7 LONG TITLE
8 General Description:
9 This bill modifies a provision amending the state construction code.
10 Highlighted Provisions:
11 This bill:
12 . modifies a provision requiring an engineer evaluation of certain buildings built
13 before 1975;
14 . S. temporarily .S eliminates a requirement that the evaluation occur when the building
14a is undergoing
15 reroofing or an alteration of or repair to certain features; and
16 . replaces that requirement with a S. temporary .S requirement that the evaluation
16a occur when the
17 building is undergoing structural alterations or repairs, and specifies what is not
18 included in structural alterations or repairs.
19 Money Appropriated in this Bill:
20 None
21 Other Special Clauses:
22 None
23 Utah Code Sections Affected:
24 AMENDS:
25 15A-3-113, as enacted by Laws of Utah 2011, Chapter 14
26
27 Be it enacted by the Legislature of the state of Utah:
28 Section 1. Section 15A-3-113 is amended to read:
29 15A-3-113. Amendments to Chapters 32 through 35 of IBC.
30 (1) A new section IBC, Section 3401.6, is added as follows: "3401.6 Parapet bracing,
31 wall anchors, and other appendages. S. [
31a constructed before 1975 shall have parapet
32 bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary,
33 etc. evaluated by a licensed engineer when [
34
34a sheathing replacement of 10% or greater, .H or H. other .H structural repairs. Reroofing
34b or
35 water membrane replacement may not be considered a structural alteration or repair for
36 purposes of this section. S. [
36a before 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires,
36b towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when the building is
36c undergoing reroofing or alteration of or repair to the feature. Parapet .S bracing, wall
36d anchors, and appendages S. required by this section .S shall be
37 evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When
38 allowed by the local building official, alternate methods of equivalent strength as referenced in
39 an approved code under Utah Code, Subsection 15A-1-204 (6)(a), will be considered when
40 accompanied by engineer-sealed drawings, details, and calculations. When found to be
41 deficient because of design or deteriorated condition, the engineer's recommendations to
42 anchor, brace, reinforce, or remove the deficient feature shall be implemented.
43 Exceptions:
44 1. Group R-3 and U occupancies.
45 2. Unreinforced masonry parapets need not be braced according to the above stated provisions
46 provided that the maximum height of an unreinforced masonry parapet above the level of the
47 diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times
48 the thickness of the parapet wall. The parapet height may be a maximum of two and one-half
49 times its thickness in other than Seismic Design Categories D, E, or F."
50 (2) IBC, Section 3408.4, is deleted and replaced with the following: "3408.4 Change in
51 Occupancy. When a change in occupancy results in a structure being reclassified to a higher
52 Occupancy Category (as defined in Table 1604.5), or when such change of occupancy results in
53 a design occupant load increase of 100% or more, the structure shall conform to the seismic
54 requirements for a new structure.
55 Exceptions:
56 1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not
57 be required to be met where it can be shown that the level of performance and seismic safety is
58 equivalent to that of a new structure. Such analysis shall consider the regularity, overstrength,
59 redundancy, and ductility of the structure within the context of the existing and retrofit (if any)
60 detailing providing. Alternatively, the building official may allow the structure to be upgraded
61 in accordance with referenced sections as found in an approved code under Utah Code,
62 Subsection 15A-1-204 (6)(a).
63 2. When a change of use results in a structure being reclassified from Occupancy Category I or
64 II to Occupancy Category III and the structure is located in a seismic map area where SDS is
65 less than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not
66 required.
67 3. Where design occupant load increase is less than 25 occupants and the Occupancy Category
68 does not change."
69 (3) In IBC, Section 3411.1, the exception is deleted and replaced with the following:
70 "Exception: Type B dwelling or sleeping units required by Section 1107 of this code are not
71 required to be provided in existing buildings and facilities unless being altered or undergoing a
72 change of occupancy classification."
73 (4) The following referenced standard is added under NFPA in IBC, Chapter 35:
74 | "Number | Title | Referenced in code section number |
75 | 720-09 |
Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment |
907.9" |
77 | "Number | Title | Referenced in code section number |
78 | 2034-2008 |
Standard of Single- and Multiple-station Carbon Monoxide Alarms |
907.9" |
80 the following:
81 | "Number | Title | Referenced in code section number |
82 | 10-10 | Portable Fire Extinguishers |
906.2, 906.3.2, 906.3.4, Table 906.3(1), Table 906.3(2)" |
84 the following:
85 | "Number | Title | Referenced in code section number |
86 | 11-10 | Low Expansion Foam | 904.7" |
88 the following:
89 | "Number | Title | Referenced in code section number |
90 | 12-08 |
Carbon Dioxide Extinguishing Systems |
904.8, 904.11" |
92 the following:
93 | "Number | Title | Referenced in code section number |
94 | 12A-09 |
Halon 1301 Fire Extinguishing Systems |
904.9" |
96 the following:
97 | "Number | Title | Referenced in code section number |
98 | 13-10 | Installation of Sprinkler Systems |
708.2, 903.3.1.1, 903.3.2, 903.3.5.1.1, 903.3.5.3, 904.11, 905.3.4, 907.6.3, 1613.3" |
100 with the following:
101 | "Number | Title | Referenced in code section number |
102 | 13D-10 |
Installation of Sprinkler Systems in One- and Two-family Dwellings and Manufactured Homes |
903.3.1.3, 903.3.5.1.1" |
104 with the following:
105 | "Number | Title | Referenced in code section number |
106 | 13R-10 |
Installation of Sprinkler Systems in Residential Occupancies Up to and Including Four Stories in Height |
903.3.1.2, 903.3.5.1.1, 903.3.5.1.2, 903.4" |
108 the following:
109 | "Number | Title | Referenced in code section number |
110 | 14-10 |
Installation of Standpipe and Hose System |
905.2, 905.3.4, 905.6.2, 905.8" |
112 the following:
113 | "Number | Title | Referenced in code section number |
114 | 17-09 | Dry chemical Extinguishing Systems | 904.5, 904.11" |
116 with the following:
117 | "Number | Title | Referenced in code section number |
118 | 17A-09 | Wet Chemical Extinguishing System | 904.5, 904.11" |
120 the following:
121 | "Number | Title | Referenced in code section number |
122 | 20-10 |
Installation of Stationary Pumps for Fire Protection |
913.1, 913.2.1, 913.5" |
124 the following:
125 | "Number | Title | Referenced in code section number |
126 | 72-10 | National Fire Alarm Code |
901.6, 903.4.1, 904.3.5, 907.2, 907.2.5, 907.2.11, 907.2.13.2, 907.3, 907.3.3, 907.3.4, 907.5.2.1.2, 907.5.3.3, 907.6, 907.6.1, 907.6.5, 907.7, 907.7.1, 907.7.2, 911.1.5, 3006.5, 3007.6" |
128 with the following:
129 | "Number | Title | Referenced in code section number |
130 | 92B-09 |
Smoke Management Systems in Malls, Atria and Large Spaces |
909.8" |
132 with the following:
133 | "Number | Title | Referenced in code section number |
134 | 101-09 | Line Safety Code | 1028.6.2" |
136 with the following:
137 | "Number | Title | Referenced in code section number |
138 | 110-10 |
Emergency and Standby Power Systems |
2702.1" |