sprinkler
788     system in accordance with Section 903.3.1.1."
789          [(17) IFC, Chapter 9, Section 905.8, Dry Standpipes, Exception is deleted and
790     rewritten as follows: "Where subject to freezing conditions and approved by the fire code
791     official."]
792          [(18)] (13) IFC, Chapter 9, Section 905.12, Existing buildings, is deleted.
793          [(19)] (14) In IFC, Chapter 9, Section 906.1, Exception 2 is amended as follows: on
794     line three after the word "6," delete the remainder of the paragraph.
795          [(20)] (15) IFC, Chapter 9, Section 907.2.3 Group E:
796          (a) [The first sentence is deleted and rewritten as follows: "A manual fire alarm system
797     that initiates the occupant notification signal using an emergency voice/alarm communication
798     system that meets the requirements of Section 907.5.2.2, or a manual fire alarm system that
799     initiates an audible and visual occupant notification signal that meets the requirements of
800     Sections 907.4.2.1 and 907.5.2.3, and is installed in accordance with Section 907.6, and with
801     rules made by the Utah Fire Prevention Board in accordance with Title 63G, Chapter 3, Utah
802     Administrative Rulemaking Act, shall be installed in Group E occupancies."] 907.2.3 Group E

803     is deleted and rewritten as follows: "A manual fire alarm system that initiates the occupant
804     notification signal using an emergency voice/alarm communication system that meets the
805     requirements of Section 907.5.2.2, or a manual fire alarm system that initiates an approved
806     audible and visual occupant notification signal that meets the requirements of Sections
807     907.5.2.1, 907.5.2.1.1, 907.5.2.1.2, and 907.5.2.3, and is installed in accordance with Section
808     907.6, and with rules made by the Utah Fire Prevention Board in accordance with Title 63G,
809     Chapter 3, Utah Administrative Rulemaking Act, shall be installed in Group E occupancies.
810     Where automatic fire sprinkler systems or smoke detectors are installed, the fire sprinkler
811     systems and smoke detectors shall be connected to the building fire alarm system."
812          (b) Exception 2, delete entirely and the remaining exceptions are renumbered.
813          (c) Exception number 4.2, [on line five, delete the words, "emergency voice/alarm
814     communication system" and replace with "fire alarm."] is deleted and rewritten as follows:
815     "The fire alarm system will activate on sprinkler water flow."
816          (d) New Sections 907.2.3.1 through 907.2.3.7 are added as follows:
817          "907.2.3.1 Automatic detection devices that detect smoke shall be installed throughout
818     all corridors and spaces open to the corridor at the maximum prescribed spacing of thirty feet
819     on center and no more than fifteen feet from the walls or smoke detectors shall be installed as
820     required in NFPA, Standard 72, Section 17.7.
821          907.2.3.2 Where structures are not protected or are partially protected with an automatic
822     fire sprinkler system, approved automatic smoke detectors shall be installed in accordance with
823     the complete coverage requirements of NFPA, Standard 72.
824          907.2.3.3 An approved key plan drawing and operating instructions shall be posted at
825     the main fire alarm panel which displays the location of all alarm zones and if applicable,
826     device addresses.
827          907.2.3.4 The main panel shall be located in a normally attended area such as the main
828     office or lobby. Location of the Main Panel other than as stated above, shall require the review
829     and authorization of the State Fire Marshal Division. Where location as required above is not
830     possible, an electronically supervised remote annunciator from the main panel shall be located
831     in a supervised area of the building. The remote annunciator shall visually indicate system
832     power status, alarms for each zone, and give both visual and audible indication of trouble
833     conditions in the system. All indicators on both the main panel and remote annunciator shall be

834     adequately labeled.
835          907.2.3.5 All system wiring shall be as follows:
836          (A) The initiating device circuits shall be designated and installed Class A as defined in
837     NFPA Standard 72.
838          (B) The notification appliance circuits shall be designated, and installed Class A as
839     defined in NFPA Standard 72.
840          (C) Signaling line circuits shall be designated and installed Class A loop as defined in
841     NFPA Standard 72.
842          907.2.3.6 Fan Shutdown shall be as follows:
843          (A) Fan shut down shall be as required in the International Mechanical Code, Chapter
844     6, Section 606.
845          (B) Duct detectors required by the International Mechanical Code shall be
846     interconnected and compatible with the fire alarm system."
847          (16) In IFC, Chapter 9, a new Section 907.5.2.3.4 is added as follows: "907.5.2.3.4
848     Special Education Classrooms. Visible and audible alarm notification appliances in Special
849     Education classrooms may be replaced with a solid red light when approved by the fire code
850     official."
851          [(21)] (17) IFC, Chapter 9, Section 907.8, Inspection, testing, and maintenance, is
852     amended to add the following sentences at the end of the section: "Increases in nuisance alarms
853     shall require the fire alarm system to be tested for sensitivity. Fire alarm systems that continue
854     after sensitivity testing with unwarranted nuisance alarms shall be replaced as directed by the
855     AHJ."
856          [(22)] (18) IFC, Chapter 9, [Section 915, Carbon Monoxide Detection, is deleted and
857     rewritten as follows:] Section 915.2.3, Group E occupancies and Exception is deleted and
858     replaced with the following:
859          ["915. Carbon Monoxide Detection.]
860          [915.1 Where required.]
861          [Group I-1, I-2, I-4, and R occupancies located in a building containing a fuel-burning
862     appliance or in a building that has an attached garage shall be equipped with single-station
863     carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL
864     2034 or UL 2075 and be installed and maintained in accordance with NFPA 720 and the

865     manufacturer's instructions. An open parking garage, as defined in Chapter 2, or an enclosed
866     parking garage, ventilated in accordance with Section 404 of the International Mechanical
867     Code, shall not be considered an attached garage. A minimum of one carbon monoxide alarm
868     shall be installed on each habitable level.]
869          [915.2 Interconnection.]
870          [Where more than one carbon monoxide alarm is required to be installed within Group
871     I-1, I-2, I-4, or R occupancies, the carbon monoxide alarm shall be interconnected in such a
872     manner that the activation of one alarm will activate all of the alarms. Physical interconnection
873     of carbon monoxide alarms shall not be required where listed wireless alarms are installed and
874     all alarms sound upon activation of one alarm. The alarm shall be clearly audible in all
875     bedrooms over background noise levels with all intervening doors closed.]
876          [915.3 Power source.]
877          [In new construction, required carbon monoxide alarms shall receive their primary
878     power from the building wiring where such wiring is served from a commercial source and
879     shall be equipped with a battery backup. Carbon monoxide alarms with integral strobes that are
880     not equipped with battery backup shall be connected to an emergency electrical system. Carbon
881     monoxide alarms shall emit a signal when the batteries are low. Wiring shall be permanent and
882     without a disconnecting switch other than as required for overcurrent protection.]
883          [Exceptions.]
884          [1. Carbon monoxide alarms are not required to be equipped with battery backup where
885     they are connected to an emergency electrical system.]
886          [2. Hard wiring of carbon monoxide alarms in existing areas shall not be required
887     where the alterations or repairs do not result in the removal of interior wall or ceiling finishes
888     exposing the structure. Unless there is an attic, crawl space, or basement available that could
889     provide access for hard wiring, without the removal of interior finishes.]
890          [915.4 Group E.]
891          [A carbon monoxide detection system shall be installed in new buildings that contain
892     Group E occupancies in accordance with this section. A carbon monoxide detection system
893     shall be installed in existing buildings that contain Group E occupancies in accordance with
894     IFC, Chapter 11, Section 1103.9.]
895          [915.4.1 Where required.]

896          [In Group E occupancies, a carbon monoxide detection system shall be provided where
897     a fuel-burning appliance, a fuel-burning fireplace, or a fuel-burning forced air furnace is
898     present.]
899          [915.4.2 Detection equipment.]
900          [Each carbon monoxide detection system shall be installed in accordance with NFPA
901     720 and the manufacturer's instructions, and be listed, for single station detectors, as complying
902     with UL 2034, and for system detectors, as complying with UL 2075.]
903          [915.4.3 Combination detectors.]
904          [A combination carbon monoxide/smoke detector is an acceptable alternative to a
905     carbon monoxide detection system if the combination carbon monoxide/smoke detector is
906     listed in accordance with UL 2075 and UL 268.]
907          [915.4.4 Power source.]
908          [Each carbon monoxide detection system shall receive primary power from the building
909     wiring if the wiring is served from a commercial source. If primary power is interrupted, each
910     carbon monoxide detection system shall receive power from a battery. Wiring shall be
911     permanent and without a disconnecting switch other than that required for over-current
912     protection.]
913          [915.4.5 Maintenance.]
914          [Each carbon monoxide detection system shall be maintained in accordance with NFPA
915     720. A carbon monoxide detection system that becomes inoperable or begins to produce
916     end-of-life signals shall be replaced."]
917          "915.2.3 Group E Occupancies. Carbon monoxide detectors shall be installed in the
918     following areas within Group E occupancies:
919          (1) Boiler rooms, furnace rooms, and similar rooms, or in adjacent areas where carbon
920     monoxide is likely to spread. (The installation of carbon monoxide detectors in boiler rooms
921     and furnace rooms may cause a false alarm problem. Locating these detectors in adjacent
922     spaces where the carbon monoxide is likely to spread may be a better option.)
923          (2) Home economics rooms with gas appliances.
924          (3) School kitchens with gas appliances. (Commercial kitchens).
925          (4) Arts rooms and other areas with a gas kiln or open flame.
926          (5) Gas roof top units, and other carbon monoxide producing HVAC units, one per

927     zone. (The zone shall be the area covered by the HVAC unit.)
928          (6) In areas with gas wall units.
929          (7) In areas with a gas water heater or boiler.
930          (8) Areas with a forge or foundry.
931          (9) Metal shop or auto shop areas or in adjacent areas where carbon monoxide is likely
932     to spread. (The installation of carbon monoxide detectors in metal shop or auto shop areas may
933     cause a false alarm problem. Locating these detectors in adjacent spaces, i.e. class rooms or
934     corridors, where the carbon monoxide is likely to spread from these spaces may be a better
935     option.)
936          (10) Labs with open flame.
937          (11) HVAC units drawing outside air that could be contaminated with carbon
938     monoxide.
939          (12) Other areas with an open flame or fuel fired appliance.
940          (F) 915.2.3.1 Carbon monoxide alarm signals shall be automatically transmitted to an
941     onsite location that is staffed by school personnel.
942          Exception: Carbon monoxide alarm signals shall not be required to be automatically
943     transmitted to an onsite location that is staffed by school personnel in Group E occupancies
944     with an occupant load of 30 or less."
945          (19) In IFC, Chapter 9, a new Section 915.7 is added as follows:
946          "915.7 Carbon Monoxide Systems in Group E Occupancies. Carbon monoxide systems
947     may be part of a fire alarm system or standalone system.
948          915.7.1 Power and Wiring.
949          915.7.1.1 Power. Carbon monoxide detection systems shall require a primary and
950     secondary power source.
951          915.7.1.2 Wiring. Class "A" wiring is required when the carbon monoxide system is
952     part of, or connected to, a fire alarm system. Standalone carbon monoxide detection systems
953     may use Class "B" wiring. All wiring shall be Class "A" or "B".
954          915.7.2 Equipment Shut Down. Equipment and appliances that are producing carbon
955     monoxide shall shut down automatically in the zone involved upon carbon monoxide system
956     activation.
957          915.7.3 Notification.

958          915.7.3.1 Local Alarm. Each occupied space shall sound an audible alarm when
959     detecting carbon monoxide at a level in excess of 70 ppm for one hour.
960          915.7.3.2 General Alarm. A blue strobe, visual alarm, is required in a normally
961     occupied location, similar to the administrative offices, when carbon monoxide is detected in
962     the facility in excess of 70 ppm for one hour.
963          915.7.3.2.1 The general alarm shall require a manual reset following an alarm
964     activation.
965          915.7.3.3 Digital Notification. Portable carbon monoxide detectors, with digital read
966     out indicating parts per million of carbon monoxide, in a space to determine the level of hazard
967     in a given space.
968          915.7.4 Monitoring. System monitoring is not required. If the system is monitored, the
969     signal should be a supervisory signal indicating carbon monoxide.
970          915.7.5 Inspection.
971          915.7.5.1 The carbon monoxide detection system shall be tested in the presence of a
972     Deputy or Special Deputy of the State Fire Marshal Division. The Deputy shall require "spot
973     testing" of the system and its components.
974          915.7.5.2 Before requesting final inspection and approval, the installing contractor shall
975     test each component of the system and issue a statement of compliance, in writing, to the State
976     Fire Marshal Division that the carbon monoxide detection system has been installed in
977     accordance with approved plans and has been tested in accordance with the manufacturers
978     specifications, and the appropriate installation standard.
979          915.7.5.3 Systems shall be tagged with the State approved tag for fire alarm systems,
980     upon final approval and shall be inspected and tagged annually by an individual certified as a
981     Master Fire Alarm Technician, by the State Fire Marshal Division.
982          915.7.6 Evacuation. The affected area within Group E Occupancies shall be evacuated
983     when carbon monoxide is detected at a level in excess of 70 ppm for one hour in that area."
984          Section 9. Section 15A-5-205 is amended to read:
985          15A-5-205. Amendments and additions to IFC related to means of egress and
986     special processes and uses.
987          [(1) In IFC, Chapter 10, Section 1008.2.1, Illumination level under normal power,
988     delete exception.]

989          [(2) In IFC, Chapter 10, Section 1010.1.9, Door operations, a new exception is added
990     as follows: "Exception: Group E occupancies for purposes of a lockdown or a lockdown drill in
991     accordance with Section 1010.1.9.6 Exception 5."]
992          [(3) In IFC, Chapter 10, Section 1010.1.9.2, Hardware height, "Exception:" is deleted
993     and replaced with "Exceptions: 1."]
994          [(4) In IFC, Chapter 10, Section 1010.1.9.2, Hardware height, Exception 2 is added as
995     follows: "2. Group E occupancies for purposes of a lockdown or a lockdown drill may have
996     one lock below 34 inches in accordance with Section 1010.1.9.6 Exception 5."]
997          [(5) In IFC, Chapter 10, Section 1010.1.9.4, Locks and latches, Item 7 is added after
998     the existing Item 6 as follows: " 7. Group E occupancies for purposes of a lockdown or a
999     lockdown drill in accordance with Section 1010.1.9.6 Exception 5."]
1000          [(6) In IFC, Chapter 10, Section 1010.1.9.5, Bolt locks, Exception 6 is added after the
1001     existing Exception 5 as follows: "6. Group E occupancies for purposes of a lockdown or a
1002     lockdown drill in accordance with Section 1010.1.9.6 Exception 5." (7) In IFC, Chapter 10,
1003     Section 1010.1.9.6, Unlatching, Exception 5 is added after the existing Exception 4 as follows:
1004     "5. Group E occupancies may have a second lock on classrooms for purposes of a lockdown or
1005     lockdown drill, if:]
1006          [5.1 The application of the lock is approved by the code official.]
1007          [5.2 The unlatching of any door or leaf does not require more than two operations.]
1008          [5.3 The lock can be released from the opposite side of the door on which it is
1009     installed.]
1010          [5.4 The lock is only applied during lockdown or during a lockdown drill.]
1011          [5.5 The lock complies with all other state and federal regulations, including the
1012     Americans with Disabilities Act of 1990, 42 U.S.C. Sec. 12101 et seq."]
1013          [(8)] (1) IFC, Chapter 10, Section [1010.1.9.7] 1010.2.14, Controlled egress doors in
1014     Groups I-1 and I-2, after existing Item 8 add Item 9 as follows: "9. The secure area or unit with
1015     special egress locks shall be located at the level of exit discharge in Type V construction."
1016          [(9)] (2) [In] IFC, Chapter 10, Section [1010.1.9.8.1] 1010.2.13.1, Delayed egress
1017     locking system, Item 9 is added after the existing Item 8 as follows: "9. The secure area or unit
1018     with delayed egress locks shall be located at the level of exit discharge in Type V
1019     construction."

1020          [(10)] (3) [In] IFC, Chapter 10, Section [BE] 1011.5.2, Riser height and tread depth,
1021     Exception 3 is deleted and replaced with the following: "3. In Group R-3 occupancies, within
1022     dwelling units in Group R-2 occupancies, and in Group U occupancies that are accessory to a
1023     Group R-3 occupancy, or accessory to individual dwelling units in Group R-2 occupancies, the
1024     maximum riser height shall be 8 inches (203 mm) and the minimum tread depth shall be 9
1025     inches (229 mm). The minimum winder tread depth at the walk line shall be 10 inches (254
1026     mm), and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than
1027     0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways
1028     with solid risers where the tread depth is less than 10 inches (254 mm)."
1029          [(11)] (4) IFC, Chapter 10, Section [BE] 1011.11, Handrails, is amended to add the
1030     following exception: " [5.] 6. In occupancies in Group R-3, as applicable in Section 1014 and
1031     in occupancies in Group U, which are accessory to an occupancy in Group R-3, as applicable in
1032     Section 1014, handrails shall be provided on at least one side of stairways consisting of four or
1033     more risers."
1034          [(12) IFC, Chapter 10, Section 1013.5, Internally illuminated exit signs, delete and
1035     rewrite the last sentence to read "Exit signs shall be illuminated at all times, including when the
1036     building is not fully occupied."]
1037          [(13) IFC, Chapter 10, Section 1025, Luminous Egress Path Markings, is deleted.]
1038          [(14) IFC, Chapter 10, Section 1029.15, Seat stability, delete Exception 2 and
1039     renumber exceptions.]
1040          [(15)] (5) IFC, Chapter 10, Section [1031.2.1] 1032.2.1, Security devices and egress
1041     locks, is amended to add the following: On line three, after the word "fire", add the words "and
1042     building."
1043          Section 10. Section 15A-5-205.5 is amended to read:
1044          15A-5-205.5. Amendments to Chapters 11 and 12 of IFC.
1045          (1) For IFC, Chapter 11, Construction Requirements for Existing Buildings:
1046          (a) [In] IFC, Chapter 11, Section 1103.2, Emergency Responder [Radio]
1047     Communication Coverage in Existing Buildings, is amended as follows: On line two after the
1048     title, the following is added: "When required by the fire code official".
1049          (b) IFC, Chapter 11, Section 1103.5.1, Group A-2, is deleted and replaced with the
1050     following:

1051          "1103.5.1 Group A-2. An automatic fire sprinkler system shall be provided throughout
1052     existing Group A-2 occupancies where indoor pyrotechnics are used."
1053          (c) IFC, Chapter 11, Section 1103.6, Standpipes, is deleted.
1054          (d) [In] IFC, Chapter 11, 1103.7, Fire Alarm Systems, is deleted and rewritten as
1055     follows: "1103.7, Fire Alarm Systems[.]. The following shall have an approved fire alarm
1056     system installed in accordance with Utah Administrative Code, R710-4, Buildings Under the
1057     Jurisdiction of the [State] Utah Fire Prevention Board:
1058          1. a building with an occupant load of 300 or more persons that is owned or operated
1059     by the state;
1060          2. a building with an occupant load of 300 or more persons that is owned or operated
1061     by an institution of higher education; and
1062          3. a building with an occupant load of 50 or more persons that is owned or operated by
1063     a school district, private school, or charter school.
1064          Exception: the requirements of this section do not apply to a building designated as an
1065     Institutional Group I (as defined in IFC 202) occupancy."
1066          (e) IFC, Chapter 11, 1103.7.1 Group E, 1103.7.2 Group I-1, 1103.7.3 Group I-2,
1067     1103.7.4 Group I-3, 1103.7.5 Group R-1, 1103.7.5.1 Group R-1 hotel and motel manual fire
1068     alarm system, 1103.7.5.1.1 Group R-1 hotel and motel automatic smoke detection system,
1069     1103.7.5.2 Group R-1 boarding and rooming houses manual fire alarm system, 1103.7.5.2.1
1070     Group R-1 boarding and rooming houses automatic smoke detection system, 1103.7.6 Group
1071     R-2 are deleted.
1072          (f) IFC, Chapter 11, Section 1103.5.4, High-rise buildings, is amended as follows: On
1073     line two, delete "not been adopted" and replace with "been adopted."
1074          [(f)] (g) IFC, Chapter 11, Section 1103.9, Carbon monoxide alarms, is deleted and
1075     rewritten as follows:
1076          "1103.9 Carbon Monoxide Detection.
1077          Existing Groups E, I-1, I-2, I-4, and R occupancies shall be equipped with carbon
1078     monoxide detection in accordance with Section 915."
1079          (2) For IFC, Chapter 12, Energy Systems:
1080          (a) Delete the section title ["1204.2.1] "1205.2.1 Solar photovoltaic systems for Group
1081     R-3 buildings" and replace with the section title ["1204.2.1] "1205.2.1 Solar photovoltaic

1082     systems for Group R-3 and buildings constructed in accordance with IRC."
1083          (b) Section [1204.2.1] 1205.2.1, Solar photovoltaic systems for Group R-3 buildings,
1084     Exception 1 is deleted, Exception 2 is renumbered to 1 and a second exception is added as
1085     follows: "2. Reduction in pathways and clear access width are permitted where a rational
1086     approach has been used and the reduction is warranted and approved by the Fire Code
1087     Official."
1088          (c) Section [1204.3.1] 1205.3.1 Perimeter pathways, and [1204.3.2] 1205.3.2 Interior
1089     pathways, are deleted and rewritten as follows: "1204.3.1 Perimeter pathways. There shall be a
1090     minimum three foot wide (914 mm) clear perimeter around the edges of the roof. The solar
1091     installation shall be designed to provide designated pathways. The pathways shall meet the
1092     following requirements:
1093          1. The pathway shall be over areas capable of supporting the live load of fire fighters
1094     accessing the roof.
1095          2. The centerline axis pathways shall be provided in both axes of the roof. Centerline
1096     axis pathways shall run where the roof structure is capable of supporting the live load of fire
1097     fighters accessing the roof.
1098          3. Smoke and heat vents required by Section 910.2.1 or 910.2.2 shall be provided with
1099     a clear pathway width of not less than three feet (914 mm) to the vents.
1100          4. Access to roof area required by Section 504.3 or 1011.12 shall be provided with a
1101     clear pathway width of not less than three feet (914 mm) around access opening and at least
1102     three feet (914 mm) clear pathway to parapet or roof edge."
1103          (d) Section [1204.3.3] 1205.3.3, Smoke ventilation, is deleted and rewritten as follows:
1104     ["1204.3.2] "1205.3.2, Smoke ventilation. The solar installation shall be designed to meet the
1105     following requirements:
1106          1. Arrays shall be no greater than 150 feet (45720 mm) by 150 feet (45720 mm) in
1107     distance in either axis in order to create opportunities for fire department smoke ventilation
1108     operations.
1109          2. Smoke ventilation options between array sections shall be one of the following:
1110          2.1 A pathway six feet (1829 mm) or greater in width.
1111          2.2 A pathway three feet (914 mm) or greater in width and bordering roof skylights or
1112     smoke and heat vents when required by Section 910.2.1 or Section 910.2.2.

1113          2.3 Smoke and heat vents designed for remote operation using devices that can be
1114     connected to the vent by mechanical, electrical, or any other suitable means, protected as
1115     necessary to remain operable for the design period. Controls for remote operation shall be
1116     located in a control panel, clearly identified and located in an approved location.["]
1117          3. Where gravity-operated dropout smoke and heat vents occur, a pathway three feet
1118     (914 mm) or greater in width on not fewer than one side."
1119          Section 11. Section 15A-5-205.6 is amended to read:
1120          15A-5-205.6. Amendments and additions to Chapter 33 of IFC.
1121          (1) IFC, Chapter 33, Section [3310.1] 3311.1, Required access, is deleted and rewritten
1122     as follows:
1123          ["3310.1] "3311.1 Required access.
1124          [3310.1.1] 3311.1.1 Approved vehicle access. Approved vehicle access for fire fighting
1125     shall be provided as described in Chapter 5 of this code to all construction or demolition sites.
1126          [3310.1.2] 3311.1.2 Fire department connections. Vehicle access shall be provided to
1127     within 100 feet of temporary or permanent fire department connections.
1128          [3310.1.3] 3311.1.3 Type of access. Vehicle access shall be provided by either
1129     temporary or permanent roads.
1130          [3310.1.3.1] 3311.3.1 Temporary road requirements. Temporary roads shall be
1131     constructed with a minimum of site specific required structural fill for permanent roads and
1132     road base, or other approved material complying with local standards.
1133          [3310.1.3.2] 3311.3.2 Reports. Compaction reports may be required. An engineer's
1134     review and certification of a temporary fire department access road is not required.
1135          [3310.1.3.3] 3311.3.3 Local jurisdictions. If an improvement completion assurance has
1136     been posted in accordance with Section 10-9a-604.5, a local jurisdiction may not require
1137     permanent roads, or asphalt or concrete on temporary roads, before final approval of the
1138     structure served by the road.
1139          [3310.1.4] 3311.1.4 Maintenance. Temporary roads shall be maintained until permanent
1140     fire apparatus access roads are available.
1141          [3310.1.5] 3311.1.5 Time line. Temporary or permanent fire department access roads
1142     shall be functional before construction above the foundation begins and before an appreciable
1143     amount of combustible construction materials are on site."

1144          (2) IFC, Chapter 33, Section [3310.2] 3311.2, Key boxes, is deleted.
1145          Section 12. Section 15A-5-206 is amended to read:
1146          15A-5-206. Amendments and additions to IFC related to hazardous materials,
1147     explosives, fireworks, and flammable and combustible liquids.
1148          (1) For IFC, Hazardous Materials - General Provisions, Chapter 50, Table 5003.1.1(1),
1149     Maximum Allowable Quantity per Control Area of Hazardous Materials Posing a Physical
1150     Hazard, apply footnote d to Explosives, Storage, Solid Pounds.
1151          (2) [For] IFC, Explosives and Fireworks, IFC, Chapter 56, Section 5601.1.3,
1152     Fireworks, Exception 4 is amended to add the following sentence at the end of the exception:
1153     "The use of fireworks for display and retail sales is allowed as set forth in Utah Code, Title 53,
1154     Chapter 7, Utah Fire Prevention and Safety Act, Sections 53-7-220 through 53-7-225; Utah
1155     Code, Title 11, Chapter 3, County and Municipal Fireworks Act; Utah Administrative Code,
1156     R710-2; and the State Fire Code."
1157          (3) For IFC, Chapter 57, Flammable and Combustible Liquids:
1158          (a) IFC, Chapter 57, Section 5701.4, Permits, is amended to add the following at the
1159     end of the section: "The owner of an underground tank that is out of service for longer than one
1160     year shall receive a Temporary Closure Notice from the Department of Environmental Quality,
1161     and a copy shall be given to the AHJ."
1162          (b) IFC, Chapter 57, Section 5706.1, General, is amended to add the following special
1163     operation: "8. Sites approved by the AHJ".
1164          (c) IFC, Chapter 57, Section 5706.2, Storage and dispensing of flammable and
1165     combustible liquids on farms and construction sites, is amended to add the following: On line
1166     five, after the words "borrow pits", add the words "and sites approved by the AHJ".
1167          (4) For IFC, Chapter 61, Liquefied Petroleum Gas:
1168          (a) IFC, Chapter 61, Section 6101.2, Permits, is amended as follows: On line two, after
1169     the word ["105.7] "105.6", add "and the adopted LP Gas rules".
1170          (b) IFC, Chapter 61, Section 6103.1, General, is deleted and rewritten as follows:
1171     "General. LP Gas equipment shall be installed in accordance with NFPA 54, NFPA 58, the
1172     adopted LP Gas rules, and the International Fuel Gas Code, except as otherwise provided in
1173     this chapter."
1174          (c) IFC, Chapter 61, Section 6104.3, Location of LP-Gas Containers, Table 6104.3,

1175     Location of LP-Gas Containers, amends column heading "Minimum Separation Between
1176     LP-Gas Containers and Buildings, Public Ways or Lot Lines of Adjoining Property" and
1177     footnote "g" by deleting and replacing with the following: "Minimum separation between
1178     LP-Gas containers and buildings, or lot lines of adjoining property that can be built on."
1179          [(c)] (d) Chapter 61, Section 6109.12, Location of storage outside of buildings, is
1180     amended as follows: In Table 6109.12, Doorway or opening to a building with two or more
1181     means of egress, with regard to quantities 720 or less and 721 -- 2,500, the currently stated "5"
1182     is deleted and replaced with "10".
1183          [(d)] (e) IFC, Chapter 61, Section 6109.15.1, Automated cylinder exchange stations, is
1184     amended as follows: Item # 4 is deleted[.] and replaced with the following: "Item #4 Electrical
1185     equipment inside of a cabinet storing cylinders, including but not limited to electronics
1186     associated with vending operations, shall comply with requirements for Class I, Division 2,
1187     equipment in accordance with NFPA 70."
1188          [(e)] (f) IFC, Chapter 61, Section 6110.1, [Temporarily out of service] Removed from
1189     service, is amended as follows: On line two, after the word "discontinued", add the words "for
1190     more than one year or longer as allowed by the AHJ,".
1191          (g) IFC, Chapter 61, Section 6110.2, Removal from site is deleted.
1192          Section 13. Section 15A-5-302 is amended to read:
1193          15A-5-302. Amendments and additions to NFPA related to National Fire Alarm
1194     and Signaling Code.
1195          For NFPA 72, National Fire Alarm and Signaling Code, [2016] 2019 edition:
1196          [(1) NFPA 72, Chapter 2, Section 2.2, NFPA Publications, is amended to add the
1197     following NFPA standard: "NFPA 20, Standard for the Installation of Stationary Pumps for
1198     Fire Protection, 2016 edition."]
1199          [(2)] (1) NFPA 72, Chapter 10, Section 10.5.1, System Designer, Subsection
1200     10.5.1.3(2), is deleted and rewritten as follows: "Certification by the National Institute for
1201     Certification in Engineering Technologies at level III or IV in Fire Alarm Systems."
1202          [(3) NFPA 72, Chapter 10, Section 10.5.2, System Installer, Subsection 10.5.2.3(2), is
1203     deleted and rewritten as follows: "Certification by the National Institute for Certification in
1204     Engineering Technologies at level III or IV in Fire Alarm Systems."]
1205          [(4)] (2) NFPA 72, Chapter 10, Section 10.5.3, Inspection, Testing, and [Maintenance]

1206     Service Personnel, Subsection 10.5.3.1, Inspection Personnel, is deleted and rewritten as
1207     follows:
1208          "Service personnel shall be qualified and experienced in the inspection, testing, and
1209     maintenance of fire alarm systems. Qualified personnel shall meet the certification
1210     requirements stated in rule made by the [State] Utah Fire Prevention Board in accordance with
1211     Title 63G, Chapter 3, Utah Administrative Rulemaking Act."
1212          [(5)] (3) NFPA 72, Chapter 10, Section 10.12, Fire Alarm Signal Deactivation,
1213     Subsection [10.13.2] 10.12.2, is amended to add the following sentence: "When approved by
1214     the AHJ, the audible notification appliances may be deactivated during the investigation mode
1215     to prevent unauthorized reentry into the building."
1216          [(6) In NFPA 72, Chapter 23, Section 23.8.5.9, Signal Initiation -- Fire Pump,
1217     Subsection 23.8.5.9.3 is added as follows: "Automatic fire pumps shall be supervised in
1218     accordance with NFPA 20, Standard for the Installation of Stationary Pumps for Fire
1219     Protection, and the AHJ."]
1220          [(7) NFPA 72, Chapter 26, Section 26.3.4, Indication of Central Station Service,
1221     Subsection 26.3.4.7 is amended as follows: On line two, after the word "notified", insert the
1222     words "without delay" and delete the words, "within 30 calendar days".]
1223          Section 14. Section 15A-5-304 is amended to read:
1224          15A-5-304. Amendments and additions to NFPA related to Automatic Fire
1225     Sprinklers Systems.
1226          (1) NFPA 13, Installation of Sprinkler Systems, [2016] 2019 edition.
1227          (a) NFPA 13, Chapter [8, Section 15.22, System Subdivision] 16, Section 16.9.11,
1228     Floor Control Valve Assemblies, Subsection 16.9.11.5, is deleted and rewritten as follows:
1229          ["8.15.22] "16.9.11.5, System Subdivision - Floor/Zone Control Valves.
1230          Individual floor/zone control valves shall be used at the riser at each floor for
1231     connections to piping serving floor areas in excess of 5,000 square feet."
1232          (b) NFPA 13, Chapter 8, Section [8.17.1.1] 16.11.2.1, Local Waterflow Alarms, is
1233     amended by adding a new subsection as follows:
1234          ["8.17.1.1.1] "16.11.2.1.1 Single Tenant Occupancies.
1235          [An] When a fire alarm system is not required by IFC, Section 907.2, an approved
1236     audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of the building, in

1237     a normally occupied location, to alert the occupants of the fire sprinkler system activation."
1238          (c) NFPA 13, Chapter 8, Section [8.17.1.1] 16.11.2.1, Local Waterflow Alarms, is
1239     amended by adding a new subsection as follows:
1240          ["8.17.1.1.2] "16.11.2.1.2 Multi-Tenant Occupancies.
1241          [An] When a fire alarm system is not required by IFC, Section 907.2, an approved
1242     audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each tenant
1243     space, in a normally occupied location, to alert the occupants of the fire sprinkler system
1244     activation."
1245          (d) NFPA 13, Chapter 8, Section [8.17.1.1] 16.11.2.1, Local Waterflow Alarms, is
1246     amended by adding a new subsection as follows:
1247          ["8.17.1.1.3] "16.11.2.1.3 Exterior Waterflow Alarm.
1248          An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the
1249     exterior of the building in a location approved by the AHJ."
1250          (2) NFPA 13D, Installation of Sprinkler Systems in One- and Two-Family Dwellings
1251     and Manufactured Homes, [2013] 2019 edition.
1252          (a) NFPA 13D, Chapter 7, Section 7.6, Alarms, is amended by adding a new
1253     subsection as follows:
1254          "7.6.1 Exterior Waterflow Alarm.
1255          When an alarm initiating device is included, an approved audible/visual waterflow
1256     alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by
1257     the AHJ."
1258          (b) NFPA 13D, Chapter 7, Section 7.6, Alarms, is amended by adding a new
1259     subsection as follows:
1260          "7.6.2 Interior Alarm.
1261          When an alarm initiating device is included, an interior fire alarm notification appliance
1262     is also required to sound throughout the dwelling. An approved audible sprinkler flow alarm to
1263     alert the occupants of the dwelling in a normally occupied location when the flow switch is
1264     activated must be provided."
1265          (3) NFPA, Standard 13R, Installation of Sprinkler Systems in Residential Occupancies
1266     up to and Including Four Stories in Height, [2013] 2019 edition.
1267          (a) NFPA 13R, Chapter 6, Section 6.8, Valves, is amended by adding a new subsection

1268     as follows:
1269          ["6.8.9] "6.8.11 Floor/Zone Control Valves.
1270          Individual floor/zone control valves shall be used at the riser at each floor for
1271     connections to piping serving floor areas in excess of 5,000 square feet or arranged in a manner
1272     acceptable to the AHJ."
1273          (b) NFPA 13R, Chapter 6, Section 16, Alarms, is amended by adding a new subsection
1274     as follows:
1275          "6.16.1.1 Local Waterflow Alarms.
1276          [An approved audible/visual waterflow alarm (horn/strobe)] When a fire alarm system
1277     is not required by IFC, Section 907.2, an approved notification appliance indicating waterflow
1278     shall be provided in the interior of each residential unit/tenant space, in a normally occupied
1279     location, to alert the occupants of the fire sprinkler system activation."
1280          (c) NFPA 13R, Chapter 6, Section 16, Alarms, is amended by adding a new subsection
1281     as follows:
1282          "6.16.1.2 Exterior Waterflow Alarm.
1283          An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the
1284     exterior of the building in a location approved by the AHJ."
1285          (4) NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based
1286     Fire Protection Systems, 2020 edition.
1287          NFPA 25, Section 5.3.4.4.1, the first line is deleted and replaced with the following:
1288          "For system antifreeze installed prior to July 1, 2023, listed antifreeze shall not be
1289     required, where all of the following conditions are met:"
1290          (5) NFPA 72, National Fire Alarm and Signaling Code, 2019 edition.
1291          NFPA 72, a new Section 18.1.1.1 is added as follows:
1292          "The fire code official may modify the requirements of this chapter in areas of
1293     educational occupancies used exclusively for special education students."
1294          Section 15. Repealer.
1295          This bill repeals:
1296          Section 15A-2a-101, Title.
1297          Section 15A-2a-102, Definitions.
1298          Section 15A-2a-201, Amendments to Chapter 4 of IBC.

1299          Section 15A-2a-202, Amendments to Chapter 5 of IBC.
1300          Section 15A-2a-203, Amendments to Chapter 6 of IBC.
1301          Section 15A-2a-204, Amendments to Chapter 7 of IBC.
1302          Section 15A-2a-301, Amendments to Chapter 7 of IFC.
1303          Section 15A-2a-302, Amendments to Chapters 9 and 33 of IFC.
1304          Section 15A-2a-401, Reference Standards.